19 Relocation

Installer and user reference guide

30

FCAHG71~140HVEB

Split system air conditioners

4P561449-1A – 2019.09

18.1.3

Symptom: The fan direction does not
correspond to the setting

The  fan  direction  does  not  correspond  with  the  user  interface
display. The fan direction does not swing. This is because the unit is
being controlled by the micro computer.

18.1.4

Symptom: White mist comes out of a unit
(Indoor unit)

▪ When humidity is high during cooling operation. If the interior of an

indoor unit is extremely contaminated, the temperature distribution
inside  a  room  becomes  uneven.  It  is  necessary  to  clean  the
interior  of  the  indoor  unit.  Ask  your  dealer  for  details  on  cleaning
the unit. This operation requires a qualified service person.

▪ Immediately  after  the  cooling  operation  stops  and  if  the  room

temperature  and  humidity  are  low.  This  is  because  warm
refrigerant  gas  flows  back  into  the  indoor  unit  and  generates
steam.

18.1.5

Symptom: White mist comes out of a unit
(Indoor unit, outdoor unit)

When the system is changed over to heating operation after defrost
operation.  Moisture  generated  by  defrost  becomes  steam  and  is
exhausted.

18.1.6

Symptom: The user interface reads "U4"
or "U5" and stops, but then restarts after
a few minutes

This is because the user interface is intercepting noise from electric
appliances  other  than  the  air  conditioner.  The  noise  prevents
communication  between  the  units,  causing  them  to  stop.  Operation
automatically restarts when the noise ceases.

18.1.7

Symptom: Noise of air conditioners
(Indoor unit)

▪ A  "zeen"  sound  is  heard  immediately  after  the  power  supply  is

turned  on.  The  electronic  expansion  valve  inside  an  indoor  unit
starts  working  and  makes  the  noise.  Its  volume  will  reduce  in
about one minute.

▪ A  continuous  low  "shah"  sound  is  heard  when  the  system  is  in

cooling  operation  or  at  a  stop.  When  the  drain  pump  is  in
operation, this noise is heard.

▪ A  "pishi-pishi"  squeaking  sound  is  heard  when  the  system  stops

after heating operation. Expansion and contraction of plastic parts
caused by temperature change make this noise.

18.1.8

Symptom: Noise of air conditioners
(Indoor unit, outdoor unit)

▪ A  continuous  low  hissing  sound  is  heard  when  the  system  is  in

cooling  or  defrost  operation.  This  is  the  sound  of  refrigerant  gas
flowing through both indoor and outdoor units.

▪ A  hissing  sound  which  is  heard  at  the  start  or  immediately  after

stopping  operation  or  defrost  operation.  This  is  the  noise  of
refrigerant caused by flow stop or flow change.

18.1.9

Symptom: Noise of air conditioners
(Outdoor unit)

When the tone of operating noise changes. This noise is caused by
the change of frequency.

18.1.10 Symptom: Dust comes out of the unit

When  the  unit  is  used  for  the  first  time  in  a  long  time.  This  is
because dust has gotten into the unit.

18.1.11 Symptom: The units can give off odours

The  unit  can  absorb  the  smell  of  rooms,  furniture,  cigarettes,  etc.,
and then emit it again.

18.1.12 Symptom: The outdoor unit fan does not

spin

During  operation.  The  speed  of  the  fan  is  controlled  in  order  to
optimise product operation.

18.1.13 Symptom: The display shows "88"

This  is  the  case  immediately  after  the  main  power  supply  switch  is
turned  on  and  means  that  the  user  interface  is  in  normal  condition.
This continues for 1 minute.

18.1.14 Symptom: The compressor in the outdoor

unit does not stop after a short heating
operation

This is to prevent refrigerant from remaining in the compressor. The
unit will stop after 5 to 10 minutes.

19

Relocation

Contact  your  dealer  for  removing  and  reinstalling  the  total  unit.
Moving units requires technical expertise.

20

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

21

Glossary

Dealer

Sales distributor for the product.

Authorised installer

Technical  skilled  person  who  is  qualified  to  install  the
product.

User

Person  who  is  owner  of  the  product  and/or  operates  the
product.

Applicable legislation

All  international,  European,  national  and  local  directives,
laws,  regulations  and/or  codes  that  are  relevant  and
applicable for a certain product or domain.

Service company

Qualified  company  which  can  perform  or  coordinate  the
required service to the product.

Installation manual

Instruction  manual  specified  for  a  certain  product  or
application, explaining how to install, configure and maintain
it.

Operation manual

Instruction  manual  specified  for  a  certain  product  or
application, explaining how to operate it.

Summary of Contents for FCAHG100HVEB

Page 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71HVEB FCAHG100HVEB FCAHG125HVEB FCAHG140HVEB...

Page 2: ...nect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field setting 18 8 Commissioning 19 8 1 Overview Commissioning 19 8 2 Precautions when commissioning 19 8 3 Checklist before com...

Page 3: ...ol Explanation For more information see the installer and user reference guide 1 2 For the user If you are NOT sure how to operate the unit contact your installer This appliance can be used by childre...

Page 4: ...lation site Provide sufficient space around the unit for servicing and air circulation Make sure the installation site withstands the weight and vibration of the unit Make sure the area is well ventil...

Page 5: ...306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3...

Page 6: ...pen refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close...

Page 7: ...xerted on the terminal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will damage the head and make proper tightening impossible Over tightenin...

Page 8: ...to the hanger brackets without exerting any pressure on other parts especially on refrigerant piping drain piping and other resin parts 1 2 3 2 2 To remove the accessories from the indoor unit 1 1 1 8...

Page 9: ...n of the system must not be done at temperatures below 15 C a b c d e i f g h a Indoor unit b Outdoor unit c User interface d Suction air e Discharge air f Refrigerant piping interconnection cable g D...

Page 10: ...mind the following to avoid interference Install the wireless user interface as close as possible to the indoor unit Install the indoor unit as far as possible from the fluorescent lights Take care th...

Page 11: ...a heat resistance of at least 120 C Insulation thickness Ambient temperature Humidity Minimum thickness 30 C 75 to 80 RH 15 mm 30 C 80 RH 20 mm 5 4 Preparing electrical wiring 5 4 1 About preparing e...

Page 12: ...e installing the unit For existing ceilings use anchors For new ceilings use sunken inserts sunken anchors or other field supplied parts A c b d e a A 50 100 mm In case of installation with standard p...

Page 13: ...size Keep the pipe size equal to or greater than that of the connecting pipe vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter Slope Make sure the drain piping slopes down at least 1 100 t...

Page 14: ...a Plastic watering can b Service drain outlet with rubber plug Use this outlet to drain water from the drain pan c Drain pump location d Drain pipe connection e Drain pipe 5 Turn OFF the power 6 Disc...

Page 15: ...itional refrigerant it is recommended to open the refrigerant stop valve after charging 6 3 3 Guidelines when connecting the refrigerant piping Take the following guidelines into account when connecti...

Page 16: ...on pieces 4 Wrap the sealing pad from the base of the unit to the top of the flare nut NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 6 4 Connecting th...

Page 17: ...ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the s...

Page 18: ...oration panel type When installing or changing the decoration panel type ALWAYS check if the correct values are set If the decoration panel is used Then 1 M C1 C2 Standard or self cleaning 13 23 15 01...

Page 19: ...interface is used However remove the wires attached to the user interface terminal board of the master unit 1 50 Hz 220 240 V b a e1 A B e2 c d A Master unit B Slave unit a Interconnection cable b Pow...

Page 20: ...d The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the...

Page 21: ...se power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires Error code Possible cause L4 The air inlet or air outlet is b...

Page 22: ...Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper mot...

Page 23: ...68 4 72 15 50 0 25 61 13 User interface CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happ...

Page 24: ...unit will stop fan operation the refrigerant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on th...

Page 25: ...2 Circulation Airflow Individual Air Direction Energy Saving Options Schedule Maintenance Information Configuration 4 Choose enable and confirm Return Setting Return Setting Circulation Airflow Enable...

Page 26: ...N Before accessing terminal devices make sure to interrupt all power supply NOTICE When cleaning the heat exchanger make sure to remove the switch box fan motor drain pump and float switch Water or de...

Page 27: ...tlet vents of indoor units and outdoor units Clean air filters and casings of indoor units see 17 2 1 To clean the air filter 426 and 17 2 3 To clean the air outlet and outside panels 427 Turn on the...

Page 28: ...oms or malfunction and details of the defect WARNING Do NOT modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire...

Page 29: ...ower failure Wait until power is restored If power failure occurs during operation the system automatically restarts immediately after power is restored Check if no fuse has blown or breaker is activa...

Page 30: ...ling or defrost operation This is the sound of refrigerant gas flowing through both indoor and outdoor units A hissing sound which is heard at the start or immediately after stopping operation or defr...

Page 31: ...lication Accessories Labels manuals information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation O...

Page 32: ...4P561449 1A 2019 09 Copyright 2018 Daikin...

Reviews: