6 Configuration

Installation and operation manual

19

EWAQ016~ EWYQ016~064CAW
Packaged air-cooled water chiller
4P489435-1B – 2017.10

It  is  advised  to  use  the  weather  dependent  setpoint  because  it
adjusts the water temperature to the actual needs for space heating.
It will prevent the unit from switching too much between thermo ON
operation  and  thermo  OFF  operation  when  using  the  remote
controller room thermostat or external room thermostat.

Lo_Ti

Lo_A

Hi_A

T

A

T

t

+ 05

00

– 05

Hi_Ti

Shift value

T

t

Target water temperature

T

A

Ambient (outdoor) temperature

Shift value

Shift value

[3‑00] Low ambient temperature (Lo_A)

Low outdoor temperature.

[3‑01] High ambient temperature (Hi_A)

High outdoor temperature.

[3‑02] Setpoint at low ambient temperature (Lo_Ti)

The  target  outgoing  water  temperature  when  the  outdoor
temperature  equals  or  drops  below  the  low  ambient  temperature
(Lo_A).

Lo_Ti  should  be  higher  than  Hi_Ti,  as  warmer  water  is  required  for
colder outdoor temperatures.

[3‑03] Setpoint at high ambient temperature (Hi_Ti)

The  target  outgoing  water  temperature  when  the  outdoor
temperature  equals  or  rises  above  the  high  ambient  temperature
(Hi_A).

Hi_Ti  should  be  lower  than  Lo_Ti,  as  less  warm  water  suffices  for
warmer outdoor temperatures.

INFORMATION

If the value of [3‑03] is mistakenly set higher than the value
of [3‑02], the value of [3‑03] will always be used.

[4] Settings are not applicable

[5] Automatic setback

[5-00]

This setting is not applicable.

[5-01]

This setting is not applicable.

[5‑02] Leaving water setback temperature

[5‑03] Room setback temperature

[5-04]

This setting is not applicable.

[6] Option setup

[6‑01] External room thermostat option

If  an  optional  external  room  thermostat  is  installed,  its  operation
must be enabled by this field setting.

The  external  room  thermostat  only  gives  an  ON/OFF  signal  to  the
heat pump based on the room temperature. Because it does not give
continuous  feedback  information  to  the  heat  pump,  it  is
supplementary to the remote controller room thermostat function. To
have a good control of the system and avoid frequent ON/OFF it is
advised to use the automatic weather dependent setpoint operation.

[6‑01]

Description

0 (default)

External room thermostat not installed.

1

External room thermostat input 1 = heating
operation ON (1)/OFF (0).

External room thermostat input 2 = cooling
operation ON (1)/OFF (0).

2

External room thermostat input 1 = operation
ON (1)/OFF (0).

External room thermostat input 2 = cooling (1)/
heating (0).

[7] Option setup

[7‑00] Forced pump operation

[7‑00]

Description

0

The pump performs intermittent sampling
during thermo off conditions. This setting is
often used when the unit is controlled by a
room thermostat.

1 (default)

The pump continues operation during thermo
off conditions.

[8] Option setup

[8‑00] Remote controller temperature control

[8‑00]

Description

0 (default)

The unit operates in leaving water temperature
control.

1

The unit operates in room temperature control.
This means that the remote controller is used
as a room thermostat, so the remote controller
can be placed in the living room to control the
room temperature.

Note: 

  When  the  unit  is  operated  in  room  temperature  control  (by

remote  controller  or  external  room  thermostat  option),  room
temperature has priority over leaving water setpoint.

[8-01]

This setting is not applicable.

[8-03]

This setting is not applicable.

[8‑04] Freeze-up prevention

Freeze-up  prevention  will  be  activated  by  starting  up  the  pump  to
circulate the water, and if the leaving or return water temperature is
<5°C for 5 minutes, the unit will start up in heating mode to prevent
too low temperatures.

The  freeze-up  prevention  is  only  active  when  the  unit  is  in  thermo
OFF condition.

The option can be enabled when there is no optional heater tape or
glycol in the system and when heat can be used from an application.

[8‑04]

Description

0 (default)

No freeze-up prevention

1

Freeze-up prevention level 1 (outdoor
temperature <4°C and leaving or return water
temperature <7°C)

2

Freeze-up prevention level 2 (outdoor
temperature <4°C)

[9] Automatic temperature compensation

If necessary, it is possible to adjust some thermistor value of the unit
by  a  correction  value.  This  can  be  used  as  countermeasure  for
thermistor tolerances or capacity shortage.

Summary of Contents for EWAQ016CAW

Page 1: ...oled water chiller English Installation and operation manual Packaged air cooled water chiller EWAQ016CAW EWAQ021CAW EWAQ025CAW EWAQ032CAW EWAQ040CAW EWAQ050CAW EWAQ064CAW EWYQ016CAW EWYQ021CAW EWYQ02...

Page 2: ...os t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymai...

Page 3: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 4: ...omponents 14 6 2 3 To access the field setting components 14 6 2 4 To access mode 1 or 2 14 6 2 5 To use mode 1 14 6 2 6 To use mode 2 15 6 2 7 Mode 1 Monitoring settings 15 6 2 8 Mode 2 Field setting...

Page 5: ...This installation manual concerns the packaged air cooled water chiller The unit is intended for outdoor installation and can be combined with fan coil units for air conditioning purposes or it can be...

Page 6: ...ystem in order to allow complete drainage of the water circuit Non brass metallic piping When using non brass metallic piping insulate the brass and non brass properly so that they do NOT make contact...

Page 7: ...tions must be avoided a larger minimum water volume will be required To ensure proper operation of the unit when changing the values of setting F 00 for cooling mode the minimum water volume has to be...

Page 8: ...chrader valve of the expansion vessel a a Schrader valve 4 2 5 To check the water volume Examples Example 1 The unit is installed 5 m below the highest point in the water circuit The total water volum...

Page 9: ...2 1 To provide the installation structure Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise NOTICE When the installation height of the unit needs to be...

Page 10: ...em field supply 5 3 2 To fill the water circuit 1 Connect the water supply to the drain and fill valve 2 Make sure the automatic air purge valve is open at least 2 turns 3 Fill with water until the pr...

Page 11: ...presence may lead to the precipitation of certain components in the glycol s corrosion inhibitor NOTICE Glycol absorbs water from its environment Therefore do NOT add glycol that has been exposed to a...

Page 12: ...set up use and maintain the unit Before operating the remote controller follow this installation procedure Wire specification Value Type 2 wire Section 0 75 1 25 mm2 Wire specification Value Maximum l...

Page 13: ...ation in this chapter is read sequentially by the installer and that the system is configured as applicable DANGER RISK OF ELECTROCUTION 6 2 Making field settings 6 2 1 About making field settings INF...

Page 14: ...lated stick such as a closed ball point pen to avoid touching of live parts Make sure to re attach the inspection cover into the electrical component box cover after the job is finished NOTICE Make su...

Page 15: ...e 2 There are two methods to activate low noise operation of the compressor unit and heat exchanger unit The first method is to enable an automatic low noise operation during night time by field setti...

Page 16: ...ach field setting is assigned a 3 digit number or code e g 5 03 which is indicated on the remote controller display The first digit 5 is the first code or field setting group The second and third digi...

Page 17: ...stop when active at that moment and will start again at the next scheduled ON function The last programmed command overrules the preceding programmed command and will remain active until the next pro...

Page 18: ...ng the night because temperature demands during night and day are not the same INFORMATION The setback function is enabled by default The setback function can be combined with the automatic weather de...

Page 19: ...ave a good control of the system and avoid frequent ON OFF it is advised to use the automatic weather dependent setpoint operation 6 01 Description 0 default External room thermostat not installed 1 E...

Page 20: ...e the fluid to freeze b Settings are not applicable C Leaving water temperature limits This setting is used to limit the selectable leaving water temperature on the remote controller C 00 Maximum leav...

Page 21: ...e powered up You read the complete installation and operation instructions as described in the installer and user reference guide Installation Check that the unit is properly installed to avoid abnorm...

Page 22: ...first running period of the unit the required power may be higher than stated on the nameplate of the unit This phenomenon is caused by the compressor that needs a continuous run time of 48 hours bef...

Page 23: ...b A B C D Possibility 1 Possibility 2 a 300 mm b 100 mm c 500 mm d 500 mm a 500 mm b 500 mm c 500 mm d 500 mm h1 h2 1500 500 F mm ABCD Sides along the installation site with obstacles F Front side Suc...

Page 24: ...Q N h g k g D E a Air purge valve b Temperature sensors R11T R12T R13T R14T c Expansion vessel 12 l d Shut off valve field installed e Water inlet connection f Water outlet connection g Drain port h W...

Page 25: ...or current limiting R1T Thermistor air fin R2T R15T Thermistor H E gas 1 H E de icer 1 sub cool H E gas 1 sub cool H E liquid H E liquid 1 suction 1 liquid 1 suction 2 H E gas 2 H E de icer 2 sub cool...

Page 26: ...stem A full overview of allowable combinations for future system extensions is available in technical engineering data and should be consulted Contact your installer to receive more information and pr...

Page 27: ...or a function is not available An unavailable function can mean insufficient permission level or can mean that a slave remote controller is used see 6 2 9 Field settings on the remote controller on pa...

Page 28: ...stem 12 3 1 About the clock INFORMATION The clock must be set manually Adjust the setting when switching from summertime to wintertime and vice versa The clock cannot be adjusted if the controller is...

Page 29: ...d settings on the remote controller on page 16 INFORMATION Temperature range for cooling 5 C 20 C leaving water temperature 10 C 20 C when glycol is used For setup of the schedule timer function see T...

Page 30: ...point operation 6 Set the leaving water temperature using and INFORMATION During this operation instead of showing the water temperature setpoint the controller shows the shift value which can be set...

Page 31: ...d 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting you should consult the last programmed command this may date from the day before Th...

Page 32: ...ture setpoint is enabled by default so only temperature shifts are possible no ON OFF instruction Quiet mode See To program quiet mode on page 33 Switch the mode on or off at a scheduled time Four act...

Page 33: ...seconds to program the detailed actions Result The first programmed action of the selected day appears 7 Select the action number you would like to program or to modify using 8 Set the correct action...

Page 34: ...ogrammed actions of a specific day press once Result You can now select another day using and and restart consulting and programming To copy programmed actions to next day In space heating program it...

Page 35: ...ct are necessary within the warranty period contact your dealer and keep the warranty card at hand 13 2 2 Recommended maintenance and inspection Since dust collects when using the unit for several yea...

Page 36: ...e unit with manufacturing number if possible and the installation date possibly listed on the warranty card 14 1 Error codes Overview In case a malfunction code appears on the indoor unit user interfa...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P489435 1B 2017 10 Copyright 2017 Daikin 4P489435 1 B 00000004...

Reviews: