background image

5 Configuration

Installation manual

15

EWAQ+008BAVP
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P478610-1 – 2017.02

#

Code

Description

N/A

[8-06]

Leaving water temperature maximum
modulation:

0°C~10°C (default: 3°C)

Requires modulation to be enabled.

This is the value by which the desired
leaving water temperature is increased
or lowered.

INFORMATION

When  leaving  water  temperature  modulation  is  enabled,
the  weather‑dependent  curve  needs  to  be  set  to  a  higher
position  than  [8-06]  plus  the  minimum  leaving  water
temperature  setpoint  required  to  reach  a  stable  condition
on  the  comfort  setpoint  for  the  room.  To  increase
efficiency, modulation can lower the leaving water setpoint.
By  setting  the  weather‑dependent  curve  to  a  higher
position, it cannot drop below the minimum setpoint. Refer
to the illustration below.

a

+[8-06]

−[8-06]

b

Ta

Tt

a

Weather-dependent curve

b

Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.

Leaving water temperature: Emitter type

#

Code

Description

[A.3.1.1.7]

[9-0B]

Reaction time of the system:

▪ 0:  Quick. 

Example: 

Small  water

volume and fan coils.

▪ 1:  Slow. 

Example: 

Large  water

volume, floor heating loops.

Depending on the system water volume
and the heat emitters type, the heat up
or cool down of a space can take
longer. This setting can compensate for
a slow or a quick heating/cooling
system by adjusting the unit capacity
during the heat up/cool down cycle.

5.2.6

Contact/helpdesk number

#

Code

Description

[6.3.2]

N/A

Number that users can call in case of
problems.

Summary of Contents for EWAQ006BAVP

Page 1: ...Packaged air cooled water chillers and packaged air to water heat pumps English Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAQ006BAVP EWAQ008BAVP EWYQ...

Page 2: ...C 100 250 100 A B C E 150 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a...

Page 3: ...valt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sek...

Page 4: ...ut 18 7 Hand over to the user 18 7 1 About locking and unlocking 19 To activate or deactivate a function lock 19 To activate or deactivate button lock 19 8 Technical data 20 8 1 Piping diagram Outdoor...

Page 5: ...ivered with the outdoor unit 3 Preparation 3 1 Preparing installation site 3 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See figure 1 on the inside of the front...

Page 6: ...electrical connections for external and internal actuators Item Description Wires Maximum running current Outdoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Normal kWh rate power supp...

Page 7: ...properly When the unit is in cooling mode condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold cli...

Page 8: ...peratures are expected add glycol to the water circuit The required concentration depends on the lowest expected outdoor temperature and on whether you want to protect the system from bursting or from...

Page 9: ...me of the system For more information refer to the chapter To check the water volume and flow rate in the installer reference guide 4 3 3 To fill the water circuit 1 Connect the water supply hose to t...

Page 10: ...that the cable does NOT come in contact with sharp edges 5 Install the switch box cover INFORMATION When installing field supply or option cables foresee sufficient cable length This will make it poss...

Page 11: ...b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 4 4 4 T...

Page 12: ...more than 4 seconds Result is displayed on the home pages 4 If you do NOT press any button for more than 1 hour or press again for more than 4 seconds the installer permission level switches back to E...

Page 13: ...Description A 2 2 E 1 E 03 Backup heater steps 0 default 1 2 Code Description A 2 2 E 2 5 0D BUH type 1 1P 1 1 2 6 kW 1 230 V default 4 3PN 1 2 6 kW 3N 400 V 9W 5 3PN 1 1 2 9 kW 3N 400 V 9W The syste...

Page 14: ...d Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for leaving water temperature control 3 WD scheduled Weather dependent scheduled only for leaving water temperature...

Page 15: ...eaving water setpoint By setting the weather dependent curve to a higher position it cannot drop below the minimum setpoint Refer to the illustration below a 8 06 8 06 b Ta Tt a Weather dependent curv...

Page 16: ...pe Indoor software type Unit control method Pump operation mode Power saving possible User interface location Options External sensor Control box Option box Leaving water Main Delta T source Room ther...

Page 17: ...pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 5 If glycol was added to th...

Page 18: ...ettings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually p...

Page 19: ...er to be able to change setpoint temperatures the simplified user interface or an external room thermostat is then required You can use the following locking modes Function lock Locks a specific funct...

Page 20: ...heat exchanger 9 Safety valve 10 Water filter 11 Expansion vessel 12 R1T Outlet water heat exchanger thermistor 13 R3T Refrigerant liquid side thermistor 14 R4T Inlet water thermistor 15 Gas stop val...

Page 21: ...1P Signal transmission circuit V1D V3D A1P Diode V1R A1P IGBT power module V2R A1P Diode module V1T V2T A1P Insulated gate bipolar transistor IGBT X1M Terminal strip Y1E Electronic expansion valve Y1S...

Page 22: ...power circuit A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat K1A Relay for heating K2A Relay for cooling M2S Shut OFF valve M4S Valve kit English...

Page 23: ...eter inputs 5 V DC pulse detection voltage supplied by PCB Electric pulse meter inputs 5 V DC pulse detection voltage supplied by PCB 2 Legend 2 Legend A4P Extension PCB control optional R6T External...

Page 24: ...for KRUCB A5P P1 P2 user interface A5P P1 P2 user interface Power supply 3 core control box power supply 230 V earth signal signal signal 2 or 3 core 2 core 2 core F1B L1 L2 L3 N earth or L N earth b...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4P478610 1 2017 02 Copyright 2017 Daikin...

Reviews: