11
|
Configuration
Installer reference guide
204
ERRA08~12E + ELVH/23E
Daikin Altherma 3 R MT F
4P708474-1 – 2023.05
▪
While the unit is in operation, the status indicator will light up blue constantly.
To set the space operation mode
1
Go to [4.1]:
Space heating/cooling
>
Operation mode
2
Select one of the following options:
▪
Heating
: Only heating mode
▪
Cooling
: Only cooling mode
▪
Automatic
: The operation mode changes automatically
between heating and cooling based on the outdoor
temperature. Restricted per month according to the
Operation mode schedule
[4.2].
When
Automatic
is selected, the unit switches its operation mode, based on the
Operation mode schedule
[4.2]. In this schedule, the end user indicates which
operation is allowed for each month.
To restrict automatic changeover according to a schedule
Conditions:
You set the space operation mode to
Automatic
.
1
Go to [4.2]:
Space heating/cooling
>
Operation mode
schedule
.
2
Select a month.
3
For each month, select an option:
▪
Reversible
: Not restricted
▪
Heating only
: Restricted
▪
Cooling only
: Restricted
4
Confirm the changes.
Example: Changeover restrictions
When
Restriction
During cold season.
Example:
October, November, December, January,
February and March.
Heating only
During warm season.
Example:
June, July and August.
Cooling only
In-between.
Example:
April, May and September.
Reversible
The unit determines its operation mode by the outdoor temperature if:
▪
Operation mode
=
Automatic
, and
▪
Operation mode schedule
=
Reversible
.
The unit determines its operation mode in such a way that it will always stay within
the following operation ranges:
▪
Space heating off temperature
▪
Space cooling off temperature
The outdoor temperature is time-averaged. If the outdoor temperature drops, the
operation mode will switch to heating and vice versa.