Refrigerant piping

CAUTION

• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque wrenches.

2-1. Caution on piping handling 

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending. 

2-2. Selection of copper and heat insulation materials

• When using commercial copper pipes and fittings, observe the following:

1) Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 
0.045kcal/mh°C))
Refrigerant gas pipe’s surface temperature reaches 230°F (110°C) max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation 

dimensions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 3/8 inch (9.5mm)

O.D. 1/4 inch (6.4mm)

I.D. 0.427-0.590 inch 

(12-15mm)

I.D. 0.315-0.393 inch 

(8-10mm)

Minimum bend radius

Thickness 0.393 inch (10mm) Min.

1-3/16 inch (30mm) or more

Thickness 0.031 inch (0.8mm) (C1220T-O)

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration oil to 

the inner surface of the 

flare.

Do not apply refrigeration 

oil to the flare nut avoid 

tightening with over torque.

[Apply oil]

Torque wrench

Piping union

Flare nut

Spanner

[Tighten]

Flare nut tightening torque

Gas side

Liquid side

3/8 inch (9.5mm)

1/4 inch (6.4mm)

24.1-29.4ft 

l

 lbf

(32.7-39.9N 

l

 m)

10.4-12.7ft 

l

 lbf

(14.2-17.2N 

l

 m)

Wall

If no flare cap is 
available, cover 
the flare mouth 
with tape to keep 
dirt or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

01_EN_3P253189-1E.fm  Page 11  Friday, August 20, 2010  9:36 AM

Summary of Contents for FTKN09JEVJU

Page 1: ...DITIONER English Fran ais Espa ol Installation manual Manuel d installation Manual de instalaci n MODELS FTXS09JEVJU FTXN09JEVJU FTXS12JEVJU FTXN12JEVJU FTKS09JEVJU FTKN09JEVJU FTKS12JEVJU FTKN12JEVJU...

Page 2: ...ing rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to severe inj...

Page 3: ...ttach the refrigerant piping securely before running the compressor If the compressor is not attached and the stop valve is open during pump down air will be sucked in when the compressor is run causi...

Page 4: ...ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firml...

Page 5: ...e the front grille How to remove the indoor unit Push up the marked area at the lower part of the front grille to release the claws If it is difficult to release remove the front grille The mounting p...

Page 6: ...pipe port cover can be kept in the mounting plate pocket Removed pipe port cover A Mounting plate Use tape measure as shown Position the end of a tape measure at Liquid pipe end Gas pipe end Through t...

Page 7: ...ther with insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as...

Page 8: ...the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulation fixing screw Forgetting to tighten this may cause water leakages How to rep...

Page 9: ...oor unit Doing so may cause electric shock or fire 5 When connecting to a wired remote controller If work space is available on the right side of the indoor unit the work can be performed with the ele...

Page 10: ...box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the louver 2 Install the electrical component box 1 screw...

Page 11: ...from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Never inst...

Page 12: ...on materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation pipes for gas and...

Page 13: ...ly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power...

Page 14: ...1010 HT 3P253189 1E M09B108C Two dimensional bar code is a code for manufacturing 66162757 00_CV_3P253189 1E fm Page 2 Friday August 20 2010 9 33 AM...

Reviews: