Forced Cooling Operation
SiUS091601E
115
Trial Operation and Field Settings
2. Forced Cooling Operation
Indoor Unit
FTX Series
FTXV Series
Item
Forced Cooling
Conditions
The forced cooling operation is allowed when both the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start
Press the forced cooling operation
ON/OFF
button (SW1) on the indoor unit
for 5 seconds.
Command
frequency
09 class: 58 Hz
12/15 class: 30 Hz
End
The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation
ON/OFF
button (SW1) on the indoor unit
again.
3) Press
ON/OFF
button on the remote controller.
Others
Protection functions have priority over all other functions during forced cooling
operation.
(R21069)
ON/OFF
ON/OFF
button (SW1)
(R23005)
ON/OFF
button (SW1)