Installation manual

1

FDQ125C7VEB

Split System air conditioners

4PW71105-1 – 08.2011

C

ONTENTS

Page

Before installation.............................................................................. 1

Selecting installation site................................................................... 2

Preparations before installation......................................................... 2

Indoor unit installation ....................................................................... 3

Refrigerant piping work ..................................................................... 3

Drain piping work .............................................................................. 4

Electric wiring work ........................................................................... 6

Wiring example and how to set the remote controller ....................... 6

Wiring example ................................................................................. 7

Installation of the decoration panel ................................................... 8

Test operation.................................................................................... 8

Wiring diagram .................................................................................. 9

The English text is the original instruction. Other languages are
translations of the original instructions.

B

EFORE

 

INSTALLATION

Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.

Refer to the installation manual of the outdoor unit for items not
described in this manual.

Caution concerning refrigerant series R410A:
The connectable outdoor units must be designed exclusively for
R410A.

Precautions

Do not install or operate the unit in rooms mentioned below.

Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)

Where corrosive gas like sulphurous gas exists. (Copper
tubing and brazed spots may corrode.)

Where volatile flammable gas like thinner or gasoline is used.

Where machines generating electromagnetic waves exist.
(Control system may malfunction.)

The unit should be installed at least 2.5 m from the floor.

Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories).
Also in vehicles or vessels.

Do not install accessories on the casing directly. Drilling holes in
the casing may damage electrical wires and consequently cause
fire.

Accessories

Check if the following accessories are included with your unit.

Screws for fixing panels are attached to the air inlet panel.

Optional accessories

Select an optional remote controller according to customer
request and install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.

When installing bottom suction: air inlet panel and canvas
connection for the air inlet panel.

FDQ125C7VEB

Split System air conditioners

Installation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

Metal clamp

1 piece

Drain hose

1 piece

Washer for 

hanging bracket

8 pieces

Medium 

sealing pad

2 pieces

Insulation for fitting

Large sealing pad

1 piece

for gas pipe

1 piece

for liquid pipe

1 piece

Installation and 

operation manual

Screws for duct flanges

1 set

16 pieces.

Wire for common 

power supply

2 pieces.

1

2

Summary of Contents for FDQ125C7VEB

Page 1: ...INSTALLATION MANUAL FDQ125C7VEB Split System air conditioners ...

Page 2: ... 680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5 6 2 1 5 4 1 3 2 6 4 4 A A 1 2 3 4 5 6a 6b 6c 7a 7b 7c 8 9 10 11 ...

Page 3: ...ÙÔ ÈÛÙÔ ÔÈËÙÈÎfi C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom posi...

Page 4: ...east 2 5 m from the floor Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may damage electrical wires and consequently cause fire Accessories Check if the following accessories are included with your unit Screws for fix...

Page 5: ...e to prevent that the fan blades or heat exchanger be touched The protection must comply with relevant European and national regulations 3 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling before installing the unit PREPARATIONS BEFORE INSTALLATION 1 Relation of ceiling opening to unit ...

Page 6: ...e gas piping and the liquid piping Otherwise this can sometimes result in water leakage Before rigging tubes check which type of refrigerant is used Use a pipe cutter and flare suitable for the used refrigerant To prevent dust moisture or other foreign matter from infiltrating the tube either pinch the end or cover it with tape Use copper alloy seamless pipes ISO 1337 The outdoor unit is charged w...

Page 7: ...t of at least 1 100 so that air may not remain trapped inside the pipe Keep pipe size equal to or greater than that of the connecting pipe vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter Push the supplied drain hose as far as possible over the drain socket Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part as indicated in the illustration Wrap th...

Page 8: ...l board and confirm drain operation Be aware that the fan will turn during the operation After confirming drainage turn off the power 1 Ceiling slab 2 Hanger bracket 3 Adjustable range 4 Drain raising pipe 5 Drain hose supplied with the unit 6 Clamp metal supplied with the unit Installation A mm Rear suction installation 231 When canvas duct is installed 350 530 When air inlet panel is directly in...

Page 9: ... the terminal Use torques according to the table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done fill in any gaps in the casing wiring holes with putty or insulation material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Do not connect wires of di...

Page 10: ... fan operation mode perform the next steps stop the air conditioning unit go to field setting mode select mode No 21 or 11 in case of group setting set the first code No to 7 set the second code No to 03 Return to normal operating mode after setting these settings and press the ON OFF operation button The operation lamp will light up and the air conditioning unit will start the fan operation for a...

Page 11: ...and decoration panel TEST OPERATION Refer to the section of For the following items take special care during construction and check after installation is finished on page 2 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank c...

Page 12: ...DIODE BRIDGE V2R POWER MODULE X1M TERMINAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Z1C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR ADAPTOR WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SELECTOR SWITCH MAIN SUB FIELD WIRING BLK BLACK ORG ORANGE CONNECTOR BLU BLUE PNK PINK WIRE CLAMP BR...

Page 13: ......

Page 14: ......

Page 15: ... 2 3 4 5 P1 P2 6 2 3 4 5 P1 P2 2 3 4 5 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 6 13 1 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 L N 3 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 6 L N L N 1 1 1 1 1 1 L N 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 12 13 14 15 16 17 ...

Page 16: ...4PW71105 1 08 2011 Copyright 2011 Daikin ...

Reviews: