4 Preparation

Installation and operation manual

6

EWAQ016~ EWYQ016~064CAW

Packaged air-cooled water chiller

4P489435-1B – 2017.10

CAUTION

Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.

This  unit  is  suitable  for  installation  in  a  commercial  and
light industrial environment.

4.2

Preparing water piping

4.2.1

Water circuit requirements

NOTICE

In  case  of  plastic  pipes,  make  sure  they  are  fully  oxygen
diffusion  tight  according  to  DIN  4726.  The  diffusion  of
oxygen into the piping can lead to excessive corrosion.

Connecting piping – Legislation.

 Make all piping connections in

accordance  with  the  applicable  legislation  and  the  instructions  in
the "Installation" chapter, respecting the water inlet and outlet.

Connecting  piping  –  Force.

  Do  NOT  use  excessive  force  when

connecting  the  piping.  Deformation  of  the  piping  can  cause
malfunctioning of the unit.

Connecting  piping  –  Tools.

  Only  use  appropriate  tooling  to

handle  brass,  which  is  a  soft  material.  If  NOT,  pipes  will  get
damaged.

Connecting piping – Air, moisture, dust.

 If air, moisture or dust

gets into the circuit, problems may occur. To prevent this:

▪ Only use clean pipes

▪ Hold the pipe end downwards when removing burrs.

▪ Cover the pipe end when inserting it through a wall, to prevent

dust and/or particles entering the pipe.

▪ Use a decent thread sealant to seal connections.

NOTICE

If  glycol  is  present  in  the  system,  make  sure  the  thread
sealant used is resistant to glycol.

Closed  circuit.

  Use  the  outdoor  unit  ONLY  in  a  closed  water

system.  Using  the  system  in  an  open  water  system  will  lead  to
excessive corrosion.

Water flow.

 You can find the minimum required water flow in the

following  table.  In  all  cases,  this  flow  needs  to  be  guaranteed.
When  the  flow  is  lower,  operation  will  stop  and  error 

  will  be

displayed.

Capacity class

Minimum required flow rate

016+021+025

23 l/min

032

36 l/min

040+050

46 l/min

064

72 l/min

Field supply components – Water pressure and temperature.

Check  that  all  components  in  the  field  piping  can  withstand  the
water pressure and water temperature.

Drainage – Low points.

 Provide drain taps at all low points of the

system in order to allow complete drainage of the water circuit.

Non-brass  metallic  piping.

  When  using  non-brass  metallic

piping,  insulate  the  brass  and  non-brass  properly  so  that  they  do
NOT  make  contact  with  each  other.  This  to  prevent  galvanic
corrosion.

Shut-off  valves. 

Two  shut-off  valves  are  delivered  with  the  unit.

Install them as shown in the following figure.

a

b

a

c

d

b

a

Adapter piece (on the inlet only in case of EWAQ
+EWYQ040~064)

b

Shut-off valve

c

Bend

d

Filter

NOTICE

Before mounting the bend, attach the filter to it.

NOTICE

If the bend is not used during installation, replace it with an
extension  (5  cm  long  for  a  1¼"  filter,  and  6  cm  long  for  a
2" filter) to ensure proper cleaning operation of the filter.

NOTICE

Be  sure  to  install  the  filter  properly.  Failure  to  install  or
incorrect installation will damage the plate heat exchanger
permanently.

Drain  taps. 

Drain  taps  must  be  provided  at  all  low  points  of  the

system to permit complete drainage of the circuit. A drain valve is
provided inside the unit.

Air vents.

 Provide air vents at all high points of the system, which

must  also  be  easily  accessible  for  servicing.  An  automatic  air
purge  valve  is  provided  inside  the  unit.  Check  that  this  air  purge
valve is NOT tightened too much, so that automatic release of air
from  the  water  circuit  is  possible.  Refer  to  field  setting  [E‑04]  in

"6.2.9 Field settings on the remote controller" on page 16

.

WARNING

▪ For correct operation of the system, a regulating valve

must  be  installed  in  the  water  system.  The  regulating
valve  is  to  be  used  to  regulate  the  water  flow  in  the
system (field supply).

▪ Selecting  a  flow  outside  the  curves  can  cause

malfunction  or  damage  to  the  unit.  Also  refer  to  the
Technical specifications.

▪ The  maximum  water  piping  temperature  is  50°C  according  to

safety device setting.

▪ Always use materials which are compatible with the water used in

the system and with the materials used in the unit. (The unit piping
fittings are made of brass, the plate heat exchangers are made of
stainless  steel  316  plates  brazed  together  with  copper  and  the
optional pump housing is made of cast iron.)

▪ Select  the  piping  diameter  in  relation  to  the  required  water  flow

and available external static pressure (ESP) of the pump. See the
following table for the recommended water piping diameter.

Capacity class

Water piping diameter

016~032

1-1/4"

Summary of Contents for EWAQ016CAW

Page 1: ...oled water chiller English Installation and operation manual Packaged air cooled water chiller EWAQ016CAW EWAQ021CAW EWAQ025CAW EWAQ032CAW EWAQ040CAW EWAQ050CAW EWAQ064CAW EWYQ016CAW EWYQ021CAW EWYQ02...

Page 2: ...os t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymai...

Page 3: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 4: ...omponents 14 6 2 3 To access the field setting components 14 6 2 4 To access mode 1 or 2 14 6 2 5 To use mode 1 14 6 2 6 To use mode 2 15 6 2 7 Mode 1 Monitoring settings 15 6 2 8 Mode 2 Field setting...

Page 5: ...This installation manual concerns the packaged air cooled water chiller The unit is intended for outdoor installation and can be combined with fan coil units for air conditioning purposes or it can be...

Page 6: ...ystem in order to allow complete drainage of the water circuit Non brass metallic piping When using non brass metallic piping insulate the brass and non brass properly so that they do NOT make contact...

Page 7: ...tions must be avoided a larger minimum water volume will be required To ensure proper operation of the unit when changing the values of setting F 00 for cooling mode the minimum water volume has to be...

Page 8: ...chrader valve of the expansion vessel a a Schrader valve 4 2 5 To check the water volume Examples Example 1 The unit is installed 5 m below the highest point in the water circuit The total water volum...

Page 9: ...2 1 To provide the installation structure Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise NOTICE When the installation height of the unit needs to be...

Page 10: ...em field supply 5 3 2 To fill the water circuit 1 Connect the water supply to the drain and fill valve 2 Make sure the automatic air purge valve is open at least 2 turns 3 Fill with water until the pr...

Page 11: ...presence may lead to the precipitation of certain components in the glycol s corrosion inhibitor NOTICE Glycol absorbs water from its environment Therefore do NOT add glycol that has been exposed to a...

Page 12: ...set up use and maintain the unit Before operating the remote controller follow this installation procedure Wire specification Value Type 2 wire Section 0 75 1 25 mm2 Wire specification Value Maximum l...

Page 13: ...ation in this chapter is read sequentially by the installer and that the system is configured as applicable DANGER RISK OF ELECTROCUTION 6 2 Making field settings 6 2 1 About making field settings INF...

Page 14: ...lated stick such as a closed ball point pen to avoid touching of live parts Make sure to re attach the inspection cover into the electrical component box cover after the job is finished NOTICE Make su...

Page 15: ...e 2 There are two methods to activate low noise operation of the compressor unit and heat exchanger unit The first method is to enable an automatic low noise operation during night time by field setti...

Page 16: ...ach field setting is assigned a 3 digit number or code e g 5 03 which is indicated on the remote controller display The first digit 5 is the first code or field setting group The second and third digi...

Page 17: ...stop when active at that moment and will start again at the next scheduled ON function The last programmed command overrules the preceding programmed command and will remain active until the next pro...

Page 18: ...ng the night because temperature demands during night and day are not the same INFORMATION The setback function is enabled by default The setback function can be combined with the automatic weather de...

Page 19: ...ave a good control of the system and avoid frequent ON OFF it is advised to use the automatic weather dependent setpoint operation 6 01 Description 0 default External room thermostat not installed 1 E...

Page 20: ...e the fluid to freeze b Settings are not applicable C Leaving water temperature limits This setting is used to limit the selectable leaving water temperature on the remote controller C 00 Maximum leav...

Page 21: ...e powered up You read the complete installation and operation instructions as described in the installer and user reference guide Installation Check that the unit is properly installed to avoid abnorm...

Page 22: ...first running period of the unit the required power may be higher than stated on the nameplate of the unit This phenomenon is caused by the compressor that needs a continuous run time of 48 hours bef...

Page 23: ...b A B C D Possibility 1 Possibility 2 a 300 mm b 100 mm c 500 mm d 500 mm a 500 mm b 500 mm c 500 mm d 500 mm h1 h2 1500 500 F mm ABCD Sides along the installation site with obstacles F Front side Suc...

Page 24: ...Q N h g k g D E a Air purge valve b Temperature sensors R11T R12T R13T R14T c Expansion vessel 12 l d Shut off valve field installed e Water inlet connection f Water outlet connection g Drain port h W...

Page 25: ...or current limiting R1T Thermistor air fin R2T R15T Thermistor H E gas 1 H E de icer 1 sub cool H E gas 1 sub cool H E liquid H E liquid 1 suction 1 liquid 1 suction 2 H E gas 2 H E de icer 2 sub cool...

Page 26: ...stem A full overview of allowable combinations for future system extensions is available in technical engineering data and should be consulted Contact your installer to receive more information and pr...

Page 27: ...or a function is not available An unavailable function can mean insufficient permission level or can mean that a slave remote controller is used see 6 2 9 Field settings on the remote controller on pa...

Page 28: ...stem 12 3 1 About the clock INFORMATION The clock must be set manually Adjust the setting when switching from summertime to wintertime and vice versa The clock cannot be adjusted if the controller is...

Page 29: ...d settings on the remote controller on page 16 INFORMATION Temperature range for cooling 5 C 20 C leaving water temperature 10 C 20 C when glycol is used For setup of the schedule timer function see T...

Page 30: ...point operation 6 Set the leaving water temperature using and INFORMATION During this operation instead of showing the water temperature setpoint the controller shows the shift value which can be set...

Page 31: ...d 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting you should consult the last programmed command this may date from the day before Th...

Page 32: ...ture setpoint is enabled by default so only temperature shifts are possible no ON OFF instruction Quiet mode See To program quiet mode on page 33 Switch the mode on or off at a scheduled time Four act...

Page 33: ...seconds to program the detailed actions Result The first programmed action of the selected day appears 7 Select the action number you would like to program or to modify using 8 Set the correct action...

Page 34: ...ogrammed actions of a specific day press once Result You can now select another day using and and restart consulting and programming To copy programmed actions to next day In space heating program it...

Page 35: ...ct are necessary within the warranty period contact your dealer and keep the warranty card at hand 13 2 2 Recommended maintenance and inspection Since dust collects when using the unit for several yea...

Page 36: ...e unit with manufacturing number if possible and the installation date possibly listed on the warranty card 14 1 Error codes Overview In case a malfunction code appears on the indoor unit user interfa...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P489435 1B 2017 10 Copyright 2017 Daikin 4P489435 1 B 00000004...

Reviews: