background image

7

English

[ How to detach side and bottom panels ]

Remove the screws in the side panel and pull the side panel outward (A). Then, while pushing
upwards (B), slide the panel towards the front of the unit (C). (Same for both left and right sides) 

( Refer to Fig. 6 and 7 )

After detaching the side panels, turn the bottom panel downward (D) about 45

°

, and pull it outward

(E). 

( Refer to Fig. 8 )

5. REFRIGERANT PIPING WORK

• See the installation manual for the outdoor unit for details on how to connect the refrigerant piping.

Be sure to insulate both the gas piping as well as the liquid piping. 

Not doing so may cause leaks. (Use insulation material which can fully resist the 120°C temperature that
the gas piping can sometimes reach when using a heat pump.)

If the temperature and humidity of the branch piping could possibly exceed 30°C or RH80%, reinforce the
refrigerant insulation (20mm or thicker). Condensation may form on the surface of the insulation.

Installation should only be carried out after checking in advance the type of refrigerant to be used. (Using 
the wrong refrigerant will prevent the unit from functioning properly.)

CAUTION

• Use a pipe cutter and flare suitable for the type of refrigerant.
• Apply ester oil or ether oil around the flare section before connecting.
• To prevent dust, moisuture or other foreign matter from infiltrating the tube, either pinch the end 

or cover it with tape.

• Do not allow anything other than the designated refrigerant to get mixed into the refrigerant 

circuit, such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room 
thoroughly right away.

Use copper alloy seamless pipes ( ISO 1337 ). 

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together, 
when connecting or disconnecting pipes to/from the unit. 

( Refer to Fig. 9 )

Refer to the Table 2 for flare dimensions and tightening 
torque. 

NOTE

Use the flare nut included with the unit main body.

CAUTION

Over-tightening the flare nut may break it and/or cause the refrigerant to leak.

(A)

(A)

(C)

(C)

(B)

Left side panel

Fig. 6

Fig. 7

Side panel screw

Left side 
panel

 

Top side

Right side 
panel

Right side panel

(D)

(E)

Bottom panel

Fig. 8

Approx. 45˚

Wall

Torque wrench

Flare nut

Piping union

Fig. 9

Spanner

01_EN_3P184443-2.fm  Page 7  Monday, July 3, 2006  3:14 PM

Summary of Contents for FAY71FJV1

Page 1: ...SAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO...

Page 2: ...reenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Page 3: ...guinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retningsgivende dokument er for...

Page 4: ...ry out installation work Do not try to install the machine your self Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this install...

Page 5: ...chen Plastic parts may deteriorate and fall off or result in water leakage b where corrosive gas such as sulfurous acid gas is produced Corroding copper pipes or soldered parts may result in refrigera...

Page 6: ...ote controller from Table 1 according to customer request and install in an appropriate place For installation follow the Installation manual included with the remote controllers Table 1 NOTE If the c...

Page 7: ...of the outdoor unit Items to be checked If not properly done what is likely to occur Check Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test finished It may...

Page 8: ...installation panel is attached to the rear of the unit To detach remove the screws from the bottom of the panel Refer to Fig 1 2 Attach the installation panel to the wall using the paper pattern for i...

Page 9: ...ok on the installation panel Refer to Fig 4 and 5 If running pipes from the left side or using embedded pipes remove the bottom panel to make work easier CAUTION Install the unit so that it is level o...

Page 10: ...wrong refrigerant will prevent the unit from functioning properly CAUTION Use a pipe cutter and flare suitable for the type of refrigerant Apply ester oil or ether oil around the flare section before...

Page 11: ...are leaking After checking for gas leaks in the pipe connections insulate them as shown in Fig 11 and 12 Install so that no pipes are exposed as this may cause leaking Pipe size Further tightening ang...

Page 12: ...igerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains fluorine it will damage the refrigerant oil Before brazing loc...

Page 13: ...it through the drain pipes and corrode the heat exchanger 7 ELECTRIC WIRING WORK All field supplied parts and materials and electric works must conform to local codes Use copper wire only For electric...

Page 14: ...nal board Remote controller cord connections not necessary for slave unit of simultaneous operation system Feed wires through the clamp and connect to the terminal board for transmission wiring no po...

Page 15: ...lack in the power wiring may cause abnormal heating Use sleeve insulated round pressure terminals for connections to the power terminal block If none are available connect wires of the same diameter t...

Page 16: ...he remote controller that suits the indoor unit which has the most functions as attached swing flap 4 For simultaneous operation system connect the remote controller cord to the master unit 1 2 3 P1 P...

Page 17: ...e installation manual attached to the wireless remote controller for setting instructions 3 Setting indoor unit number of simultaneous operation system When using in simultaneous operation system mode...

Page 18: ...ler from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the remote controller terminal board of the master unit 5 CONTROL BY 2 REMOTE CON...

Page 19: ...function diagnoses below 2 HOW TO DIAGNOSE FOR PROBLEMS With the power on Troubles can be monitored on the remote controller or the LED s on the PC board of the indoor unit Trouble shooting with the d...

Page 20: ...rmal mode 3 Depending on the model or the conditions it may carry out an emergency shut down 4 If the HBP H2P is off the branch wiring between each of the indoor and outdoor units may either be incorr...

Page 21: ...utdoor unit E1 Outdoor unit s PC board faulty outdoor unit E3 High pressure abnormal outdoor unit E4 Low pressure abnormal outdoor unit E5 Compressor motor lock malfunction outdoor unit E7 Outdoor fan...

Page 22: ...s shown the wiring between the indoor and outdoor units is not properly wired Therefore immediately disconnect the power supply and correct the wiring The com pressor and the fan mounted on the outdoo...

Page 23: ...OLLER KIT IS BEING USED 5 REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM CONFIRM ENGINEERING MATERIALS AND CATALOGS ETC BEFORE CONNECTING 6 SYMBOLS SHOW AS FOLLOWS RED RED BLK BLAC...

Page 24: ...YSTEM CONFIRM ENGINEERING MATERIALS AND CATALOGS ETC BEFORE CONNECTING 6 SYMBOLS SHOW AS FOLLOWS RED RED BLK BLACK WHT WHITE YLW YELLOW ORG ORANGE GRY GRAY PRP PURPLE BLU BLUE 7 CONFIRM THE METHOD OF...

Page 25: ...0608 HT 3P184443 2 EM00A030E 00_CV_3P184443 2 fm Page 2 Monday July 3 2006 2 21 PM...

Reviews: