Troubleshooting
SiMT041509E
55
Service Diagnosis
4.3
Freeze-up Protection Control / Heating Peak-cut Control
Error Code
A5
Method of Error
Detection
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated
according to the temperature detected by the indoor heat exchanger thermistor.
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor
is used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Error Decision
Conditions
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C.
Heating peak-cut control
During heating operation, the indoor heat exchanger temperature is above 60°C.
Supposed
Causes
Short-circuited air
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Troubleshooting
Check No.01
Refer to P.83
NO
NO
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
YES
YES
(R21064)
YES
YES
NO
Caution
Provide sufficient air passage.
Clean the air filter.
Clean the indoor heat
exchanger.
Replace the indoor unit PCB
(control PCB).
Replace the indoor heat
exchanger thermistor.
As
described in the
thermistor characteristic
chart?
Check the air filter.
Check the dust accumulation on
the indoor heat exchanger.
Is there any short circuit?
Dirty?
Dirty?
Check the air passage.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for FTKM18PVMK
Page 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45 ...
Page 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition ...