13 Piping installation

Installation and operation manual

18

FHA-A(9)

Split system air conditioner

3P668115-4E – 2022.11

13.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

≥13 mm

12.7 mm (1/2")

14~16 mm

≥13 mm

15.9 mm (5/8”)

17~20 mm

≥13 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

13.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

13.2.1

To connect the refrigerant piping to the
indoor unit

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

WARNING: MILDLY FLAMMABLE MATERIAL

The  R32  refrigerant  (if  applicable)  in  this  unit  is  mildly
flammable.  Refer  to  the  outdoor  unit  specifications  for  the
type of refrigerant to be used.

Refrigerant piping can be connected from following directions:

a

b

c

a

Rear right piping

b

Right piping

c

Upward piping

Rear right piping

1

Remove the rear piping pipe port cover and cut out the holes for
piping. When cutting out the holes, make sure to avoid the knob
part of the cover.

a

b

a

Rear refrigerant piping

b

Rear piping pipe port cover

2

Run the field supply pipes through the cut out holes.

3

After the drain and refrigerant piping is finished, install the pipe
port  cover  back.  Run  all  the  cables  through  the  clamp  of  the
pipe port cover and fix.

a b c

a

Clamp of the pipe port cover

b

Cables

Upward piping

INFORMATION

L-shaped  connection  piping  kit  (optional  accessory)  is
required.

1

Remove the top pipe port cover and cut out the holes for piping.
When cutting out the holes, make sure to avoid the knob part of
the  cover.  Use  an  L-shaped  connection  piping  kit  (optional
accessory)  for  the  piping.  Run  the  pipes  through  the  cut  out
holes.

a

b

a

Upward refrigerant piping

b

Top pipe port cover

Right piping

1

Remove the reinforcing plate at the right side and put back the
screw in the original position on the indoor unit.

2

Remove the decoration side panel.

3

Remove the rectangular part of the decoration side panel.

Summary of Contents for FHA35AVEB98

Page 1: ...ion and operation manual Split system air conditioner English Installation and operation manual Split system air conditioner FHA35AVEB98 FHA50AVEB98 FHA60AVEB98 FHA71AVEB98 FHA100AVEB8 FHA125AVEB8 FHA...

Page 2: ...ksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi...

Page 3: ...n accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compati...

Page 4: ...el 21 16 Commissioning 21 16 1 Checklist before commissioning 21 16 2 To perform a test run 22 17 Configuration 22 17 1 Field setting 22 18 Technical data 23 18 1 Wiring diagram 23 18 1 1 Unified wiri...

Page 5: ...ersion of ISO14903 can be used CAUTION Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refrige...

Page 6: ...consequences for the environment and human health For more information contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT b...

Page 7: ...f obstructions Maintenance and service see 7 Maintenance and service 410 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Make sure to turn OFF the main sw...

Page 8: ...ant leaks in the room and comes into contact with fire from a burner a heater or a cooker this may result in a fire in case of R32 or the formation of a harmful gas Turn OFF any combustible heating de...

Page 9: ...peration range INFORMATION For the operation limits see the technical data of the connected outdoor unit 6 2 About operation modes INFORMATION Depending on the installed system some operation modes wi...

Page 10: ...become caught or the unit may break down NOTICE Avoid operating in the horizontal direction It may cause dew or dust to settle on the ceiling or flap Left and right airflow direction setting The left...

Page 11: ...ation of the terminals see the warning label for persons performing service and maintenance a a b c a Residual voltage measuring points b Printed circuit board c Control box 7 2 Cleaning the unit exte...

Page 12: ...legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes...

Page 13: ...ing units requires technical expertise 10 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applic...

Page 14: ...n installing optional equipment also read the installation manual of the optional equipment Depending on the field conditions it might be easier to install the optional equipment first Ceiling strengt...

Page 15: ...e accessories b c a a Accessories b Fixing screw for side covers c Decoration side cover To mount the indoor unit 1 Open the knockout hole at the wiring inlet at the rear or the top of the unit and in...

Page 16: ...a T joint To connect the drain piping to the indoor unit NOTICE Incorrect connection of the drain hose might cause leaks and damage the installation space and surroundings Drain piping can be connecte...

Page 17: ...level in accordance with the instructions in 12 2 1 Guidelines when installing the indoor unit 414 Gradually pour approximately 1 l of water through the air discharge outlet and check for leaks a 100...

Page 18: ...DLY FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used Refrigerant piping can be conn...

Page 19: ...y III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 14 1 Specifications of standard wiring c...

Page 20: ...tion of power supply cable m Wiring fixture fixed with a screw accessory n Tie wrap accessory 6 Seal all gaps with sealing material accessory to prevent small animals from entering the system 7 Reatta...

Page 21: ...To open the indoor unit 415 2 When installing the suction grille attach the strap of the suction grille to the hook on the indoor unit INFORMATION When closing the suction grille make sure the straps...

Page 22: ...When using any other user interface see the installation manual or service manual of the user interface Setting Wireless remote controller address if applicable When using wireless remote controller s...

Page 23: ...er interface to master unit The system does not operate properly when two or more user interfaces are attached in the simultaneous operation system mode Setting T1 T2 input setting Remote control is a...

Page 24: ...essor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit boa...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...3P668115 4E 2022 11 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: