Indoor Unit Installation

6.

Drain piping

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water 

flows smoothly.

3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.

[Figure of hose front end]

4) When extending the drain hose, use a commercially available 

extension hose with an inner diameter of 5/8 inch (16mm).
Be sure to thermally insulate the indoor section of the extension 
hose.

5) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 1/2 inch (13mm)) directly to 
the drain hose attached to the indoor unit as 
with embedded piping work, use any 
commercially available drain socket (nominal 
diameter 1/2 inch (13mm)) as a joint.

Refrigerant Piping Work

1.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward 

so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

φ

11/16” (

φ

18mm)

φ

5/8” (

φ

16mm)

φ

5/8” 

(

φ

16mm)

The drain hose provided 
to indoor unit.

Indoor unit 
drain hose

φ

5/8” 

(

φ

16mm)

Extension drain hose

Heat insulation tube
(field supply)

Commercially available drain socket 
(nominal diameter 1/2 inch (13mm))

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 1/2 inch 
(13mm))

The drain hose provided 
to indoor unit.

φ

18

Set exactly at the position shown below.

A

Flaring

Die

A 0-0.020 inch (0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch (1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch (1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

(Cut exactly at 

right angles.)

 Remove burrs.

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in a 
perfect circle.

Make sure that the 
flare nut is fitted.

01_EN_3P253189-1E.fm  Page 10  Friday, August 20, 2010  9:36 AM

Summary of Contents for FTKN09JEVJU

Page 1: ...DITIONER English Fran ais Espa ol Installation manual Manuel d installation Manual de instalaci n MODELS FTXS09JEVJU FTXN09JEVJU FTXS12JEVJU FTXN12JEVJU FTKS09JEVJU FTKN09JEVJU FTKS12JEVJU FTKN12JEVJU...

Page 2: ...ing rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to severe inj...

Page 3: ...ttach the refrigerant piping securely before running the compressor If the compressor is not attached and the stop valve is open during pump down air will be sucked in when the compressor is run causi...

Page 4: ...ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firml...

Page 5: ...e the front grille How to remove the indoor unit Push up the marked area at the lower part of the front grille to release the claws If it is difficult to release remove the front grille The mounting p...

Page 6: ...pipe port cover can be kept in the mounting plate pocket Removed pipe port cover A Mounting plate Use tape measure as shown Position the end of a tape measure at Liquid pipe end Gas pipe end Through t...

Page 7: ...ther with insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as...

Page 8: ...the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulation fixing screw Forgetting to tighten this may cause water leakages How to rep...

Page 9: ...oor unit Doing so may cause electric shock or fire 5 When connecting to a wired remote controller If work space is available on the right side of the indoor unit the work can be performed with the ele...

Page 10: ...box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the louver 2 Install the electrical component box 1 screw...

Page 11: ...from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Never inst...

Page 12: ...on materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation pipes for gas and...

Page 13: ...ly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power...

Page 14: ...1010 HT 3P253189 1E M09B108C Two dimensional bar code is a code for manufacturing 66162757 00_CV_3P253189 1E fm Page 2 Friday August 20 2010 9 33 AM...

Reviews: