5 Preparation

Installer reference guide

9

FTXA25~50(A)(B)2V1B(W)(S)(T)(B)
Daikin room air conditioner
4P518023-3F – 2019.10

5.2.1

Installation site requirements of the
indoor unit

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

INFORMATION

The sound pressure level is less than 70 dBA.

Air flow.

 Make sure nothing blocks the air flow.

Drainage.

  Make  sure  condensation  water  can  be  evacuated

properly.

Wall insulation

. When conditions in the wall exceed 30°C and a

relative  humidity  of  80%,  or  when  fresh  air  is  inducted  into  the
wall,  then  additional  insulation  is  required  (minimum  10  mm
thickness, polyethylene foam).

Wall  strength. 

Check  whether  the  wall  or  the  floor  is  strong

enough to support the weight of the unit. If there is a risk, reinforce
the wall or the floor before installing the unit.

Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
3 metres may NOT be sufficient.

▪ Choose a location where the hot/cold air discharged from the unit

or the operation noise, will NOT disturb anyone.

Fluorescent lights

. When installing a wireless user interface in a

room  with  fluorescent  lights,  mind  the  following  to  avoid
interference:

▪ Install  the  wireless  user  interface  as  close  as  possible  to  the

indoor unit.

▪ Install  the  indoor  unit  as  far  as  possible  from  the  fluorescent

lights.

It  is  NOT  recommended  to  install  the  unit  in  the  following  places
because it may shorten the life of the unit:

▪ Where the voltage fluctuates a lot

▪ In vehicles or vessels

▪ Where acidic or alkaline vapour is present

▪ In  places  where  a  mineral  oil  mist,  spray  or  vapour  may  be

present  in  the  atmosphere.  Plastic  parts  may  deteriorate  and  fall
off or cause water leakage.

▪ In places where the unit would be in the path of direct sunlight.

▪ In bathrooms.

▪ Sound  sensitive  areas  (e.g.  near  a  bedroom),  so  that  the

operation noise will cause no trouble.

WARNING

Do NOT place objects below the indoor and/or outdoor unit
that  may  get  wet.  Otherwise  condensation  on  the  unit  or
refrigerant pipes, air filter dirt or drain blockage may cause
dripping,  and  objects  under  the  unit  may  get  dirty  or
damaged.

Spacing. 

Install the unit at least 1.8 m from the floor and keep the

following  requirements  in  mind  for  distances  from  the  walls  and
the ceiling:

≥50

≥50

≥30

(mm)

Note: 

 Make sure that there are no obstacles within 500 mm under

the signal receiver. They may influence reception performance of the
user interface.

5.3

Preparing refrigerant piping

5.3.1

Refrigerant piping requirements

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Class

L1 liquid piping

L1 gas piping

15~35

Ø6.4

Ø9.5

42+50

Ø6.4

Ø12.7

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

5.3.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

12.7 mm (1/2")

14~16 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

Summary of Contents for FTXA50A2V1BW

Page 1: ...1BW FTXA25A2V1BW FTXA35A2V1BW FTXA42A2V1BW FTXA50A2V1BW CTXA15 A B 2V1BS FTXA20 A B 2V1BS FTXA25 A B 2V1BS FTXA35 A B 2V1BS FTXA42 A B 2V1BS FTXA50 A B 2V1BS CTXA15 A B 2V1BT FTXA20 A B 2V1BT FTXA25 A...

Page 2: ...ing 15 6 4 4 Pipe bending guidelines 15 6 4 5 To flare the pipe end 15 6 4 6 To connect the refrigerant piping to the indoor unit 16 6 5 Connecting the electrical wiring 16 6 5 1 About connecting the...

Page 3: ...rks executed on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the pro...

Page 4: ...e for 1 8 m Floor standing units 1 8 x 2 2 m Wall mounted units 2 2 m Ceiling mounted units 3 Use the graph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 14...

Page 5: ...applicable legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case recharge is required see the nam...

Page 6: ...d When disconnecting the power supply the current carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the term...

Page 7: ...in to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box This chapter describes what you...

Page 8: ...nt E g persons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause...

Page 9: ...ause no trouble WARNING Do NOT place objects below the indoor and or outdoor unit that may get wet Otherwise condensation on the unit or refrigerant pipes air filter dirt or drain blockage may cause d...

Page 10: ...multicore cable for power supply cables 6 Installation 6 1 Overview Installation This chapter describes what you have to do and know on site to install the system Typical workflow Installation typical...

Page 11: ...front grille CAUTION Wear protective gloves 1 Open the front panel Refer to 6 2 1 To open the front panel 410 2 Remove the service cover Refer to 6 2 4 To open the service cover 411 3 Remove the wire...

Page 12: ...ew NOTICE When closing the electrical wiring box cover make sure that the tightening torque does NOT exceed 2 0 0 2 N m 6 3 Installing the indoor unit 6 3 1 Precautions when installing the indoor unit...

Page 13: ...half round needle file NOTICE Do NOT use nippers to remove the pipe port cover as this would damage the front grille 6 3 5 To provide drainage Make sure condensation water can be evacuated properly T...

Page 14: ...right side NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plug when inserting it The drain plug may deteriorate and cause drain leakage from the plug a a 4 mm hexagonal wrench 3 Inse...

Page 15: ...nit Regardless of the period INFORMATION Do NOT open the refrigerant stop valve before checking the refrigerant piping When you need to charge additional refrigerant it is recommended to open the refr...

Page 16: ...ing to the indoor unit 4 Connecting the main power supply 6 5 2 Precautions when connecting the electrical wiring INFORMATION Also read the precautions and requirements in the following chapters Gener...

Page 17: ...t that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block...

Page 18: ...ng plate hooks 4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4 12L accessory 6 6 4 To install the screw covers 1 Open the front panel and turn the flap up 2 Install...

Page 19: ...cified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit to make sure that al...