15
English
4. Simultaneous operation system individual setting
It is easier if the optional remote controller is used when setting the slave unit.
•
Perform the following procedures when setting the master and slave unit separately.
Procedure
(1)
Change the SECOND CODE NO. to “02”, individual setting, so that the slave unit can be individually
set. ( Refer to Table 8 )
(SECOND CODE NO. is factory set to “01”, unified setting.)
Table 8
(2)
Perform field setting for the master unit.
(3)
Turn off the main power supply switch after (2).
(4)
Detach remote controller from the master unit and connect it to the slave unit.
(5)
Turn on the main power supply switch again, and as in (1), change the SECOND CODE NO. to “02”,
individual setting.
(6)
Perform field setting for the slave unit.
(7)
Turn off the main power supply switch after (6).
(8)
If there is more than one slave unit, repeat steps 4 to 7.
(9)
Detach the remote controller from the slave unit after the setting, and reattach to the master unit. This
is the end of the setting procedure.
* You do not need to rewire the remote controller from the master unit if the optional remote controller
for slave unit is used.
(However, remove the wires attached to the remote controller terminal board of the master unit.)
5. CONTROL BY 2 REMOTE CONTROLLERS
(Controlling 1 indoor unit by 2 remote controllers)
•
When using 2 remote controllers, one must be set to “MAIN” and the other to “SUB”.
MAIN/SUB CHANGEOVER
1.
Insert a wedge-head screwdriver into the recess between the upper and lower parts of remote con-
troller and, working from the 2 positions, remove carefully the upper part.
(Refer to Fig. 20)
(The remote controller PC board is attached to the upper part of the remote controller.)
2.
Turn the MAIN/SUB changeover switch on one of the two remote controller PC board to “S”.
(Leave the switch of the other remote controller set to “M”.)
(Refer to Fig. 21)
Setting
Mode No.
FIRST CODE NO.
SECOND CODE NO.
Unified setting
11 (21)
1
01
Individual setting
02
P
1
P
2
1 2 3
P
1
P
2
1 2 3
P
1
P
2
P
1
P
2
1 2 3
1 2 3
P
1
P
2
1 2 3
1 2 3
P
1
P
2
Main power supply
Main power supply
Main switch
Fuse
Fuse
Outdoor unit
Outdoor unit
Main switch
Indoor unit (Master)
Indoor unit (Master)
Indoor unit (Slave)
Indoor unit
(Slave)
Remote controller
Remote controller
( 1 ) ( 2 )
( 3 ) ( 7 )
( 4 )
( 8 )
( 5 ) ( 6 )