12 Unit installation
Installation and operation manual
14
FHA-A(9)
Split system air conditioner
3P668115-4E – 2022.11
CAUTION
Appliance NOT accessible to the general public. Install it in
a secured area, protected from easy access.
This unit is suitable for installation in a commercial, light
industrial, household and residential environment.
WARNING
For units using the R32 refrigerant it is necessary to keep
any required ventilation openings clear of obstructions.
▪
Paper pattern for installation
(accessory). Use the paper pattern
when selecting the installation location. It contains the dimensions
of the unit and the locations of suspension bolts, piping outlet,
drain piping outlet and electric wiring inlet.
▪
Spacing
. Mind the following requirements:
Minimum distance to the wall
: 30 mm left and right of the unit,
however, ≥200 mm is recommended for easier servicing.
≥30
≥30
(mm)
Minimum and maximum distance to the floor
:
▪ Minimum: 2.5 m to avoid accidental touching.
▪ Maximum: Depends on the capacity class. See
22].
b
a
c
d
≥300
≥2500
(mm)
a
Discharge
b
Suction
c
Obstacle
d
Floor
INFORMATION
Some options may require additional service space. Sees
the installation manual of the used option before
installation.
12.2
Mounting the indoor unit
12.2.1
Guidelines when installing the indoor unit
INFORMATION
Optional equipment.
When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
▪
Ceiling strength
. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
▪ For existing ceilings, use anchors.
▪ For new ceilings, use sunken inserts, sunken anchors or other
field supplied parts.
25~55
b
(mm)
a
d
e
c
a
Ceiling slab
b
Anchor
c
Long nut with turnbuckle
d
Suspended ceiling
e
Suspension bolt
▪
Suspension bolts and unit.
Use M8~M10 suspension bolts for
installation. Attach the hanger bracket to the suspension bolt. Fix it
securely using a nut and washer on the top and bottom of the
hanger bracket.
Front view
5
175
200
c
b
a
G
H
J
(mm)
Top (ceiling) view
(mm)
F
210
D
B:
260
30
163
E
189
87
C
A
B
k
l
d
j
e
A:
690
h
g
f1
g
f2
i
4×
A
B
C
D
E
F
G
H
J
FHA35+50
960
920
378
324 270 375 398 377 260
FHA60+71
1270
1230
533
479 425 530 553 532 415
FHA100~140
1590
1550
693
639 585 690 713 692 575
A
Unit dimension
B
Suspension bolt pitch
a
Rear left drain piping outlet hole
b
Rear wiring outlet location
c
Wall hole for rear piping outlet (
⌀
100 mm)
d
Top panel wiring outlet position
e
Discharge
f1
Nut (field supply)
f2
Double nut (field supply)
h
Hanger bracket
g
Washer for hanger bracket (accessory)
i
Suspension bolt
j
Top panel drain piping connection position
k
Top panel gas side piping connection position
l
Top panel liquid side piping connection positions