1 General safety precautions

Installer and user reference guide

4

FCAHG71~140HVEB

Split system air conditioners

4P561449-1A – 2019.09

NOTICE

Improper  installation  or  attachment  of  equipment  or
accessories  could  result  in  electric  shock,  short-circuit,
leaks,  fire  or  other  damage  to  the  equipment.  Only  use
accessories,  optional  equipment  and  spare  parts  made  or
approved by Daikin.

WARNING

Make  sure  installation,  testing  and  applied  materials
comply  with  applicable  legislation  (on  top  of  the
instructions described in the Daikin documentation).

CAUTION

Wear  adequate  personal  protective  equipment  (protective
gloves,  safety  glasses,…)  when  installing,  maintaining  or
servicing the system.

WARNING

Tear apart and throw away plastic packaging bags so that
nobody,  especially  children,  can  play  with  them.  Possible
risk: suffocation.

DANGER: RISK OF BURNING

▪ Do  NOT  touch  the  refrigerant  piping,  water  piping  or

internal parts during and immediately after operation. It
could  be  too  hot  or  too  cold.  Give  it  time  to  return  to
normal  temperature.  If  you  must  touch  it,  wear
protective gloves.

▪ Do NOT touch any accidental leaking refrigerant.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

CAUTION

Do NOT touch the air inlet or aluminium fins of the unit.

NOTICE

▪ Do  NOT  place  any  objects  or  equipment  on  top  of  the

unit.

▪ Do NOT sit, climb or stand on the unit.

NOTICE

Works  executed  on  the  outdoor  unit  are  best  done  under
dry weather conditions to avoid water ingress.

In  accordance  with  the  applicable  legislation,  it  might  be  necessary
to provide a logbook with the product containing at least: information
on maintenance, repair work, results of tests, stand-by periods,…

Also,  at  least,  following  information  MUST  be  provided  at  an
accessible place at the product:

▪ Instructions for shutting down the system in case of an emergency

▪ Name and address of fire department, police and hospital

▪ Name,  address  and  day  and  night  telephone  numbers  for

obtaining service

In Europe, EN378 provides the necessary guidance for this logbook.

1.3.2

Installation site

▪ Provide  sufficient  space  around  the  unit  for  servicing  and  air

circulation.

▪ Make sure the installation site withstands the weight and vibration

of the unit.

▪ Make  sure  the  area  is  well  ventilated.  Do  NOT  block  any

ventilation openings.

▪ Make sure the unit is level.

Do NOT install the unit in the following places:

▪ In potentially explosive atmospheres.

▪ In  places  where  there  is  machinery  that  emits  electromagnetic

waves.  Electromagnetic  waves  may  disturb  the  control  system,
and cause malfunction of the equipment.

▪ In  places  where  there  is  a  risk  of  fire  due  to  the  leakage  of

flammable  gases  (example:  thinner  or  gasoline),  carbon  fibre,
ignitable dust.

▪ In  places  where  corrosive  gas  (example:  sulphurous  acid  gas)  is

produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.

Instructions for equipment using R32 refrigerant

If applicable.

WARNING

▪ Do NOT pierce or burn.

▪ Do  NOT  use  means  to  accelerate  the  defrosting

process  or  to  clean  the  equipment,  other  than  those
recommended by the manufacturer.

▪ Be  aware  that  R32  refrigerant  does  NOT  contain  an

odour.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (example:  open  flames,  an
operating  gas  appliance  or  an  operating  electric  heater)
and have a room size as specified below.

NOTICE

▪ Do NOT re-use joints which have been used already.

▪ Joints  made  in  installation  between  parts  of  refrigerant

system shall be accessible for maintenance purposes.

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation  (for  example  national  gas  regulation)  and  are
executed only by authorised persons.

Installation space requirements

NOTICE

▪ Pipework shall be protected from physical damage.

▪ Installation of pipework shall be kept to a minimum.

WARNING

If  appliances  contain  R32  refrigerant,  the  floor  area  of  the
room  in  which  the  appliances  are  installed,  operated  and
stored  MUST  be  larger  than  the  minimum  floor  area
defined in table below A (m

2

). This applies to:

▪ Indoor  units 

without

  a  refrigerant  leakage  sensor;  in

case  of  indoor  units 

with

  refrigerant  leakage  sensor,

consult the installation manual

▪ Outdoor  units  installed  or  stored  indoors  (e.g.  winter

garden, garage, machinery room)

▪ Pipework in unventilated spaces

Summary of Contents for FCAHG100HVEB

Page 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71HVEB FCAHG100HVEB FCAHG125HVEB FCAHG140HVEB...

Page 2: ...nect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field setting 18 8 Commissioning 19 8 1 Overview Commissioning 19 8 2 Precautions when commissioning 19 8 3 Checklist before com...

Page 3: ...ol Explanation For more information see the installer and user reference guide 1 2 For the user If you are NOT sure how to operate the unit contact your installer This appliance can be used by childre...

Page 4: ...lation site Provide sufficient space around the unit for servicing and air circulation Make sure the installation site withstands the weight and vibration of the unit Make sure the area is well ventil...

Page 5: ...306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3...

Page 6: ...pen refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close...

Page 7: ...xerted on the terminal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will damage the head and make proper tightening impossible Over tightenin...

Page 8: ...to the hanger brackets without exerting any pressure on other parts especially on refrigerant piping drain piping and other resin parts 1 2 3 2 2 To remove the accessories from the indoor unit 1 1 1 8...

Page 9: ...n of the system must not be done at temperatures below 15 C a b c d e i f g h a Indoor unit b Outdoor unit c User interface d Suction air e Discharge air f Refrigerant piping interconnection cable g D...

Page 10: ...mind the following to avoid interference Install the wireless user interface as close as possible to the indoor unit Install the indoor unit as far as possible from the fluorescent lights Take care th...

Page 11: ...a heat resistance of at least 120 C Insulation thickness Ambient temperature Humidity Minimum thickness 30 C 75 to 80 RH 15 mm 30 C 80 RH 20 mm 5 4 Preparing electrical wiring 5 4 1 About preparing e...

Page 12: ...e installing the unit For existing ceilings use anchors For new ceilings use sunken inserts sunken anchors or other field supplied parts A c b d e a A 50 100 mm In case of installation with standard p...

Page 13: ...size Keep the pipe size equal to or greater than that of the connecting pipe vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter Slope Make sure the drain piping slopes down at least 1 100 t...

Page 14: ...a Plastic watering can b Service drain outlet with rubber plug Use this outlet to drain water from the drain pan c Drain pump location d Drain pipe connection e Drain pipe 5 Turn OFF the power 6 Disc...

Page 15: ...itional refrigerant it is recommended to open the refrigerant stop valve after charging 6 3 3 Guidelines when connecting the refrigerant piping Take the following guidelines into account when connecti...

Page 16: ...on pieces 4 Wrap the sealing pad from the base of the unit to the top of the flare nut NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 6 4 Connecting th...

Page 17: ...ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the s...

Page 18: ...oration panel type When installing or changing the decoration panel type ALWAYS check if the correct values are set If the decoration panel is used Then 1 M C1 C2 Standard or self cleaning 13 23 15 01...

Page 19: ...interface is used However remove the wires attached to the user interface terminal board of the master unit 1 50 Hz 220 240 V b a e1 A B e2 c d A Master unit B Slave unit a Interconnection cable b Pow...

Page 20: ...d The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the...

Page 21: ...se power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires Error code Possible cause L4 The air inlet or air outlet is b...

Page 22: ...Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper mot...

Page 23: ...68 4 72 15 50 0 25 61 13 User interface CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happ...

Page 24: ...unit will stop fan operation the refrigerant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on th...

Page 25: ...2 Circulation Airflow Individual Air Direction Energy Saving Options Schedule Maintenance Information Configuration 4 Choose enable and confirm Return Setting Return Setting Circulation Airflow Enable...

Page 26: ...N Before accessing terminal devices make sure to interrupt all power supply NOTICE When cleaning the heat exchanger make sure to remove the switch box fan motor drain pump and float switch Water or de...

Page 27: ...tlet vents of indoor units and outdoor units Clean air filters and casings of indoor units see 17 2 1 To clean the air filter 426 and 17 2 3 To clean the air outlet and outside panels 427 Turn on the...

Page 28: ...oms or malfunction and details of the defect WARNING Do NOT modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire...

Page 29: ...ower failure Wait until power is restored If power failure occurs during operation the system automatically restarts immediately after power is restored Check if no fuse has blown or breaker is activa...

Page 30: ...ling or defrost operation This is the sound of refrigerant gas flowing through both indoor and outdoor units A hissing sound which is heard at the start or immediately after stopping operation or defr...

Page 31: ...lication Accessories Labels manuals information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation O...

Page 32: ...4P561449 1A 2019 09 Copyright 2018 Daikin...

Reviews: