SiUS091601E
Trial Operation
Trial Operation and Field Settings
116
3. Trial Operation
Outline
Carry out the trial operation in accordance with the operation manual to ensure that all functions
and parts, such as flap movement, are working properly.
Trial operation should be carried out in either cooling or heating operation.
Detail
1. Measure the power supply voltage and make sure that it falls within the specified range.
2. In cooling operation, select the lowest programmable temperature (18°C, 64°F); in heating
operation, select the highest programmable temperature (30°C, 86°F).
Trial operation may be disabled in either operation mode depending on the room
temperature.
After trial operation is complete, set the temperature to a normal level (26 ~ 28°C, 78 ~ 82°F
in cooling, 20 ~ 24°C, 68 ~ 75°F in heating operation).
For protection, the system does not start for 3 minutes after it is turned off.
ARC480 Series
(1) Press the center of
TEMP
button and
OFF
button on the remote controller at the same time.
(2) Select
T
(trial operation) with
TEMP
or
TEMP
button.
(3) Press
FAN
button to enter the trial operation mode.
(4) Press
COOL
or
HEAT
button to start trial operation.
(5) Trial operation terminates in about 30 minutes and switches into the normal mode. To quit trial
operation, press
OFF
button.
(R22999)
(1) (5)
(1) (2)
(4)
(4)
(3)
Summary of Contents for FTX09NMVJU
Page 12: ...SiUS091601E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 15: ...SiUS091601E Specifications 4 Part 2 Specifications 1 Specifications 5...
Page 65: ...SiUS091601E Remote Controller 54 Part 5 Remote Controller 1 FTX Series 55 2 FVXS Series 57...
Page 144: ...Revision History Month Year Version Revised contents 02 2016 SiUS091601E First edition...