Installation manual

2

FHYCP + FCQ

Split System air conditioners

4PW23696-1

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

S

ELECTING

 

INSTALLATION

 

SITE

When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 

mm thickness,

polyethylene foam).

For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 2 or
3 directions.

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service can be
ensured.

Where piping between indoor and outdoor units is possible within
the allowable limit. (Refer to the installation manual of the outdoor
unit.)

Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions and
radios. This is to prevent image interference and noise in those
electrical appliances. (Noise may be generated depending on the
conditions under which the electric wave is generated, even if
1 meter is kept.)

2

Ceiling height

This indoor unit may be installed on ceilings up to 3.5 m in
height (for 80~125 units: 4.2 m). However, it becomes necessary
to make field settings using the remote controller when installing
the unit at a height over 2.7 m (for 80~125 units: 3.2 m).
To  avoid accidental touching, it is recommended to install the
unit higher than 2.5 m.
Refer to 

"Field setting" on page 7

  and to the decoration panel

installation manual.

3

Air flow directions

Select the air flow directions best suited to the room and point of
installation. (For air discharge in 2 or 3 directions, it is necessary
to make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to 

"Field setting" on page 7

(See

figure 1)

 (

: air flow direction)

4

Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.

(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see 

figure 2

  (

:  air flow

direction)

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1

Relation of ceiling opening to unit and suspension bolt position.

(See figure 3)

Installation is possible when opening dimensions are as follows.
When installing the unit within the frame for fixing ceiling
materials. 

(See figure 4)

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

1

Air discharge in 4 directions

2

Air discharge in 3 directions

3

Air discharge in 2 directions

1

Air discharge

2

Air inlet

NOTE

Leave 200 mm or more space where marked with *, on
sides where the air outlet is closed.

Model

H

35~71

240

100+125

298

1

Refrigerant piping

2

Suspension bolt (x4)

3

Hanger bracket

4

False ceiling

5

Suspension bolt pitch

6

Indoor unit

7

Ceiling opening

8

Decoration panel

1

Dimensions inside frame

2

Opening dimension inside the frame for ceiling

3

Frame

4

Ceiling material

5

Ceiling opening dimension

6

Ceiling-panel overlapping dimension

Summary of Contents for FHYCP100B8V1

Page 1: ...INSTALLATION MANUAL FHYCP71B8V1 FHYCP100B8V1 FHYCP125B8V1 FCQ35B8V1 FCQ50B8V1 FCQ60B8V1 FCQ71B8V3B FCQ100B8V3B FCQ125B8V3B Split System air conditioners...

Page 2: ...4 2 7 8 9 10 12 13 11 1 2 3 1500 1500 2 3 4 5 1 50 100 1 2 3 4 950 1 1 5 35 35 3 7 1 4 3 5 5 75 550 750 220 300 mm 1 1 5 mm 1 2 3 4 5 6 100 mm 1 2 2 1 1 4 4 3 3 1 2 1 3 2 1 7 6 1 2 3 4 5 6 7 8 9 10 11...

Page 3: ...1 2 3 P1 P2 6 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 6 1 2 3 1 2 3 1 2 3 4 5 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 3 1 2 3 1 2 3 4 7 8 P1 P2 1 2 3 P1 P2 1...

Page 4: ...jumiem atbilst sekojo iem standartiem un citiem normat viem dokumentiem 24 s v zhode s nasledovnou mi normou ami alebo in m i normat vnym i dokumentom ami za predpokladu e sa pou vaj v s lade s na im...

Page 5: ...r or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluct...

Page 6: ...ions Select the air flow directions best suited to the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote controller an...

Page 7: ...t and washer from the upper and lower sides of the hanger bracket Securing the hanger bracket See figure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installa...

Page 8: ...g pipe vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter Insert the supplied drain hose into the drain socket up to the white tape Tighten the clamp until the screw head is less then 4mm f...

Page 9: ...he outdoor unit the capacity of the circuit breaker and switch and wiring instructions Electrical characteristics Specifications for field wire WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER How...

Page 10: ...worst case electric shock or fire WIRING EXAMPLE For the wiring of outdoor units refer to the installation manual attached to the outdoor units Confirm the system type Pair type or multi system 1 remo...

Page 11: ...ual setting on page 7 to set master and slave units separately When using wireless remote controllers When using wireless remote controllers wireless remote controller address setting is necessary Ref...

Page 12: ...e for 3 minutes 6 Push air flow direction adjust button to make sure the unit is in operation 7 Press Inspection Test Operation button and operate normally 8 Confirm function of unit according to the...

Page 13: ...IODE TIMER GREEN H3P LIGHT EMITTING DIODE FILTER SIGN RED H4P LIGHT EMITTING DIODE DEFROST ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS ADDRESS SET ADAPTER FOR WIRING RyC RyF MAGNE...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23696 1...

Reviews: