7 Commissioning

Installation and operation manual

11

FCAG35~140AVEB
Split system air conditioners
4P471224-1 – 2017.03

7

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

7.1

Checklist before commissioning

Do NOT operate the system before the following checks are OK:

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

In case a wireless user interface is used: The 

indoor unit

decoration panel

 with infrared receiver is installed.

The 

outdoor unit

 is properly mounted.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed  according  to  this  document,  and  have  not  been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

The 

insulation resistance

 of the compressor is OK.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

7.2

To perform a test run

This  task  is  only  applicable  when  using  the  BRC1E52  or  BRC1E53
user  interface.  When  using  any  other  user  interface,  see  the
installation manual or service manual of the user interface.

NOTICE

Do not interrupt the test run.

INFORMATION

Backlight.

  To  perform  an  ON/OFF  action  on  the  user

interface,  the  backlight  does  not  need  to  be  lit.  For  any
other  action,  it  needs  to  be  lit  first.  The  backlight  is  lit  for
±30 seconds when you press a button.

1

Perform introductory steps.

#

Action

1

Open the liquid stop valve (A) and gas stop valve (B)
by removing the stem cap and turning
counterclockwise with a hex wrench until it stops.

A

B

2

Close the service cover to prevent electric shocks.

3

Turn ON power for at least 6 hours before starting
operation to protect the compressor.

4

On the user interface, set the unit to cooling operation
mode.

2

Start the test run

#

Action

Result

1

Go to the home menu.

Cool

Set to

28

°C

2

Press at least 4 seconds.

The Service Settings menu
is displayed.

3

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

4

Press.

Test Operation is
displayed on the home
menu.

Cool

Return

Setting

Test Operation

5

Press within 10 seconds.

Test run starts.

3

Check operation for 3 minutes.

4

Check operation of the airflow direction.

#

Action

Result

1

Press.

Return 

Setting

Return

Setting

Air Volume/direction

Air Volume

Direction

Position 0

Low

2

Select Position 0.

Return 

Setting

Return

Setting

Air Volume/direction

Air Volume

Direction

Low

Position 0

3

Change the position.

If the airflow flap of the
indoor unit moves,
operation is OK.

If not, operation is not OK.

Summary of Contents for FCAG35AVEB

Page 1: ...tion and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAG35AVEB FCAG50AVEB FCAG60AVEB FCAG71AVEB FCAG100AVEB FCAG125AVEB FCAG...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...rranty 17 12 3 1 Warranty period 17 12 3 2 Recommended maintenance and inspection 17 13 Troubleshooting 18 13 1 Symptoms that are NOT system malfunctions 18 13 1 1 Symptom The system does not operate...

Page 4: ...door temperature 15 46 C DB Indoor temperature 18 37 C DB 12 28 C WB RQ71 125 Outdoor temperature 5 46 C DB 9 21 C DB 10 15 C WB Indoor temperature 18 37 C DB 12 28 C WB 10 27 C DB Outdoor units Cooli...

Page 5: ...nel 263 mm In case of installation with fresh air intake kit 100 140 class 256mm In case of installation with standard panel 306mm In case of installation with fresh air intake kit 316mm In case of in...

Page 6: ...ern for installation upper part of the packing d Screws accessories Ceiling opening and unit Make sure the ceiling opening is within the following limits Minimum 860 mm to be able to fit the unit Maxi...

Page 7: ...ing Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with a correct gauge for the operating capacity of the units 100 675 mm a a T joint To connect the drain...

Page 8: ...fications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulation In...

Page 9: ...make sure the numbers match with the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to pr...

Page 10: ...10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneous operation system We recommend using the optional user interface to set the slave unit Perform the following steps...

Page 11: ...ng the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION Backli...

Page 12: ...and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E7 There is a...

Page 13: ...OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG...

Page 14: ...ctions of the system For more information about the user interface see the operation manual of the installed user interface 11 Operation 11 1 Operation range Use the system in the following temperatur...

Page 15: ...isplay Hot start In order to prevent cold air from blowing out of an indoor unit at the start of heating operation the indoor fan is automatically stopped The display of the user interface shows It ma...

Page 16: ...oating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth CAUTION Before accessing terminal devic...

Page 17: ...ly flammable refrigerant they normally don t leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in a fire in case of R32 or the...

Page 18: ...re NOT system malfunctions The following symptoms are NOT system malfunctions 13 1 1 Symptom The system does not operate The air conditioner does not start immediately after the ON OFF button on the u...

Page 19: ...of operating noise changes This noise is caused by the change of frequency 13 1 10 Symptom Dust comes out of the unit When the unit is used for the first time in a long time This is because dust has...

Page 20: ...4P471224 1 2017 03 Copyright 2017 Daikin...

Reviews: