Installation manual
7
FDQ125C7VEB
Split System air conditioners
4PW71105-1 – 08.2011
W
IRING
EXAMPLE
■
Fit the power supply wiring of each system with a switch and
fuse as shown in
figure 14
and
figure 15
.
Complete system example (3 systems)
Precautions
1.
A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
2.
For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.
Field setting
Field setting must be made from the remote controller in accordance
with the installation condition.
■
Setting can be made by changing the "Mode number", "FIRST
CODE No." and "SECOND CODE No.".
■
For setting and operation, refer to "Field setting" in the
installation manual of the remote controller.
Setting for optional accessories
In case of connecting optional accessories, refer to the operation
manuals provided with the optional accessories and establish
necessary settings.
External static pressure setting
Settings for external static pressure can be achieved in 2 ways:
Using the airflow automatic adjustment function
Airflow automatic adjustment is the volume of blow-off air that
has been automatically adjusted to the rated quantity.
1
Make sure the test run is done with a dry coil.
If the coil is not dry, run the unit for 2 hours with fan only to dry
the coil.
2
Check if the power supply wiring to the air conditioning unit is
completed along with the duct installation.
If a closing damper is installed in the air conditioning unit, make
sure that it is open.
Also check if the air filter is properly attached into the air
passage on the air suction side of the air conditioning unit.
3
If there is more than one air inlet and outlet, adjust the dampers
so that the airflow rate of each air inlet and outlet is conform with
the designed airflow rate.
Make sure the air conditioning unit is in fan operation mode.
Press and set the airflow adjustment button on the remote
controller to change the airflow rate to H or L.
4
Setting the airflow automatic adjustment settings.
When the air conditioning unit is running in fan operation mode
perform the next steps:
-
stop the air conditioning unit,
-
go to field setting mode,
-
select mode No. 21 (or 11 in case of group setting),
-
set the first code No. to "7",
-
set the second code No. to "03".
Return to normal operating mode after setting these settings
and press the ON/OFF operation button. The operation lamp will
light up and the air conditioning unit will start the fan operation
for airflow automatic adjustment.
After 1 to 8 minutes, the air conditioning unit stops operating
automatically when the fan operation for airflow automatic
adjustment has been carried out, the operation lamp will be off.
1
Power supply
2
Main switch
3
Fuse
4
Outdoor unit
5
Indoor unit
6
Remote controller (optional accessory)
When using 1 remote controller for 1 indoor unit. (Normal
operation) (See
figure 14
and
figure 15
)
Use with 2 remote controllers
(See figure 16)
(a)
(a) Shown in figure is with common power supply
For group control
(See figure 17)
(a)
NOTE
It is not necessary to designate an indoor unit address
when using group control. The address is automatically
set when the power is activated.
NOTE
To comply with EN/IEC 61000-3-12
(b)
, following rules
must be considered:
■
If the combination of units is one of the following,
use separate power supplies.
(See figure 15)
2x F RZQ250C
■
Otherwise, refer to the table with S
sc
(short-circuit
power) values for FDQ_C combinations, to be
found on the extranet.
-
If no S
sc
value is mentioned in the table for the
used combination, the common power supply
wire delivered with the unit can be used.
(See
figure 14)
-
If a S
sc
value is mentioned in the table for the
used combination, either the common power
supply wire delivered with the unit (see
figure 14
) or separate power supplies (see
figure 15
) can be used. Daikin recommends to
use separate power supplies.
Refer to the wiring diagram for connections. For more
details, refer to the electrical data.
(b) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to low-voltage systems with
input current >16 A and
≤
75 A per phase.
L N
1 2
3
L N
1 2
3
Accessory delivered with
the unit
Do not adjust the dampers during fan operation for
airflow automatic adjustment.
Mode
No.
First
code No.
Second
code No.
Setting content
11 (21)
7
01
Airflow adjustment is OFF
02
Completion of airflow adjustment
03
Start of airflow adjustment