background image

6 Configuration

Installation and operation manual

10

FCAG35~140AVEB

Split system air conditioners

4P471224-1 – 2017.03

If the distance to the floor is (m)

Then

1

M

C1

C2

≤2.7

13 (23)

0

01

2.7<x≤3.0

02

3.0<x≤3.5

03

Setting: Air flow direction

This setting must correspond with the actual used air flow directions.
See  the  installation  manual  of  the  optional  blocking  pad  kit  and  the
manual of the user interface.

Default: 01 (= all-round air flow)

Example: 

1

2

3

4

1

2

3

4

1

2

3

a

b

c

a

All-round air flow

b

4-way air flow (all air outlets open, 2 corners closed)
(optional blocking pad kit required)

c

3-way air flow (1 air outlet closed, all corners open)
(optional blocking pad kit required)

Setting: Air volume when thermostat control is OFF

This  setting  must  correspond  with  the  needs  of  the  user.  It
determines  the  fan  speed  of  the  indoor  unit  during  thermostat  OFF
condition.

1

If you have set the fan to operate, set the air volume speed:

If you want

Then

1

Outdoor unit

M

C1

C2

General

3MX+4MX

+5MX

During cooling
operation

LL

2

12

(22)

6

01

Setup volume

2

02

During heating
operation

LL

2

Monitoring 1

2

12

(22)

3

01

Setup volume

2

Monitoring 2

2

02

Setting: Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which the 

TIME TO CLEAN AIR FILTER

notification is displayed on the user interface. When using a wireless
user  interface,  you  must  also  set  the  address  (see  the  installation
manual of the user interface).

If you want an interval of…

(air contamination)

Then

1

M

C1

C2

±2500 h (light)

10 (20)

0

01

±1250 h (heavy)

02

No notification

3

02

Individual setting in a simultaneous operation system

We  recommend  using  the  optional  user  interface  to  set  the  slave
unit.

Perform the following steps:

2

Change  the  second  code  number  to  02  to  perform  individual
setting on the slave unit.

If you want to set the slave unit as…

Then

1

M

C1

C2

Unified setting

21(11)

01

01

Individual setting

02

3

Perform field setting for the master unit.

4

Turn off the main power supply switch.

5

Disconnect  the  remote  controller  from  the  master  unit  and
connect it to the slave unit.

6

Change to individual setting.

7

Perform field setting for the slave unit.

8

Turn off the main power supply or, in case of more slave units,
repeat the previous steps for all slave units.

9

Disconnect the user interface from the slave unit and reconnect
it to the master unit.

It  is  not  necessary  to  rewire  the  remote  controller  from  the  master
unit  if  the  optional  user  interface  is  used.  (However,  remove  the
wires  attached  to  the  user  interface  terminal  board  of  the  master
unit)

1~ 50 Hz

220-240 V

b

a

e1

A B

e2

c

d

A

Master unit

B

Slave unit

a

Interconnection cable

b

Power supply cable

c

Earth leakage circuit breaker

d

Fuse

e1

Main user interface

e2

Optional user interface

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

C1

: First code number

C2

: Second code number

: Default

(2)

Fan speed:

LL

: Low fan speed

Setup volume

: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button

on the user interface.

Monitoring  1,  2

:  The  fan  is  OFF,  but  runs  for  a  short  time  every  6  minutes  to  detect  the  room  temperature  by  Low  fan

speed (1) or by Setup volume (2).

Summary of Contents for FCAG35AVEB

Page 1: ...tion and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAG35AVEB FCAG50AVEB FCAG60AVEB FCAG71AVEB FCAG100AVEB FCAG125AVEB FCAG...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...rranty 17 12 3 1 Warranty period 17 12 3 2 Recommended maintenance and inspection 17 13 Troubleshooting 18 13 1 Symptoms that are NOT system malfunctions 18 13 1 1 Symptom The system does not operate...

Page 4: ...door temperature 15 46 C DB Indoor temperature 18 37 C DB 12 28 C WB RQ71 125 Outdoor temperature 5 46 C DB 9 21 C DB 10 15 C WB Indoor temperature 18 37 C DB 12 28 C WB 10 27 C DB Outdoor units Cooli...

Page 5: ...nel 263 mm In case of installation with fresh air intake kit 100 140 class 256mm In case of installation with standard panel 306mm In case of installation with fresh air intake kit 316mm In case of in...

Page 6: ...ern for installation upper part of the packing d Screws accessories Ceiling opening and unit Make sure the ceiling opening is within the following limits Minimum 860 mm to be able to fit the unit Maxi...

Page 7: ...ing Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with a correct gauge for the operating capacity of the units 100 675 mm a a T joint To connect the drain...

Page 8: ...fications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulation In...

Page 9: ...make sure the numbers match with the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to pr...

Page 10: ...10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneous operation system We recommend using the optional user interface to set the slave unit Perform the following steps...

Page 11: ...ng the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION Backli...

Page 12: ...and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E7 There is a...

Page 13: ...OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG...

Page 14: ...ctions of the system For more information about the user interface see the operation manual of the installed user interface 11 Operation 11 1 Operation range Use the system in the following temperatur...

Page 15: ...isplay Hot start In order to prevent cold air from blowing out of an indoor unit at the start of heating operation the indoor fan is automatically stopped The display of the user interface shows It ma...

Page 16: ...oating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth CAUTION Before accessing terminal devic...

Page 17: ...ly flammable refrigerant they normally don t leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in a fire in case of R32 or the...

Page 18: ...re NOT system malfunctions The following symptoms are NOT system malfunctions 13 1 1 Symptom The system does not operate The air conditioner does not start immediately after the ON OFF button on the u...

Page 19: ...of operating noise changes This noise is caused by the change of frequency 13 1 10 Symptom Dust comes out of the unit When the unit is used for the first time in a long time This is because dust has...

Page 20: ...4P471224 1 2017 03 Copyright 2017 Daikin...

Reviews: