Daikin EWAQ016CAW Installation And Operation Manual Download Page 35

13 Maintenance and service

Installation and operation manual

35

EWAQ016~ EWYQ016~064CAW
Packaged air-cooled water chiller
4P489435-1B – 2017.10

12.3.9

Operating the optional remote controller

If besides the main remote controller the optional remote controller is
installed as well, the main remote controller (master) can access all
settings  while  the  second  remote  controller  (slave)  can  not  access
schedule settings and parameter settings.

Refer to the installation manual for more details.

13

Maintenance and service

WARNING

Never replace a fuse with a fuse of a wrong ampere ratings
or  other  wires  when  a  fuse  blows  out.  Use  of  wire  or
copper wire may cause the unit to break down or cause a
fire.

CAUTION

Do not insert fingers, rods or other objects into the air inlet
or  outlet.  Do  not  remove  the  fan  guard.  When  the  fan  is
rotating at high speed, it will cause injury.

CAUTION

After  a  long  use,  check  the  unit  stand  and  fitting  for
damage. If damaged, the unit may fall and result in injury.

Water pressure

Check whether the water pressure is above 1 bar. If it is lower, add
water.

13.1

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R410A

Global warming potential (GWP) value: 2087.5

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant  charge  in  the  system  (expressed  as  tonnes
CO

2

-equivalent)  is  used  to  determine  the  maintenance

intervals. Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

Please contact your installer for more information.

WARNING

The refrigerant in the system is safe and normally does not
leak. If the refrigerant leaks in the room, contact with a fire
of  a  burner,  a  heater  or  a  cooker  may  result  in  a  harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room and contact the dealer where you purchased the unit.

Do not use the system until a service person confirms that
the portion where the refrigerant leaks is repaired.

13.2

After-sales service and warranty

13.2.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

13.2.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

14

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system must be repaired by a qualified service person:

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does not properly work.

Turn off the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does not work
well.

Turn off the power.

If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.

Notify your installer and
report the malfunction
code.

If  the  system  does  not  properly  operate  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  according  to  the  following
procedures.

Malfunction

Measure

The remote controller
display is blank.

▪ Check  if  there  is  no  power  failure.  Wait

until  power  is  restored.  If  power  failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

▪ Check  if  the  benefit  kWh  rate  power

supply is active.

An error code is
displayed on the
remote controller.

Consult your local dealer. Refer to

"8.1 Error codes: Overview" on page 22

 for

a detailed list of error codes.

Summary of Contents for EWAQ016CAW

Page 1: ...oled water chiller English Installation and operation manual Packaged air cooled water chiller EWAQ016CAW EWAQ021CAW EWAQ025CAW EWAQ032CAW EWAQ040CAW EWAQ050CAW EWAQ064CAW EWYQ016CAW EWYQ021CAW EWYQ02...

Page 2: ...os t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymai...

Page 3: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 4: ...omponents 14 6 2 3 To access the field setting components 14 6 2 4 To access mode 1 or 2 14 6 2 5 To use mode 1 14 6 2 6 To use mode 2 15 6 2 7 Mode 1 Monitoring settings 15 6 2 8 Mode 2 Field setting...

Page 5: ...This installation manual concerns the packaged air cooled water chiller The unit is intended for outdoor installation and can be combined with fan coil units for air conditioning purposes or it can be...

Page 6: ...ystem in order to allow complete drainage of the water circuit Non brass metallic piping When using non brass metallic piping insulate the brass and non brass properly so that they do NOT make contact...

Page 7: ...tions must be avoided a larger minimum water volume will be required To ensure proper operation of the unit when changing the values of setting F 00 for cooling mode the minimum water volume has to be...

Page 8: ...chrader valve of the expansion vessel a a Schrader valve 4 2 5 To check the water volume Examples Example 1 The unit is installed 5 m below the highest point in the water circuit The total water volum...

Page 9: ...2 1 To provide the installation structure Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise NOTICE When the installation height of the unit needs to be...

Page 10: ...em field supply 5 3 2 To fill the water circuit 1 Connect the water supply to the drain and fill valve 2 Make sure the automatic air purge valve is open at least 2 turns 3 Fill with water until the pr...

Page 11: ...presence may lead to the precipitation of certain components in the glycol s corrosion inhibitor NOTICE Glycol absorbs water from its environment Therefore do NOT add glycol that has been exposed to a...

Page 12: ...set up use and maintain the unit Before operating the remote controller follow this installation procedure Wire specification Value Type 2 wire Section 0 75 1 25 mm2 Wire specification Value Maximum l...

Page 13: ...ation in this chapter is read sequentially by the installer and that the system is configured as applicable DANGER RISK OF ELECTROCUTION 6 2 Making field settings 6 2 1 About making field settings INF...

Page 14: ...lated stick such as a closed ball point pen to avoid touching of live parts Make sure to re attach the inspection cover into the electrical component box cover after the job is finished NOTICE Make su...

Page 15: ...e 2 There are two methods to activate low noise operation of the compressor unit and heat exchanger unit The first method is to enable an automatic low noise operation during night time by field setti...

Page 16: ...ach field setting is assigned a 3 digit number or code e g 5 03 which is indicated on the remote controller display The first digit 5 is the first code or field setting group The second and third digi...

Page 17: ...stop when active at that moment and will start again at the next scheduled ON function The last programmed command overrules the preceding programmed command and will remain active until the next pro...

Page 18: ...ng the night because temperature demands during night and day are not the same INFORMATION The setback function is enabled by default The setback function can be combined with the automatic weather de...

Page 19: ...ave a good control of the system and avoid frequent ON OFF it is advised to use the automatic weather dependent setpoint operation 6 01 Description 0 default External room thermostat not installed 1 E...

Page 20: ...e the fluid to freeze b Settings are not applicable C Leaving water temperature limits This setting is used to limit the selectable leaving water temperature on the remote controller C 00 Maximum leav...

Page 21: ...e powered up You read the complete installation and operation instructions as described in the installer and user reference guide Installation Check that the unit is properly installed to avoid abnorm...

Page 22: ...first running period of the unit the required power may be higher than stated on the nameplate of the unit This phenomenon is caused by the compressor that needs a continuous run time of 48 hours bef...

Page 23: ...b A B C D Possibility 1 Possibility 2 a 300 mm b 100 mm c 500 mm d 500 mm a 500 mm b 500 mm c 500 mm d 500 mm h1 h2 1500 500 F mm ABCD Sides along the installation site with obstacles F Front side Suc...

Page 24: ...Q N h g k g D E a Air purge valve b Temperature sensors R11T R12T R13T R14T c Expansion vessel 12 l d Shut off valve field installed e Water inlet connection f Water outlet connection g Drain port h W...

Page 25: ...or current limiting R1T Thermistor air fin R2T R15T Thermistor H E gas 1 H E de icer 1 sub cool H E gas 1 sub cool H E liquid H E liquid 1 suction 1 liquid 1 suction 2 H E gas 2 H E de icer 2 sub cool...

Page 26: ...stem A full overview of allowable combinations for future system extensions is available in technical engineering data and should be consulted Contact your installer to receive more information and pr...

Page 27: ...or a function is not available An unavailable function can mean insufficient permission level or can mean that a slave remote controller is used see 6 2 9 Field settings on the remote controller on pa...

Page 28: ...stem 12 3 1 About the clock INFORMATION The clock must be set manually Adjust the setting when switching from summertime to wintertime and vice versa The clock cannot be adjusted if the controller is...

Page 29: ...d settings on the remote controller on page 16 INFORMATION Temperature range for cooling 5 C 20 C leaving water temperature 10 C 20 C when glycol is used For setup of the schedule timer function see T...

Page 30: ...point operation 6 Set the leaving water temperature using and INFORMATION During this operation instead of showing the water temperature setpoint the controller shows the shift value which can be set...

Page 31: ...d 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting you should consult the last programmed command this may date from the day before Th...

Page 32: ...ture setpoint is enabled by default so only temperature shifts are possible no ON OFF instruction Quiet mode See To program quiet mode on page 33 Switch the mode on or off at a scheduled time Four act...

Page 33: ...seconds to program the detailed actions Result The first programmed action of the selected day appears 7 Select the action number you would like to program or to modify using 8 Set the correct action...

Page 34: ...ogrammed actions of a specific day press once Result You can now select another day using and and restart consulting and programming To copy programmed actions to next day In space heating program it...

Page 35: ...ct are necessary within the warranty period contact your dealer and keep the warranty card at hand 13 2 2 Recommended maintenance and inspection Since dust collects when using the unit for several yea...

Page 36: ...e unit with manufacturing number if possible and the installation date possibly listed on the warranty card 14 1 Error codes Overview In case a malfunction code appears on the indoor unit user interfa...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P489435 1B 2017 10 Copyright 2017 Daikin 4P489435 1 B 00000004...

Reviews: