Troubleshooting
SiMT041509E
65
Service Diagnosis
4.10 Actuation of High Pressure Switch
Error Code
E3
Method of Error
Detection
Abnormality is detected when the contact of the high pressure switch opens.
Error Decision
Conditions
High pressure switch (S1PH) activating pressure: 4.15 MPa
High pressure switch (S1PH) recovery pressure: 3.2 MPa
Supposed
Causes
Actuation of high pressure switch (S1PH)
Closed stop valve
Disconnection of connector S40
Disconnection of 2 terminals of high pressure switch (S1PH)
Defective outdoor unit PCB
Broken S1PH harness
Defective high pressure switch (S1PH)
Troubleshooting
NO
YES
Nearly 0
Ω
Resistance
∞
Check
the resistance
between the pins 1 - 2 on
the connector
S40.
Stop valve open?
Open the stop valve.
Nearly 0
Ω
Resistance
∞
Replace the harness for the high
pressure switch.
Replace the high pressure switch
(S1PH).
Disconnect the connector
S40 from the PCB.
Replace the outdoor unit PCB
(main PCB).
Disconnect the 2 terminals of
the high pressure switch
(S1PH).
NO
YES
High
pressure switch
connector S40 properly
connected?
Reconnect the connector.
Check
the resistance
between the 2
terminals of the high
pressure switch
(S1PH).
(R22435)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for FTKM18PVMK
Page 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45 ...
Page 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition ...