Installation manual

4

FHYCP + FCQ

Split System air conditioners

4PW23696-1

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for the used refrigerant.

If R-407C or R-410A refrigerant is used, apply ether or ester oil
around the flare portions before connecting.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc. inside the refrigerant circuit.

Refer to 

Table 1

 for the dimensions of flare nut spaces and the

appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

Table 1

When connecting the flare nut, coat the flare both inside and outside
with refrigerating ether or ester oil and initially tighten by hand 3 or 4
turns before tightening firmly.

Coat here with ether oil or ester oil

Check the pipe connector for gas leaks, then insulate it as
shown in the figure below.

If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a
fire.

Finally make sure there is no refrigerant gas leak. A toxic gas
may be released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.

D

RAIN

 

PIPING

 

WORK

Rig the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

1

Install the drain pipes.

-

Keep piping as short as possible and slope it downwards so 
that air may not remain trapped inside the pipe.

-

Keep pipe size equal to or greater than that of the connecting 
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer 
diameter).

-

Insert the supplied drain hose into the drain socket, up to the 
white tape.

-

Tighten the clamp until the screw head is less then 4mm from 
the hose.

-

Insulate the drain piping inside the building.

-

If the drain hose cannot be sufficiently set on a slope, fit the 
hose with drain raising piping (field supply).

HOW TO PERFORM PIPING 

(See figure 8)

-

Connect the drain hose to the drain raising pipes, and 
insulate them.

-

Connect the drain hose to the drain outlet on the indoor unit, 
and tighten it with the clamp.

PRECAUTIONS

Install the drain raising pipes at a height of less than 550 mm.

Install the drain raising pipes at a right angle to the indoor unit
and no more than 300 mm from the unit.

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Pipe 

gauge

Tightening torque

Flare dimension A (mm)

Flare shape

R-407C

R-410A

Ø6.4

14.2~17.2 N•m 

(144~176 kgf•cm)

8.3~8.7

8.7~9.1

Ø9.5

32.7~39.9 N•m 

(333~407 kgf•cm)

12.0~12.4

12.8~13.2

Ø12.7

49.5~60.3 N•m 

(504~616 kgf•cm)

15.4~15.8

16.2~16.6

Ø15.9

61.8~75.4 N•m 

(630~770 kgf•cm)

18.6~19.0

19.3~19.7

Ø19.1

97.2~118.6 N•m 

(990~1210 kgf•cm)

22.9~23.3

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting of 
liquid line (supplied with 
the unit)

4

Insulation for fitting of gas 
line (supplied with the 
unit)

5

Clamps (use 2 clamps 
per insulation)

2

3

1

4

R0.4~0.8

45

° ±

2

90

°±

2

A

5

4

2

1

3

1

Hanging bar

1

Clamp metal (supplied 
with the unit)

2

Drain hose (supplied with 
the unit)

3

White tape (field supply)

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

NOTE

The incline of attached drain hose should be 75 mm or
less so that the drain socket does not have to
withstand additional force.

To ensure a downward slope of 1:100, install hanging
bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the pipes as
shown in 

figure 9

.  Select converging drain pipes

whose gauge is suitable for the operating capacity of
the unit.

1

T-joint converging drain pipes

1

1-1.5 m

2

1

3

Summary of Contents for FHYCP100B8V1

Page 1: ...INSTALLATION MANUAL FHYCP71B8V1 FHYCP100B8V1 FHYCP125B8V1 FCQ35B8V1 FCQ50B8V1 FCQ60B8V1 FCQ71B8V3B FCQ100B8V3B FCQ125B8V3B Split System air conditioners...

Page 2: ...4 2 7 8 9 10 12 13 11 1 2 3 1500 1500 2 3 4 5 1 50 100 1 2 3 4 950 1 1 5 35 35 3 7 1 4 3 5 5 75 550 750 220 300 mm 1 1 5 mm 1 2 3 4 5 6 100 mm 1 2 2 1 1 4 4 3 3 1 2 1 3 2 1 7 6 1 2 3 4 5 6 7 8 9 10 11...

Page 3: ...1 2 3 P1 P2 6 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 6 1 2 3 1 2 3 1 2 3 4 5 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 3 1 2 3 1 2 3 4 7 8 P1 P2 1 2 3 P1 P2 1...

Page 4: ...jumiem atbilst sekojo iem standartiem un citiem normat viem dokumentiem 24 s v zhode s nasledovnou mi normou ami alebo in m i normat vnym i dokumentom ami za predpokladu e sa pou vaj v s lade s na im...

Page 5: ...r or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluct...

Page 6: ...ions Select the air flow directions best suited to the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote controller an...

Page 7: ...t and washer from the upper and lower sides of the hanger bracket Securing the hanger bracket See figure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installa...

Page 8: ...g pipe vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter Insert the supplied drain hose into the drain socket up to the white tape Tighten the clamp until the screw head is less then 4mm f...

Page 9: ...he outdoor unit the capacity of the circuit breaker and switch and wiring instructions Electrical characteristics Specifications for field wire WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER How...

Page 10: ...worst case electric shock or fire WIRING EXAMPLE For the wiring of outdoor units refer to the installation manual attached to the outdoor units Confirm the system type Pair type or multi system 1 remo...

Page 11: ...ual setting on page 7 to set master and slave units separately When using wireless remote controllers When using wireless remote controllers wireless remote controller address setting is necessary Ref...

Page 12: ...e for 3 minutes 6 Push air flow direction adjust button to make sure the unit is in operation 7 Press Inspection Test Operation button and operate normally 8 Confirm function of unit according to the...

Page 13: ...IODE TIMER GREEN H3P LIGHT EMITTING DIODE FILTER SIGN RED H4P LIGHT EMITTING DIODE DEFROST ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS ADDRESS SET ADAPTER FOR WIRING RyC RyF MAGNE...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23696 1...

Reviews: