11/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[7-08]
Activation of keep-hot-function
R/W
0: Disabled (*3)
1: Enabled (*4)
9.I
[7-09]
R/W
20~95%, step: 5%
20%
9.I
[7-0A]
R/W
20~95%, step: 5%
95%
9.I
[7-0B]
R/W
20~95%, step: 5%
95%
9.I
[7-0C]
R/W
20~300 seconds, step: 5 sec
125 seconds
9.I
[8-00]
R/W
0~20 min, step: 1 min
1 min
9.I
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.I
[8-02]
R/W
0~10 hour, step: 0,5 hour
[E-07]=1:
0,5 hour
[E-07]
≠
1:
3 hour
9.I
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.I
[8-04]
R/W
0~95 min, step: 5 min
95 min
9.I
[8-05]
R/W
0: No
1: Yes
9.I
[8-06]
R/W
0~10°C, step: 1°C
5°C
9.I
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
9.I
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
9.I
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.I
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
9.I
[8-0B]
13
9.I
[8-0C]
10
9.I
[8-0D]
16
9.I
[9-00]
R/W
37~65, step: 1°C
[2-0C]=2:
65°C
[2-0C]
≠
2:
55°C
9.I
[9-01]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-02]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-03]
R/W
5~18°C, step: 1°C
7°C
9.I
[9-04]
R/W
1~4°C, step: 1°C
2°C
9.I
[9-05]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-06]
R/W
37~65, step: 1°C
[2-0C]=2:
65°C
[2-0C]
≠
2:
55°C
9.I
[9-07]
R/W
5~18°C, step: 1°C
7°C
9.I
[9-08]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-09]
R/W
1~18°C, step: 1°C
18°C
9.I
[9-0A]
R/W
[3-07]~[3-06]°C, step: 0,5°C
23°C
9.I
[9-0B]
R/W
[3-09]~[3-08]°C, step: 0,5°C
23°C
9.I
[9-0C]
R/W
1~6°C, step: 0,5°C
1°C
9.I
[9-0D]
R/W
0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6
9.I
[9-0E]
6
9.I
[C-00]
R/W
0: Solar priority
1: Heat pump priority
9.I
[C-01]
0
9.I
[C-02]
R/W
0: No
1: Yes
9.I
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.I
[C-04]
R/W
2~10°C, step: 1°C
3°C
9.I
[C-05]
R/W
1: 1 contact
2: 2 contacts
9.I
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
9.I
[C-07]
R/W
0: Leaving water
1: External room thermostat
2: Room thermostat
Additional zone fixed pump PWM, in case a bizone kit is installed.
Main zone fixed pump PWM, in case a bizone kit is installed.
Time needed by the mixing valve to turn from one side to the other, in case a
bizone kit is installed.
What is the desired comfort main LWT in cooling?
What is the desired eco main LWT in cooling?
What is the desired comfort main LWT in heating?
Minimum running time for domestic hot water operation.
What is the minimum pump speed during space and domestic hot water
operation?
What is the allowed LWT undershoot during cooling start-up?
What is the desired eco main LWT in heating?
--
--
Maximum running time for domestic hot water operation.
What is the mimimum desired LWT for add. zone in heating?
Bivalent hysteresis temperature.
Anti-recycling time.
Booster heater delay timer.
Additional running time for the maximum running time.
Allow modulation of the LWT to control the room temp?
Leaving water temperature maximum modulation.
--
What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
What is the maximum desired LWT for main zone in cooling?
What is the maximum desired LWT for add. zone in heating?
What is the mimimum desired LWT for add. zone in cooling?
What is the maximum desired LWT for add. zone in cooling?
Room temperature hysteresis.
Pump speed limitation
What is the room buffering temperature in heating?
What is the room buffering temperature in cooling?
What is the mimimum desired LWT for main zone in cooling?
Leaving water temperature overshoot temperature.
--
Domestic heating water priority.
--
Is an external backup heat source connected?
Bivalent activation temperature.
What is the thermo request contact type for the main zone?
What is the unit control method in space operation?
What is the thermo request contact type for the add. zone?
(*1)
*6V*_(*2)
*9W*_
(*3)
ELB*_(*4)
ELV*_
(*5)
*X*_(*6)
*H*
4P717809
‐
1
–