FHYCP + FCQ
Split System air conditioners
4PW23696-1

Installation manual

3

2

Make the ceiling opening needed for installation where
applicable. (For existing ceilings.)

-

Refer to the paper pattern for installation for the ceiling 
opening dimensions.

-

Create the ceiling opening required for installation. From the 
side of the opening to the casing outlet, implement the 
refrigerant and drain piping and wiring for remote controller 
(unnecessary for wireless type). Refer to each piping or 
wiring section.

-

After making an opening in the ceiling, it may be necessary 
to reinforce ceiling beams to keep the ceiling level and to 
prevent it from vibrating. Consult the builder for details.

3

Install the suspension bolts. (Use either a W3/8 or M10 size
bolt.)

Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce
the ceiling in order to bear the weight of the unit. Adjust
clearance from the ceiling before proceeding further.
Installation example 

(See figure 5)

I

NSTALLATION

 

PROCEDURES

 

FOR

 

FRESH

 

AIR

 

INTAKE

 

DUCT

 

CONNECTION

1

Preparing the connection hole. 

(See figure 10)

-

Cut off the knockout hole on the side plate with a nipper.

-

Cut the insulation of the hole portion with a cutter.

2

Placing the insulation. 

(See figure 11)

-

Put the insulation tightly around the hole of the unit as 
shown. The ends of the side plate and the inner insulation 
must be completely adhered without leaving any clearance 
along the circumference of the hole. Make sure the inner 
surface of insulation tightly contacts the inner insulation edge 
and the side plate.

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories (except for the decoration
panel), read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed. However, for existing
ceilings, install fresh air inlet component kit and branch duct before
installing the unit.

1

Install the indoor unit temporarily.

-

Attach the hanger bracket to the suspension bolt. Be sure to 
fix it securely by using a nut and washer from the upper and 
lower sides of the hanger bracket.

-

Securing the hanger bracket 

(See figure 6)

2

Fix the paper pattern for installation. (For new ceilings only.)

-

The paper pattern for installation corresponds with the 
measurements of the ceiling opening. Consult the builder for 
details.

-

The centre of the ceiling opening is indicated on the paper 
pattern for installation. The centre of the unit is indicated on 
the unit casing and on the paper pattern for installation.

-

After removing the packaging material from the paper pattern 
for installation, attach the paper pattern for installation to the 
unit with the attached screws as shown in 

figure 7

.

-

Adjust the height of the unit until it matches the indication in 

figure 7

.

3

Adjust the unit to the right position for installation.

(See 

"Preparations before installation" on page 2

.)

4

Check if the unit is horizontally levelled.

-

Do not install the unit tilted. The indoor unit is equipped with a 
built-in drain pump and float switch. (If the unit is tilted 
against condensate flow, the float switch may malfunction 
and cause water to drip.)

-

Check if the unit is levelled at all four corners with a water 
level or a water-filled vinyl tube as shown in 

figure 14

.

5

Remove the paper pattern for installation. (For new ceilings
only.)

NOTE

Installation is possible with a ceiling dimension of
910 mm (marked with*). However, to achieve a ceiling-
panel overlapping dimension of 20 mm, the spacing
between the ceiling and the unit should be 35 mm or
less. If the spacing between ceiling and the unit is over
35 mm, attach ceiling material to the part or recover
the ceiling.

1

Ceiling slab

2

Anchor

3

Long nut or turn-buckle

4

Suspension bolt

5

False ceiling

NOTE

All the above parts are field supplied.

For other installation than standard installation,
contact your Daikin dealer for details.

1

Piping

2

Drain pipe

3

Side plate

4

Inner insulation

5

Slit

1

Insulation (field supply)

2

Side plate

3

Inner insulation

1

Nut (field supply)

2

Washer (supplied with the unit)

3

Hanger bracket

4

Tighten (double nut)

1

Height adjustment of the unit

2

Ceiling material

3

Paper pattern for installation

4

Installation of paper pattern for installation (supplied with the 
unit)

5

Centre of the ceiling opening

6

Centre of the unit

7

Screws (supplied with the unit)

1

Water level

2

Vinyl tube

Summary of Contents for FHYCP100B8V1

Page 1: ...INSTALLATION MANUAL FHYCP71B8V1 FHYCP100B8V1 FHYCP125B8V1 FCQ35B8V1 FCQ50B8V1 FCQ60B8V1 FCQ71B8V3B FCQ100B8V3B FCQ125B8V3B Split System air conditioners...

Page 2: ...4 2 7 8 9 10 12 13 11 1 2 3 1500 1500 2 3 4 5 1 50 100 1 2 3 4 950 1 1 5 35 35 3 7 1 4 3 5 5 75 550 750 220 300 mm 1 1 5 mm 1 2 3 4 5 6 100 mm 1 2 2 1 1 4 4 3 3 1 2 1 3 2 1 7 6 1 2 3 4 5 6 7 8 9 10 11...

Page 3: ...1 2 3 P1 P2 6 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 6 1 2 3 1 2 3 1 2 3 4 5 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 3 1 2 3 1 2 3 4 7 8 P1 P2 1 2 3 P1 P2 1...

Page 4: ...jumiem atbilst sekojo iem standartiem un citiem normat viem dokumentiem 24 s v zhode s nasledovnou mi normou ami alebo in m i normat vnym i dokumentom ami za predpokladu e sa pou vaj v s lade s na im...

Page 5: ...r or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluct...

Page 6: ...ions Select the air flow directions best suited to the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote controller an...

Page 7: ...t and washer from the upper and lower sides of the hanger bracket Securing the hanger bracket See figure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installa...

Page 8: ...g pipe vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter Insert the supplied drain hose into the drain socket up to the white tape Tighten the clamp until the screw head is less then 4mm f...

Page 9: ...he outdoor unit the capacity of the circuit breaker and switch and wiring instructions Electrical characteristics Specifications for field wire WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER How...

Page 10: ...worst case electric shock or fire WIRING EXAMPLE For the wiring of outdoor units refer to the installation manual attached to the outdoor units Confirm the system type Pair type or multi system 1 remo...

Page 11: ...ual setting on page 7 to set master and slave units separately When using wireless remote controllers When using wireless remote controllers wireless remote controller address setting is necessary Ref...

Page 12: ...e for 3 minutes 6 Push air flow direction adjust button to make sure the unit is in operation 7 Press Inspection Test Operation button and operate normally 8 Confirm function of unit according to the...

Page 13: ...IODE TIMER GREEN H3P LIGHT EMITTING DIODE FILTER SIGN RED H4P LIGHT EMITTING DIODE DEFROST ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS ADDRESS SET ADAPTER FOR WIRING RyC RyF MAGNE...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23696 1...

Reviews: