FDQ125C7VEB
Split System air conditioners
4PW71105-1 – 08.2011
Installation manual
6
E
LECTRIC
WIRING
WORK
General instructions
■
All field supplied parts and materials and electric works must
conform to local codes.
■
Use copper wire only.
■
Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".
■
All wiring must be performed by an authorized electrician.
■
Attach the earth leakage circuit breaker and fuse to the power
supply line.
■
A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
■
Refer to the installation manual delivered with the outdoor unit
for the size of power supply electric wire connected to the
outdoor unit, the capacity of the earth leakage breaker and fuse
and for wiring instructions.
■
Be sure to ground the air conditioner.
■
Do not connect the ground wire to:
-
gas pipes: might cause explosions or fire if gas leaks.
-
telephone ground wires or lightning rods: might cause
abnormally high electric potential in the ground during
lightning storms.
-
plumbing pipes: no grounding effect if hard vinyl piping is
used.
■
Make sure electrical wires are stripped
equally.
Electrical characteristics
MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
Specifications for field wire
W
IRING
EXAMPLE
AND
HOW
TO
SET
THE
REMOTE
CONTROLLER
How to connect wiring
Remove the switch box cover as shown in
figure 13
, and make the
connections.
Precautions
1.
Observe the notes mentioned below when wiring to the power
supply terminal board.
•
Use a round crimp-style terminal for insulation sleeve for
connection to the terminal block for wiring the units. When
none are available, follow the instructions below.
•
Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
•
When connecting wires of the same gauge, connect them
according to the figure.
Use the specified electric wire. Connect the wire securely to
the terminal. Lock the wire down without applying excessive
force to the terminal. Use torques according to the table below.
•
When attaching the control box lid, make sure not to pinch
any wires.
•
After all wiring connections are done, fill in any gaps in the
casing wiring holes with putty or insulation material (field
supply) thus to prevent small animals or dirt from entering the
unit from outside and causing short circuits in the control box.
2.
Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.
3.
Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.
4.
For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.
5.
Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.
6.
Use only specified wires and tightly connect wires to the terminals.
Be careful that wires do not place external stress on the terminals.
Keep wiring in neat order so that they do not obstruct other
equipment such as popping open the switch box cover. Make sure
the cover closes tight. Incomplete connections could result in
overheating, and in the worse case, electric shock or fire.
Hz
Volts
Voltage
range
Power supply
MCA
MFA
50/60
220-240/220
±10%
2.9
16 A
NOTE
For details, refer to "Electrical data" in the technical
data book.
Wire
Size (mm
2
)
Length
Between
indoor units
H05VV-U4G
(a),(b)
(a) Shows only in case of protected pipes. Use H07RN-F in case of no protection.
(b) Run transmission wiring between the indoor and outdoor units through a conduit
to protect against external forces, and feed the conduit through the wall together
with refrigerant piping.
2.5
—
Unit-Remote
controller
Sheathed wire
(2 wire)
(c)
(c) Use double insulation wire for remote controller (sheath thickness:
≥
1 mm) or run
wires through a wall or conduit so that the user cannot come in contact with them.
0.75–1.25
Max. 500 m
(d)
(d) This length shall be the total extended length in the system of the group control.
1
Switch box cover
2
Switch box low voltage wiring inlet
3
Switch box high voltage wiring inlet
4
Wiring diagram
5
Switch box
Tightening torque (N•m)
Terminal block for unit transmission and remote controller
0.9
Terminal block for power supply
1.2
NOTE
The customer has the ability to select the remote
controller thermistor.
1
2
3
1
Round crimp-style terminal
2
Attach insulation sleeve
3
Wiring
Summary of Contents for FDQ125C7VEB
Page 1: ...INSTALLATION MANUAL FDQ125C7VEB Split System air conditioners ...
Page 13: ......
Page 14: ......