16 Energy saving and optimum operation

Installer and user reference guide

25

FCAHG71~140HVEB
Split system air conditioners
4P561449-1A – 2019.09

15.4

Adjusting the air flow direction

Refer to the operation manual of the user interface.

15.4.1

About the air flow flap

Double flow+multi-flow units

For  the  following  conditions,  a  micro  computer  controls  the  air  flow
direction which may be different from the display.

Cooling

Heating

▪ When the room temperature is

lower 

than 

the 

set

temperature.

▪ When starting operation.

▪ When the room temperature is

higher 

than 

the 

set

temperature.

▪ At defrost operation.

▪ When operating continuously at horizontal air flow direction.

▪ When continuous operation with downward air flow is performed

at the time of cooling with a ceiling-suspended or a wall-mounted
unit, the micro computer may control the flow direction, and then
the user interface indication will also change.

The air flow direction can be adjusted in one of the following ways:

▪ The air flow flap itself adjusts its position.

▪ The air flow direction can be fixed by the user.

▪ Automatic 

 and desired position  .

WARNING

Never touch the air outlet or the horizontal blades while the
swing  flap  is  in  operation.  Fingers  may  become  caught  or
the unit may break down.

NOTICE

▪ The  movable  limit  of  the  flap  is  changeable.  Contact

your dealer for details. (only for double-flow, multi-flow,
corner, ceiling-suspended and wall-mounted).

▪ Avoid operating in the horizontal direction 

. It may

cause dew or dust to settle on the ceiling or flap.

15.5

Active circulation airflow

Use active circulation airflow to heat or cool the room more quickly.

15.5.1

To start the active circulation airflow

1

Set the active circulation airflow

1

Go to the home screen.

Cool

Set to

28

°C

2

Press.

Return

Setting

Main Menu                           1/2

Circulation Airflow

Individual Air Direction

Energy Saving Options

Schedule

Maintenance Information

Configuration

3

Select Circulation airflow

Return

Setting

Main Menu                           1/2

Circulation Airflow

Individual Air Direction

Energy Saving Options

Schedule

Maintenance Information

Configuration

4

Choose enable and confirm.

Return

Setting

Return

Setting

Circulation Airflow
Enable/Disable

Enable

5

Confirm setting.

Return

Setting

Return

Setting

Circulation Airflow
Save the settings?

Yes

No

6

Go to the home screen.

Cool

Set to

28

°C

7

Check if Air Volume/direction
is set to automatic. If not set
to automatic.

Return

Setting

Return

Setting

Air Volume/direction

Air Volume

Direction

Auto

Auto

2

Turn on the unit by the user interface.

16

Energy saving and optimum
operation

Observe  the  following  precautions  to  ensure  the  system  operates
properly.

▪ Adjust  the  air  outlet  properly  and  avoid  direct  air  flow  to  room

inhabitants.

▪ Adjust  the  room  temperature  properly  for  a  comfortable

environment. Avoid excessive heating or cooling.

▪ Prevent  direct  sunlight  from  entering  a  room  during  cooling

operation by using curtains or blinds.

▪ Ventilate  often.  Extended  use  requires  special  attention  to

ventilation.

▪ Keep doors and windows closed. If the doors and windows remain

open,  air  will  flow  out  of  your  room  causing  a  decrease  in  the
cooling or heating effect.

▪ Be  careful  NOT  to  cool  or  heat  too  much.  To  save  energy,  keep

the temperature setting at a moderate level.

▪ NEVER place objects near the air inlet or the air outlet of the unit.

Doing  so  may  cause  a  reduced  heating/cooling  effect  or  stop
operation.

▪ Turn off the main power supply switch to the unit when the unit is

NOT  used  for  longer  periods  of  time.  If  the  main  power  supply
switch  is  on,  the  unit  consumes  electricity.  Before  restarting  the
unit,  turn  on  the  main  power  supply  switch  6  hours  before
operation to ensure smooth running.

▪ When the display shows 

 (time to clean the air filter), clean the

filters (see 

"17.2.1 To clean the air filter" 

[

4

 26]).

▪ Keep  the  indoor  unit  and  user  interface  at  least  1  m  away  from

televisions, radios, stereos, and other similar equipment. Failing to
do so may cause static or distorted pictures.

▪ Do  NOT  place  items  under  the  indoor  unit,  as  they  may  be

damaged by water.

▪ Condensation  may  form  if  the  humidity  is  above  80%  or  if  the

drain outlet gets blocked.

Summary of Contents for FCAHG100HVEB

Page 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71HVEB FCAHG100HVEB FCAHG125HVEB FCAHG140HVEB...

Page 2: ...nect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field setting 18 8 Commissioning 19 8 1 Overview Commissioning 19 8 2 Precautions when commissioning 19 8 3 Checklist before com...

Page 3: ...ol Explanation For more information see the installer and user reference guide 1 2 For the user If you are NOT sure how to operate the unit contact your installer This appliance can be used by childre...

Page 4: ...lation site Provide sufficient space around the unit for servicing and air circulation Make sure the installation site withstands the weight and vibration of the unit Make sure the area is well ventil...

Page 5: ...306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3...

Page 6: ...pen refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close...

Page 7: ...xerted on the terminal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will damage the head and make proper tightening impossible Over tightenin...

Page 8: ...to the hanger brackets without exerting any pressure on other parts especially on refrigerant piping drain piping and other resin parts 1 2 3 2 2 To remove the accessories from the indoor unit 1 1 1 8...

Page 9: ...n of the system must not be done at temperatures below 15 C a b c d e i f g h a Indoor unit b Outdoor unit c User interface d Suction air e Discharge air f Refrigerant piping interconnection cable g D...

Page 10: ...mind the following to avoid interference Install the wireless user interface as close as possible to the indoor unit Install the indoor unit as far as possible from the fluorescent lights Take care th...

Page 11: ...a heat resistance of at least 120 C Insulation thickness Ambient temperature Humidity Minimum thickness 30 C 75 to 80 RH 15 mm 30 C 80 RH 20 mm 5 4 Preparing electrical wiring 5 4 1 About preparing e...

Page 12: ...e installing the unit For existing ceilings use anchors For new ceilings use sunken inserts sunken anchors or other field supplied parts A c b d e a A 50 100 mm In case of installation with standard p...

Page 13: ...size Keep the pipe size equal to or greater than that of the connecting pipe vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter Slope Make sure the drain piping slopes down at least 1 100 t...

Page 14: ...a Plastic watering can b Service drain outlet with rubber plug Use this outlet to drain water from the drain pan c Drain pump location d Drain pipe connection e Drain pipe 5 Turn OFF the power 6 Disc...

Page 15: ...itional refrigerant it is recommended to open the refrigerant stop valve after charging 6 3 3 Guidelines when connecting the refrigerant piping Take the following guidelines into account when connecti...

Page 16: ...on pieces 4 Wrap the sealing pad from the base of the unit to the top of the flare nut NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 6 4 Connecting th...

Page 17: ...ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the s...

Page 18: ...oration panel type When installing or changing the decoration panel type ALWAYS check if the correct values are set If the decoration panel is used Then 1 M C1 C2 Standard or self cleaning 13 23 15 01...

Page 19: ...interface is used However remove the wires attached to the user interface terminal board of the master unit 1 50 Hz 220 240 V b a e1 A B e2 c d A Master unit B Slave unit a Interconnection cable b Pow...

Page 20: ...d The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the...

Page 21: ...se power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires Error code Possible cause L4 The air inlet or air outlet is b...

Page 22: ...Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper mot...

Page 23: ...68 4 72 15 50 0 25 61 13 User interface CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happ...

Page 24: ...unit will stop fan operation the refrigerant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on th...

Page 25: ...2 Circulation Airflow Individual Air Direction Energy Saving Options Schedule Maintenance Information Configuration 4 Choose enable and confirm Return Setting Return Setting Circulation Airflow Enable...

Page 26: ...N Before accessing terminal devices make sure to interrupt all power supply NOTICE When cleaning the heat exchanger make sure to remove the switch box fan motor drain pump and float switch Water or de...

Page 27: ...tlet vents of indoor units and outdoor units Clean air filters and casings of indoor units see 17 2 1 To clean the air filter 426 and 17 2 3 To clean the air outlet and outside panels 427 Turn on the...

Page 28: ...oms or malfunction and details of the defect WARNING Do NOT modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire...

Page 29: ...ower failure Wait until power is restored If power failure occurs during operation the system automatically restarts immediately after power is restored Check if no fuse has blown or breaker is activa...

Page 30: ...ling or defrost operation This is the sound of refrigerant gas flowing through both indoor and outdoor units A hissing sound which is heard at the start or immediately after stopping operation or defr...

Page 31: ...lication Accessories Labels manuals information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation O...

Page 32: ...4P561449 1A 2019 09 Copyright 2018 Daikin...

Reviews: