13 Piping installation

Installation and operation manual

17

FHA-A(9)
Split system air conditioner
3P668115-4E – 2022.11

a

b

c

e

f

d

a

Round part

b

Rectangular part of the decoration side panel

c

Decoration side panel

d

Screw

e

Reinforcing plate

f

Right drain piping

Drain piping connection

b

a

d c b

f

d c b

f

A

A'

A

A'

4

2

c

d

e

5

90°

90°

A-A'

A-A'

A

B

1

3

2~5

1

a

Drain pipe connection (attached to the unit)

b

Drain hose (accessory)

c

Metal clamp (accessory)

d

Large sealing pad (accessory)

e

Drain piping (field supply)

f

Tightened part of metal clamp

A

In case of bending the end of the metal clamp

B

In case of wrapping the end of the metal clamp with vinyl
tape

1

Push  the  drain  hose  as  far  as  possible  over  the  drain  pipe
connection.

2

Tighten  the  metal  clamp  at  the  base  of  the  drain  socket.  Wrap
the  end  of  the  metal  clamp  with  vinyl  tape  or  bend  the  end
inwards to avoid damaging the sealing pad.

3

Check for water leaks (see 

"To check for water leaks"

 [

4

 17]).

4

Wind  the  large  sealing  pad  (=  insulation)  around  the  metal
clamp  and  drain  hose,  and  fix  it  with  tie  wraps.  Start  wrapping
from the tightened part of the metal clamp so that the end of the
metal clamp is wrapped twice.

5

Connect the drain piping to the drain hose.

To check for water leaks

Make  sure  the  unit  is  level  in  accordance  with  the  instructions  in

"12.2.1  Guidelines  when  installing  the  indoor  unit"

  [

4

  14].  Gradually

pour approximately 1 l of water through the air discharge outlet, and
check for leaks.

a

≥100

b

(mm)

a

Air outlet

b

Plastic water container with tube length ≥100 mm

13

Piping installation

13.1

Preparing refrigerant piping

13.1.1

Refrigerant piping requirements

CAUTION

Piping MUST be installed according to instructions given in

"13  Piping  installation"

  [

4

  17].  Only  mechanical  joints  (e.g.

braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant piping.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

For  piping  connection  of  the  indoor  unit,  use  the  following  piping
diameters:

Pipe outer diameter (mm)

Class

Liquid pipe

Gas pipe

35

Ø6.4

Ø9.5

50+60

Ø6.4

Ø12.7

71~140

Ø9.5

Ø15.9

Refrigerant piping material

Piping material:

 phosphoric acid deoxidised seamless copper

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

15.9 mm (5/8")

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

Summary of Contents for FHA35AVEB98

Page 1: ...ion and operation manual Split system air conditioner English Installation and operation manual Split system air conditioner FHA35AVEB98 FHA50AVEB98 FHA60AVEB98 FHA71AVEB98 FHA100AVEB8 FHA125AVEB8 FHA...

Page 2: ...ksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi...

Page 3: ...n accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compati...

Page 4: ...el 21 16 Commissioning 21 16 1 Checklist before commissioning 21 16 2 To perform a test run 22 17 Configuration 22 17 1 Field setting 22 18 Technical data 23 18 1 Wiring diagram 23 18 1 1 Unified wiri...

Page 5: ...ersion of ISO14903 can be used CAUTION Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refrige...

Page 6: ...consequences for the environment and human health For more information contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT b...

Page 7: ...f obstructions Maintenance and service see 7 Maintenance and service 410 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Make sure to turn OFF the main sw...

Page 8: ...ant leaks in the room and comes into contact with fire from a burner a heater or a cooker this may result in a fire in case of R32 or the formation of a harmful gas Turn OFF any combustible heating de...

Page 9: ...peration range INFORMATION For the operation limits see the technical data of the connected outdoor unit 6 2 About operation modes INFORMATION Depending on the installed system some operation modes wi...

Page 10: ...become caught or the unit may break down NOTICE Avoid operating in the horizontal direction It may cause dew or dust to settle on the ceiling or flap Left and right airflow direction setting The left...

Page 11: ...ation of the terminals see the warning label for persons performing service and maintenance a a b c a Residual voltage measuring points b Printed circuit board c Control box 7 2 Cleaning the unit exte...

Page 12: ...legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes...

Page 13: ...ing units requires technical expertise 10 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applic...

Page 14: ...n installing optional equipment also read the installation manual of the optional equipment Depending on the field conditions it might be easier to install the optional equipment first Ceiling strengt...

Page 15: ...e accessories b c a a Accessories b Fixing screw for side covers c Decoration side cover To mount the indoor unit 1 Open the knockout hole at the wiring inlet at the rear or the top of the unit and in...

Page 16: ...a T joint To connect the drain piping to the indoor unit NOTICE Incorrect connection of the drain hose might cause leaks and damage the installation space and surroundings Drain piping can be connecte...

Page 17: ...level in accordance with the instructions in 12 2 1 Guidelines when installing the indoor unit 414 Gradually pour approximately 1 l of water through the air discharge outlet and check for leaks a 100...

Page 18: ...DLY FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used Refrigerant piping can be conn...

Page 19: ...y III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 14 1 Specifications of standard wiring c...

Page 20: ...tion of power supply cable m Wiring fixture fixed with a screw accessory n Tie wrap accessory 6 Seal all gaps with sealing material accessory to prevent small animals from entering the system 7 Reatta...

Page 21: ...To open the indoor unit 415 2 When installing the suction grille attach the strap of the suction grille to the hook on the indoor unit INFORMATION When closing the suction grille make sure the straps...

Page 22: ...When using any other user interface see the installation manual or service manual of the user interface Setting Wireless remote controller address if applicable When using wireless remote controller s...

Page 23: ...er interface to master unit The system does not operate properly when two or more user interfaces are attached in the simultaneous operation system mode Setting T1 T2 input setting Remote control is a...

Page 24: ...essor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit boa...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...3P668115 4E 2022 11 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: