Ceiling  strength

.  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

▪ For existing ceilings, use anchors.

▪ For  new  ceilings,  use  sunken  inserts,  sunken  anchors  or  other

field supplied parts.

A

c

b

d
e

a

A

50~100 mm

: In case of installation with standard panel

100~150 mm

: In case of installation with fresh air intake kit

130~180 mm

: In case of installation with self-cleaning

decoration panel

a

Ceiling slab

b

Anchor

c

Long nut or turnbuckle

d

Suspension bolt

e

Suspended ceiling

Suspension bolts.

 Use M8~M10 suspension bolts for installation.

Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
using  a  nut  and  washer  from  the  upper  and  lower  sides  of  the
hanger bracket.

(mm)

780

710

a1

b

b

a2

c

a1

Nut (field supply)

a2

Double nut (field supply)

b

Washer (accessories)

c

Hanger bracket (attached to the unit)

Paper  pattern  for  installation 

(upper  part  of  the  packing).  Use

the paper pattern to determine the correct horizontal positioning. It
contains  the  necessary  dimensions  and  centers.  You  can  attach
the paper pattern to the unit.

a

c

b

d

a

Centre of the unit

b

Centre of the ceiling opening

c

Paper pattern for installation (upper part of the packing)

d

Screws (accessories)

Ceiling opening and unit

:

▪ Make sure the ceiling opening is within the following limits:

Minimum

: 860 mm to be able to fit the unit.

Maximum

:  910  mm  to  ensure  enough  overlap  between  the

decoration  panel  and  the  suspended  ceiling.  If  the  ceiling
opening is larger, add extra ceiling material.

▪ Make  sure  the  unit  and  its  hanger  brackets  (suspension)  are

centered within the ceiling opening.

(mm)

710
840
860~910

950

c
d

e
f

780

840

860~910

950

c

d e

f

a

b

a

Drain piping

b

Refrigerant piping

c

Hanger bracket pitch (suspension)

d

Unit

e

Ceiling opening

f

Decoration panel

If A

Then

B

C

A

C

B

860 mm

(= min.)

10 mm

45 mm

910 mm

(= max.)

35 mm

20 mm

A

Ceiling opening

B

Distance between the unit and the ceiling opening

C

Overlap between the decoration panel and the suspended
ceiling

Installation  guide

.  Use  the  installation  guide  to  determine  the

correct vertical position.

A

B

C

a b c

A

In case of installation with standard decoration panel

B

In case of installation with fresh air intake kit

C

In case of installation with self-cleaning decoration panel

a

Suspended ceiling

b

Installation guide (accessory)

c

Unit

Level

. Make sure the unit is level at all 4 corners using a level or a

water-filled vinyl tube.

c

b

b

a

a

Level

b

Vinyl tube

c

Water level

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

Summary of Contents for FCAG35AVEB

Page 1: ...tion and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAG35AVEB FCAG50AVEB FCAG60AVEB FCAG71AVEB FCAG100AVEB FCAG125AVEB FCAG...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...rranty 17 12 3 1 Warranty period 17 12 3 2 Recommended maintenance and inspection 17 13 Troubleshooting 18 13 1 Symptoms that are NOT system malfunctions 18 13 1 1 Symptom The system does not operate...

Page 4: ...door temperature 15 46 C DB Indoor temperature 18 37 C DB 12 28 C WB RQ71 125 Outdoor temperature 5 46 C DB 9 21 C DB 10 15 C WB Indoor temperature 18 37 C DB 12 28 C WB 10 27 C DB Outdoor units Cooli...

Page 5: ...nel 263 mm In case of installation with fresh air intake kit 100 140 class 256mm In case of installation with standard panel 306mm In case of installation with fresh air intake kit 316mm In case of in...

Page 6: ...ern for installation upper part of the packing d Screws accessories Ceiling opening and unit Make sure the ceiling opening is within the following limits Minimum 860 mm to be able to fit the unit Maxi...

Page 7: ...ing Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with a correct gauge for the operating capacity of the units 100 675 mm a a T joint To connect the drain...

Page 8: ...fications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulation In...

Page 9: ...make sure the numbers match with the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to pr...

Page 10: ...10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneous operation system We recommend using the optional user interface to set the slave unit Perform the following steps...

Page 11: ...ng the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION Backli...

Page 12: ...and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E7 There is a...

Page 13: ...OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG...

Page 14: ...ctions of the system For more information about the user interface see the operation manual of the installed user interface 11 Operation 11 1 Operation range Use the system in the following temperatur...

Page 15: ...isplay Hot start In order to prevent cold air from blowing out of an indoor unit at the start of heating operation the indoor fan is automatically stopped The display of the user interface shows It ma...

Page 16: ...oating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth CAUTION Before accessing terminal devic...

Page 17: ...ly flammable refrigerant they normally don t leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in a fire in case of R32 or the...

Page 18: ...re NOT system malfunctions The following symptoms are NOT system malfunctions 13 1 1 Symptom The system does not operate The air conditioner does not start immediately after the ON OFF button on the u...

Page 19: ...of operating noise changes This noise is caused by the change of frequency 13 1 10 Symptom Dust comes out of the unit When the unit is used for the first time in a long time This is because dust has...

Page 20: ...4P471224 1 2017 03 Copyright 2017 Daikin...

Reviews: