FHYCP + FCQ
Split System air conditioners
4PW23696-1

Installation manual

7

F

IELD

 

SETTING

Field setting must be made from the remote controller in accordance
with the installation condition.

Setting can be made by changing the "Mode number", "FIRST
CODE No." and "SECOND CODE No.".

For setting and operation, refer to "Field setting" in the
installation manual of the remote controller.

Setting ceiling height

Select the SECOND CODE No. that corresponds to the ceiling
height. (SECOND CODE No. is factory set to "01" for a ceiling height
of 2.7 m or less.)

The figure of ceiling height is for air discharge in 4 directions.

Setting air discharge direction

For changing air discharge direction (2 or 3 directions), refer to the
option handbook of the optional blocking pad kit. (SECOND CODE
No. is factory set to "01" for air discharge in 4 directions.)

Setting when installing high performance filters

In case of installing high performance filters, refer to the option
handbook of the high performance filters.

Setting air filter sign

Remote controllers are equipped with liquid crystal air filter signs to
display the time to clean the air filter.

Change the SECOND CODE No. Depending on the amount of dirt or
dust in the room. (SECOND CODE No. is factory set to "01" for air
filter contamination-light)

Air Filter contamination

When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.

Setting indoor unit number of simultaneous operation 
system

When using in simultaneous operation system mode, change the
SECOND CODE No. as shown in the table. (SECOND CODE No. is
factory set to "01" for 1 connected unit.)

When using in simultaneous operation system mode, refer to

"Simultaneous operation system individual setting" on page 7

 to set

master and slave units separately.

When using wireless remote controllers

When using wireless remote controllers, wireless remote controller
address setting is necessary. Refer to the installation manual
attached to the wireless remote controller for setting instructions.

Simultaneous operation system individual setting

It is easier if the optional remote controller is used when setting the
slave unit.

Perform the following procedures when setting the master and slave
unit separately.

Procedure 

(See figure 19)

1

Change the SECOND CODE No. to "02", individual setting, so
that the slave unit can be individually set. (SECOND CODE No.
is factory set to "01", unified setting.)

2

Perform field setting for the master unit.

3

Turn off the main power supply switch after (2).

4

Detach remote controller from the master unit and connect it to
the slave unit.

5

Turn  on the main power supply switch again, and as in (1),
change the Position No. to "02", individual setting.

6

Perform field setting for the slave unit.

7

Turn off the main power supply switch after (6).

8

Detach the remote controller from the slave unit after the setting,
and reattach to the master unit. This is the end of the setting
procedure.

You do not need to rewire the remote controller from the master unit if
the optional remote controller for slave unit is used. (However,
remove the wires attached to the remote controller terminal board of
the master unit.)

Ceiling height (m)

Mode n°

1st code n°

2nd code n°

units 

35~71

units 

100~125

<2.7

<3.2

N

13 (23)

0

01

>2.7 or 

<3.0

<3.2 or 

<3.6

H

13 (23)

0

02

>3.0 or 

<3.5

<3.6 or 

4.2

S

13 (23)

0

03

Setting

Display 
interval

Mode n°

1st code n°

2nd code n°

Light

±2500 hrs

10 (20)

0

01

Heavy

±1250 hrs

10 (20)

0

02

Setting

Mode No.

FIRST 

CODE No.

SECOND 

CODE No.

Pair system (1 unit)

11 (21)

0

01

Simultaneous 

operation system 

(2-unit)

02

Simultaneous 

operation system 

(3-unit)

03

Simultaneous 

operation system 

(4-unit)

04

Setting

Mode No.

FIRST 

CODE No.

SECOND 

CODE No.

Unified setting

11 (21)

1

01

Individual setting

02

Summary of Contents for FHYCP100B8V1

Page 1: ...INSTALLATION MANUAL FHYCP71B8V1 FHYCP100B8V1 FHYCP125B8V1 FCQ35B8V1 FCQ50B8V1 FCQ60B8V1 FCQ71B8V3B FCQ100B8V3B FCQ125B8V3B Split System air conditioners...

Page 2: ...4 2 7 8 9 10 12 13 11 1 2 3 1500 1500 2 3 4 5 1 50 100 1 2 3 4 950 1 1 5 35 35 3 7 1 4 3 5 5 75 550 750 220 300 mm 1 1 5 mm 1 2 3 4 5 6 100 mm 1 2 2 1 1 4 4 3 3 1 2 1 3 2 1 7 6 1 2 3 4 5 6 7 8 9 10 11...

Page 3: ...1 2 3 P1 P2 6 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 6 1 2 3 1 2 3 1 2 3 4 5 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 3 1 2 3 1 2 3 4 7 8 P1 P2 1 2 3 P1 P2 1...

Page 4: ...jumiem atbilst sekojo iem standartiem un citiem normat viem dokumentiem 24 s v zhode s nasledovnou mi normou ami alebo in m i normat vnym i dokumentom ami za predpokladu e sa pou vaj v s lade s na im...

Page 5: ...r or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluct...

Page 6: ...ions Select the air flow directions best suited to the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote controller an...

Page 7: ...t and washer from the upper and lower sides of the hanger bracket Securing the hanger bracket See figure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installa...

Page 8: ...g pipe vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter Insert the supplied drain hose into the drain socket up to the white tape Tighten the clamp until the screw head is less then 4mm f...

Page 9: ...he outdoor unit the capacity of the circuit breaker and switch and wiring instructions Electrical characteristics Specifications for field wire WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER How...

Page 10: ...worst case electric shock or fire WIRING EXAMPLE For the wiring of outdoor units refer to the installation manual attached to the outdoor units Confirm the system type Pair type or multi system 1 remo...

Page 11: ...ual setting on page 7 to set master and slave units separately When using wireless remote controllers When using wireless remote controllers wireless remote controller address setting is necessary Ref...

Page 12: ...e for 3 minutes 6 Push air flow direction adjust button to make sure the unit is in operation 7 Press Inspection Test Operation button and operate normally 8 Confirm function of unit according to the...

Page 13: ...IODE TIMER GREEN H3P LIGHT EMITTING DIODE FILTER SIGN RED H4P LIGHT EMITTING DIODE DEFROST ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS ADDRESS SET ADAPTER FOR WIRING RyC RyF MAGNE...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23696 1...

Reviews: