SiMT041509E
Troubleshooting
Service Diagnosis
76
Troubleshooting
Check No.15
Refer to P.86
Check No.18
Refer to P.88
Check No.20
Refer to P.89
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Turn off the power.
Check the connection.
Check the power supply voltage.
Correct the power supply.
Voltage as rated?
(R22376)
NO
NO
NO
NO
YES
YES
YES
YES
Check No. 20
Check the short circuit of the diode
bridge.
Check No.15
Check with the inverter analyzer.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn on the power. Check the
electrolytic capacitor voltage.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Reconnect the electrical
components or compressor
harnesses as specified.
Replace the outdoor unit
PCB (main PCB).
∗
Inverter analyzer:
RSUK0917C
Normal?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
Within 320 VDC?
Any LED off?
+ 100
– 50
Summary of Contents for FTKM18PVMK
Page 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45 ...
Page 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition ...