background image

6 Commissioning

Installation manual

17

EWAQ+008BAVP
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P478610-1 – 2017.02

6

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

6.1

Checklist before commissioning

Do  NOT  operate  the  system  before  the  following  checks  are  OK.
Depending  on  the  system  layout,  not  all  components  may  be
available.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

outdoor unit

 is properly mounted.

The 

control box

 is properly mounted.

The 

option box

 is properly mounted.

Only if you use the optional backup heater:

The 

backup heater

 is properly mounted.

The following 

field wiring

 has been carried out according

to  the  available  documentation  and  the  applicable
legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between the outdoor unit and the control box

▪ Between the control box and the option box

▪ Between the control box and the backup heater

▪ Between the local supply panel and the control box

▪ Between the local supply panel and the option box

▪ Between the outdoor unit and the valves

▪ Between the control box and the room thermostat

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed  according  to  this  document,  and  have  not  been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the outdoor unit.

Only if you use the optional backup heater:

Depending  on  the  backup  heater  type, 

backup  heater

circuit  breaker

  F1B  (on  the  switch  box  of  the  backup

heater) is turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There are no 

water leaks

 inside the outdoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

pressure relief valve

 purges water when opened.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions.  See  "To  check  the  water  volume"  in

"3.2 Preparing water piping" on page 5

.

If 

glycol

  was  added  to  the  system,  confirm  the  correct

glycol concentration, and check if glycol setting [E‑0D]=1.

NOTICE

▪ Make  sure  glycol  setting  [E-0D]  matches  the  liquid

inside the water circuit (0=water only, 1=water+glycol).
If  the  glycol  setting  is  NOT  set  correctly,  the  liquid
inside the piping can freeze.

▪ When  glycol  is  added  to  the  system,  but  the  glycol

concentration is lower than prescribed, the liquid inside
the piping can still freeze.

INFORMATION

The  software  is  equipped  with  an  "installer-on-site"  mode
([4‑0E]),  that  disables  automatic  operation  by  the  unit.  At
first  installation,  setting  [4‑0E]  is  by  default  set  to  "1",
meaning  automatic  operation  is  disabled.  All  protective
functions  are  then  disabled.  If  the  user  interface  home
pages  are  off,  the  unit  will  NOT  operate  automatically.  To
enable  automatic  operation  and  the  protective  functions,
set [4‑0E] to "0".

36 hours after the first power-on, the unit will automatically
set  [4‑0E]  to  "0",  ending  "installer-on-site"  mode  and
enabling  the  protective  functions.  If  –  after  first
installation  –  the  installer  returns  to  the  site,  the  installer
has to set [4‑0E] to "1" manually.

6.2

Checklist during commissioning

The 

minimum  flow  rate

  is  guaranteed  in  all  conditions.

See  "To  check  the  water  volume  and  flow  rate"  in

"3.2 Preparing water piping" on page 5

.

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

6.2.1

To perform an air purge

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page and room temperature home page are turned OFF.

1

Go  to  [A.7.3]: 

  >  Installer  settings  >  Commissioning  >  Air

purge.

2

Set the type.

3

Select Start air purge and press 

.

4

Select OK and press 

.

NOTICE

The  outdoor  unit  is  equipped  with  a  manual  air  purge
valve. The air purge procedure requires manual action.

NOTICE

When  purging  air  with  the  manual  air  purge  valve  of  the
unit, collect any fluid that might leak out of the valve. If this
fluid is NOT collected, it might drip on internal components
and damage the unit.

Summary of Contents for EWAQ006BAVP

Page 1: ...Packaged air cooled water chillers and packaged air to water heat pumps English Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAQ006BAVP EWAQ008BAVP EWYQ...

Page 2: ...C 100 250 100 A B C E 150 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a...

Page 3: ...valt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sek...

Page 4: ...ut 18 7 Hand over to the user 18 7 1 About locking and unlocking 19 To activate or deactivate a function lock 19 To activate or deactivate button lock 19 8 Technical data 20 8 1 Piping diagram Outdoor...

Page 5: ...ivered with the outdoor unit 3 Preparation 3 1 Preparing installation site 3 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See figure 1 on the inside of the front...

Page 6: ...electrical connections for external and internal actuators Item Description Wires Maximum running current Outdoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Normal kWh rate power supp...

Page 7: ...properly When the unit is in cooling mode condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold cli...

Page 8: ...peratures are expected add glycol to the water circuit The required concentration depends on the lowest expected outdoor temperature and on whether you want to protect the system from bursting or from...

Page 9: ...me of the system For more information refer to the chapter To check the water volume and flow rate in the installer reference guide 4 3 3 To fill the water circuit 1 Connect the water supply hose to t...

Page 10: ...that the cable does NOT come in contact with sharp edges 5 Install the switch box cover INFORMATION When installing field supply or option cables foresee sufficient cable length This will make it poss...

Page 11: ...b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 4 4 4 T...

Page 12: ...more than 4 seconds Result is displayed on the home pages 4 If you do NOT press any button for more than 1 hour or press again for more than 4 seconds the installer permission level switches back to E...

Page 13: ...Description A 2 2 E 1 E 03 Backup heater steps 0 default 1 2 Code Description A 2 2 E 2 5 0D BUH type 1 1P 1 1 2 6 kW 1 230 V default 4 3PN 1 2 6 kW 3N 400 V 9W 5 3PN 1 1 2 9 kW 3N 400 V 9W The syste...

Page 14: ...d Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for leaving water temperature control 3 WD scheduled Weather dependent scheduled only for leaving water temperature...

Page 15: ...eaving water setpoint By setting the weather dependent curve to a higher position it cannot drop below the minimum setpoint Refer to the illustration below a 8 06 8 06 b Ta Tt a Weather dependent curv...

Page 16: ...pe Indoor software type Unit control method Pump operation mode Power saving possible User interface location Options External sensor Control box Option box Leaving water Main Delta T source Room ther...

Page 17: ...pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 5 If glycol was added to th...

Page 18: ...ettings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually p...

Page 19: ...er to be able to change setpoint temperatures the simplified user interface or an external room thermostat is then required You can use the following locking modes Function lock Locks a specific funct...

Page 20: ...heat exchanger 9 Safety valve 10 Water filter 11 Expansion vessel 12 R1T Outlet water heat exchanger thermistor 13 R3T Refrigerant liquid side thermistor 14 R4T Inlet water thermistor 15 Gas stop val...

Page 21: ...1P Signal transmission circuit V1D V3D A1P Diode V1R A1P IGBT power module V2R A1P Diode module V1T V2T A1P Insulated gate bipolar transistor IGBT X1M Terminal strip Y1E Electronic expansion valve Y1S...

Page 22: ...power circuit A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat K1A Relay for heating K2A Relay for cooling M2S Shut OFF valve M4S Valve kit English...

Page 23: ...eter inputs 5 V DC pulse detection voltage supplied by PCB Electric pulse meter inputs 5 V DC pulse detection voltage supplied by PCB 2 Legend 2 Legend A4P Extension PCB control optional R6T External...

Page 24: ...for KRUCB A5P P1 P2 user interface A5P P1 P2 user interface Power supply 3 core control box power supply 230 V earth signal signal signal 2 or 3 core 2 core 2 core F1B L1 L2 L3 N earth or L N earth b...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4P478610 1 2017 02 Copyright 2017 Daikin...

Reviews: