176
FTX-N/U, FVXS-N, FDMQ-R Series EDUS091558E
3P379970-10C
11
Facility Setting*
(cooling at low outdoor temperature)
This function is limited only for facilities (the target of air conditioning is equipment (such as computer)).
Never use it in a residence or offi ce (the space where there is a human).
*Only for RX, RK, and RXL models.
Cutting jumper 6 (J6)
on the circuit board will expand the operation range down to 5°F (–15°C). However it will stop if the
outdoor temperature drops below –4°F (–20°C) and start back up once the temperature rises again.
1) Remove the top plate of the outdoor unit. (09/12 class: 3 screws, 15/18/24 class: 6 screws)
2) Remove the front plate. (09/12 class: 4 screws, 15/18/24 class: 8 screws)
3) Cut the jumper (J6) of the PCB inside.
CAUTION
•
If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
•
Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
• Do not place humidifi ers or other items which might raise the humidity in rooms where facility settings are being used.
A humidifi er might cause dew jumping from the indoor unit outlet vent.
•
Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.
Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from the liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.
Forced cooling operation
Using the indoor unit ON/OFF switch
Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)
•
Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press the indoor unit ON/OFF switch.
Gas
stop valve
Valve cap
Hexagonal
wrench
Close
Liquid
stop valve
Service port
Using the indoor unit’s remote controller
[For wall mounted units]
1) Press
,
and
at the same time.
2) Press
, then select , press
.
3) Press
to turn on the system.
•
Forced cooling operation will stop automatically after about 30 minutes.
To stop the operation, press
.
HEAT PUMP model
COOLING ONLY model
[For fl oor standing units]
1) Press
and select the COOL operation.
2) Press
to turn on the system.
3) Press
,
and
at the same time.
4) Press
, select “
”, and press
for confi rmation.
•
Forced cooling operation will stop automatically after about 30 minutes. To stop the operation, press
.
CAUTION
•
When pressing the switch, do not touch the terminal block. It has a high voltage, and touching it could cause electric shock.
01_EN_3P379970-10C.indd 11
10/18/2019 9:18:04 AM
Summary of Contents for FTX-N/U
Page 1: ...Heat Pump Split Type Air Conditioners FTX N U FVXS N FDMQ R Series EDUS091558E...
Page 2: ......
Page 17: ...FTX N U FVXS N FDMQ R Series EDUS091558E 15 C 3D123383 FTX24UVJU C 3D123379 FTX18UVJU...
Page 19: ...FTX N U FVXS N FDMQ R Series EDUS091558E 17 3D112919B FDMQ18 24RVJU 3D112918B FDMQ12RVJU...
Page 20: ...18 FTX N U FVXS N FDMQ R Series EDUS091558E 3D049611A BRC082A43 C 3D091305A BRC1E73...
Page 22: ...20 FTX N U FVXS N FDMQ R Series EDUS091558E 3D107983A RXL24UMVJUA 3D123362 RXL18UMVJUA...
Page 25: ...FTX N U FVXS N FDMQ R Series EDUS091558E 23 3D112629A FDMQ12 18 24RVJU...
Page 32: ...30 FTX N U FVXS N FDMQ R Series EDUS091558E 3D107985A RXL24UMVJUA...
Page 59: ...FTX N U FVXS N FDMQ R Series EDUS091558E 57 3D113126 FDMQ18RVJU...
Page 60: ...58 FTX N U FVXS N FDMQ R Series EDUS091558E 3D113128 FDMQ24RVJU...
Page 62: ...60 FTX N U FVXS N FDMQ R Series EDUS091558E 3D113129 FDMQ24RVJU...
Page 65: ...FTX N U FVXS N FDMQ R Series EDUS091558E 63 3D123455 FTX18UVJU 3D100354 FTX15NMVJU...
Page 66: ...64 FTX N U FVXS N FDMQ R Series EDUS091558E 3D094737 FVXS09NVJU 3D074866A FTX24UVJU...
Page 67: ...FTX N U FVXS N FDMQ R Series EDUS091558E 65 3D094777A FVXS15NVJU 3D094766 FVXS12NVJU...
Page 70: ...68 FTX N U FVXS N FDMQ R Series EDUS091558E 3D123453 RXL18UMVJUA 3D100636 RXL15QMVJUA...
Page 71: ...FTX N U FVXS N FDMQ R Series EDUS091558E 69 3D123454 RXL24UMVJUA...
Page 394: ...392 FTX N U FVXS N FDMQ R Series EDUS091558E 1P124687 1A...
Page 395: ...FTX N U FVXS N FDMQ R Series EDUS091558E 393 1P124687 1A...
Page 396: ...394 FTX N U FVXS N FDMQ R Series EDUS091558E 1P124687 1A...
Page 397: ...FTX N U FVXS N FDMQ R Series EDUS091558E 395 1P124687 1A...
Page 401: ...FTX N U FVXS N FDMQ R Series EDUS091558E 399 3P124623 1E 4 Fig 6 Fig 5 Fig 8 Fig 7...
Page 412: ...410 FTX N U FVXS N FDMQ R Series EDUS091558E 3P124623 1E 15...
Page 422: ...420 FTX N U FVXS N FDMQ R Series EDUS091558E 3P124623 1E 25 Fig 9 Fig 12 Fig 10 Fig 11...
Page 423: ...FTX N U FVXS N FDMQ R Series EDUS091558E 421 3P124623 1E 26 Fig 14 Fig 13 Fig 16 Fig 15...
Page 425: ...FTX N U FVXS N FDMQ R Series EDUS091558E 423 1P126474 1B...
Page 426: ...424 FTX N U FVXS N FDMQ R Series EDUS091558E 1P126474 1B...
Page 427: ...FTX N U FVXS N FDMQ R Series EDUS091558E 425 1P126474 1B...
Page 428: ...426 FTX N U FVXS N FDMQ R Series EDUS091558E 1P126474 1B...
Page 433: ...FTX N U FVXS N FDMQ R Series EDUS091558E 431 3P162015 1A...
Page 434: ...432 FTX N U FVXS N FDMQ R Series EDUS091558E 3P162015 1A...
Page 435: ...FTX N U FVXS N FDMQ R Series EDUS091558E 433 3P162015 1A...
Page 436: ...434 FTX N U FVXS N FDMQ R Series EDUS091558E 3P162015 1A...
Page 455: ...FTX N U FVXS N FDMQ R Series EDUS091558E 453 3P400464 1...
Page 457: ...FTX N U FVXS N FDMQ R Series EDUS091558E 455 3P561172 1...
Page 459: ...FTX N U FVXS N FDMQ R Series EDUS091558E 457 3P534932 1B...
Page 469: ...FTX N U FVXS N FDMQ R Series EDUS091558E 467 3P436077 1...
Page 471: ...FTX N U FVXS N FDMQ R Series EDUS091558E 469 3P436078 1...
Page 472: ...470 FTX N U FVXS N FDMQ R Series EDUS091558E 3P436079 1 14 26 KPS067A44 Snow Hood Outlet...
Page 473: ...FTX N U FVXS N FDMQ R Series EDUS091558E 471 3P436079 1...
Page 475: ...FTX N U FVXS N FDMQ R Series EDUS091558E 473 3P436071 1...
Page 477: ...FTX N U FVXS N FDMQ R Series EDUS091558E 475 3P436072 1...
Page 478: ...476 FTX N U FVXS N FDMQ R Series EDUS091558E 3P436073 1 14 29 KPS063A47 Snow Hood Outlet...
Page 479: ...FTX N U FVXS N FDMQ R Series EDUS091558E 477 3P436073 1...
Page 480: ...478 FTX N U FVXS N FDMQ R Series EDUS091558E...
Page 481: ......
Page 482: ......
Page 483: ......