12 Unit installation

Installation and operation manual

14

FHA-A(9)

Split system air conditioner

3P668115-4E – 2022.11

CAUTION

Appliance NOT accessible to the general public. Install it in
a secured area, protected from easy access.

This  unit  is  suitable  for  installation  in  a  commercial,  light
industrial, household and residential environment.

WARNING

For units using the R32 refrigerant it is necessary to keep
any required ventilation openings clear of obstructions.

Paper pattern for installation

 (accessory). Use the paper pattern

when selecting the installation location. It contains the dimensions
of  the  unit  and  the  locations  of  suspension  bolts,  piping  outlet,
drain piping outlet and electric wiring inlet.

Spacing

. Mind the following requirements:

Minimum  distance  to  the  wall

:  30  mm  left  and  right  of  the  unit,

however, ≥200 mm is recommended for easier servicing.

≥30

≥30

(mm)

Minimum and maximum distance to the floor

:

▪ Minimum: 2.5 m to avoid accidental touching.

▪ Maximum:  Depends  on  the  capacity  class.  See 

"17.1  Field

setting"

 [

4

 22].

b

a

c

d

≥300

≥2500

(mm)

a

Discharge

b

Suction

c

Obstacle

d

Floor

INFORMATION

Some  options  may  require  additional  service  space.  Sees
the  installation  manual  of  the  used  option  before
installation.

12.2

Mounting the indoor unit

12.2.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

Ceiling  strength

.  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

▪ For existing ceilings, use anchors.

▪ For  new  ceilings,  use  sunken  inserts,  sunken  anchors  or  other

field supplied parts.

25~55

b

(mm)

a

d

e

c

a

Ceiling slab

b

Anchor

c

Long nut with turnbuckle

d

Suspended ceiling

e

Suspension bolt

Suspension  bolts  and  unit.

  Use  M8~M10  suspension  bolts  for

installation. Attach the hanger bracket to the suspension bolt. Fix it
securely  using  a  nut  and  washer  on  the  top  and  bottom  of  the
hanger bracket.

Front view

5

175

200

c

b

a

G

H

J

(mm)

Top (ceiling) view

(mm)

F

210

D

B: 

260

30

163

E

189

87

C

A

B

k

l

d

j

e

A: 

690

h

g

f1

g

f2

i

A

B

C

D

E

F

G

H

J

FHA35+50

960

920

378

324 270 375 398 377 260

FHA60+71

1270

1230

533

479 425 530 553 532 415

FHA100~140

1590

1550

693

639 585 690 713 692 575

A

Unit dimension

B

Suspension bolt pitch

a

Rear left drain piping outlet hole

b

Rear wiring outlet location

c

Wall hole for rear piping outlet (

100 mm)

d

Top panel wiring outlet position

e

Discharge

f1

Nut (field supply)

f2

Double nut (field supply)

h

Hanger bracket

g

Washer for hanger bracket (accessory)

i

Suspension bolt

j

Top panel drain piping connection position

k

Top panel gas side piping connection position

l

Top panel liquid side piping connection positions

Summary of Contents for FHA35AVEB98

Page 1: ...ion and operation manual Split system air conditioner English Installation and operation manual Split system air conditioner FHA35AVEB98 FHA50AVEB98 FHA60AVEB98 FHA71AVEB98 FHA100AVEB8 FHA125AVEB8 FHA...

Page 2: ...ksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi...

Page 3: ...n accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compati...

Page 4: ...el 21 16 Commissioning 21 16 1 Checklist before commissioning 21 16 2 To perform a test run 22 17 Configuration 22 17 1 Field setting 22 18 Technical data 23 18 1 Wiring diagram 23 18 1 1 Unified wiri...

Page 5: ...ersion of ISO14903 can be used CAUTION Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refrige...

Page 6: ...consequences for the environment and human health For more information contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT b...

Page 7: ...f obstructions Maintenance and service see 7 Maintenance and service 410 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Make sure to turn OFF the main sw...

Page 8: ...ant leaks in the room and comes into contact with fire from a burner a heater or a cooker this may result in a fire in case of R32 or the formation of a harmful gas Turn OFF any combustible heating de...

Page 9: ...peration range INFORMATION For the operation limits see the technical data of the connected outdoor unit 6 2 About operation modes INFORMATION Depending on the installed system some operation modes wi...

Page 10: ...become caught or the unit may break down NOTICE Avoid operating in the horizontal direction It may cause dew or dust to settle on the ceiling or flap Left and right airflow direction setting The left...

Page 11: ...ation of the terminals see the warning label for persons performing service and maintenance a a b c a Residual voltage measuring points b Printed circuit board c Control box 7 2 Cleaning the unit exte...

Page 12: ...legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes...

Page 13: ...ing units requires technical expertise 10 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applic...

Page 14: ...n installing optional equipment also read the installation manual of the optional equipment Depending on the field conditions it might be easier to install the optional equipment first Ceiling strengt...

Page 15: ...e accessories b c a a Accessories b Fixing screw for side covers c Decoration side cover To mount the indoor unit 1 Open the knockout hole at the wiring inlet at the rear or the top of the unit and in...

Page 16: ...a T joint To connect the drain piping to the indoor unit NOTICE Incorrect connection of the drain hose might cause leaks and damage the installation space and surroundings Drain piping can be connecte...

Page 17: ...level in accordance with the instructions in 12 2 1 Guidelines when installing the indoor unit 414 Gradually pour approximately 1 l of water through the air discharge outlet and check for leaks a 100...

Page 18: ...DLY FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used Refrigerant piping can be conn...

Page 19: ...y III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 14 1 Specifications of standard wiring c...

Page 20: ...tion of power supply cable m Wiring fixture fixed with a screw accessory n Tie wrap accessory 6 Seal all gaps with sealing material accessory to prevent small animals from entering the system 7 Reatta...

Page 21: ...To open the indoor unit 415 2 When installing the suction grille attach the strap of the suction grille to the hook on the indoor unit INFORMATION When closing the suction grille make sure the straps...

Page 22: ...When using any other user interface see the installation manual or service manual of the user interface Setting Wireless remote controller address if applicable When using wireless remote controller s...

Page 23: ...er interface to master unit The system does not operate properly when two or more user interfaces are attached in the simultaneous operation system mode Setting T1 T2 input setting Remote control is a...

Page 24: ...essor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit boa...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...3P668115 4E 2022 11 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: