background image

2 About the box

Installation and operation manual

4

FCAG35~140AVEB

Split system air conditioners

4P471224-1 – 2017.03

Technical engineering data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

extranet (authentication required).

For the installer

2

About the box

2.1

Indoor unit

2.1.1

To remove the accessories from the
indoor unit

a

e

f

d

c

b

h

j

i

g

k

l

m

a

Paper pattern for installation (upper part of packing)

b

General safety precautions

c

Indoor unit installation and operation manual

d

Installation guide

e

Washers for hanger brackets

f

Screws (to temporarily attach the paper pattern for
installation to the indoor unit)

g

Cable ties

h

Metal clamp

i

Insulation piece (drain pipe)

j

Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)

k

Drain hose

l

Insulation piece: Small (liquid pipe)

m

Insulation piece: Large (gas pipe)

3

About the units and options

3.1

About the indoor unit

Use the system in the following temperature and humidity ranges for
safe and effective operation.

For combination with R410A outdoor unit, refer to the following table:

Outdoor units

Cooling

Heating

RR71~125

Outdoor
temperature

–15~46°C DB

Indoor
temperature

18~37°C DB

12~28°C WB

RQ71~125

Outdoor
temperature

–5~46°C DB

–9~21°C DB

–10~15°C WB

Indoor
temperature

18~37°C DB

12~28°C WB

10~27°C DB

Outdoor units

Cooling

Heating

RXS35~60

Outdoor
temperature

–10~46°C DB

–15~24°C DB

–16~18°C WB

Indoor
temperature

18~32°C DB

10~30°C DB

3MXS40~68

4MXS68~80

5MXS90

Outdoor
temperature

–10~46°C DB

–15~24°C DB

–16~18°C WB

Indoor
temperature

18~32°C DB

10~30°C DB

RZQG71~140

Outdoor
temperature

–15~50°C DB

–19~21°C DB

–20~15.5°C WB

Indoor
temperature

18~37°C DB

12~28°C WB

10~27°C DB

RZQSG71~140

Outdoor
temperature

–15~46°C DB

–14~21°C DB

–15~15.5°C WB

Indoor
temperature

20~37°C DB

14~28°C WB

10~27°C DB

RZQ200~250

Outdoor
temperature

–5~46°C DB

–14~21°C DB

–15~15°C WB

Indoor
temperature

20~37°C DB

14~28°C WB

10~27°C DB

AZQS71~125

Outdoor
temperature

–15~46°C DB

–14~21°C DB

–15~15.5°C WB

Indoor
temperature

20~37°C DB

14~28°C WB

10~27°C DB

For combination with R32 outdoor unit, refer to the following table:

Outdoor units

Cooling

Heating

RXM35~60

Outdoor
temperature

–10~46°C DB

–15~24°C DB

–16~18°C WB

Indoor
temperature

18~32°C DB

10~30°C DB

3MXM40~68

4MXM68~80

5MXM90

Outdoor
temperature

–10~46°C DB

–15~24°C DB

–16~18°C WB

Indoor
temperature

18~32°C DB

10~30°C DB

RZAG71~140

Outdoor
temperature

–20~52°C DB

–19.5~21°C DB

–20~15.5°C WB

Indoor
temperature

18~37°C DB

12~28°C WB

10~27°C DB

RZASG71~140

Outdoor
temperature

–15~46°C DB

–14~21°C DB

–15~15.5°C WB

Indoor
temperature

20~37°C DB

14~28°C WB

10~27°C DB

Summary of Contents for FCAG35AVEB

Page 1: ...tion and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAG35AVEB FCAG50AVEB FCAG60AVEB FCAG71AVEB FCAG100AVEB FCAG125AVEB FCAG...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...rranty 17 12 3 1 Warranty period 17 12 3 2 Recommended maintenance and inspection 17 13 Troubleshooting 18 13 1 Symptoms that are NOT system malfunctions 18 13 1 1 Symptom The system does not operate...

Page 4: ...door temperature 15 46 C DB Indoor temperature 18 37 C DB 12 28 C WB RQ71 125 Outdoor temperature 5 46 C DB 9 21 C DB 10 15 C WB Indoor temperature 18 37 C DB 12 28 C WB 10 27 C DB Outdoor units Cooli...

Page 5: ...nel 263 mm In case of installation with fresh air intake kit 100 140 class 256mm In case of installation with standard panel 306mm In case of installation with fresh air intake kit 316mm In case of in...

Page 6: ...ern for installation upper part of the packing d Screws accessories Ceiling opening and unit Make sure the ceiling opening is within the following limits Minimum 860 mm to be able to fit the unit Maxi...

Page 7: ...ing Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with a correct gauge for the operating capacity of the units 100 675 mm a a T joint To connect the drain...

Page 8: ...fications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulation In...

Page 9: ...make sure the numbers match with the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to pr...

Page 10: ...10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneous operation system We recommend using the optional user interface to set the slave unit Perform the following steps...

Page 11: ...ng the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION Backli...

Page 12: ...and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E7 There is a...

Page 13: ...OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG...

Page 14: ...ctions of the system For more information about the user interface see the operation manual of the installed user interface 11 Operation 11 1 Operation range Use the system in the following temperatur...

Page 15: ...isplay Hot start In order to prevent cold air from blowing out of an indoor unit at the start of heating operation the indoor fan is automatically stopped The display of the user interface shows It ma...

Page 16: ...oating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth CAUTION Before accessing terminal devic...

Page 17: ...ly flammable refrigerant they normally don t leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in a fire in case of R32 or the...

Page 18: ...re NOT system malfunctions The following symptoms are NOT system malfunctions 13 1 1 Symptom The system does not operate The air conditioner does not start immediately after the ON OFF button on the u...

Page 19: ...of operating noise changes This noise is caused by the change of frequency 13 1 10 Symptom Dust comes out of the unit When the unit is used for the first time in a long time This is because dust has...