11
|
Configuration
Installer reference guide
222
ERRA08~12E + ELVH/23E
Daikin Altherma 3 R MT F
4P708474-1 – 2023.05
If you want to…
Then…
Completely deactivate quiet
mode
Select
Off
.
Result:
The unit never runs in quiet
mode. The user cannot change this.
Manually activate a quiet
mode level
Select
Manual
.
Go to [7.4.3]
Level
and select the
applicable quiet mode level.
Example:
Most quiet
.
Result:
The unit always runs in the
selected quiet mode level. The user
cannot change this.
▪
Enable the user to program a
quiet mode schedule, AND/
OR
▪
Configure restrictions based
on local regulations
Select
Automatic
.
Result:
▪
The user (or you) can program the
schedule in [7.4.2]
Schedule
. For
more
information
about
scheduling, see
▪
You can configure restrictions in
[7.4.4]
Restrictions
.
See
below.
▪
The possible outcomes for the
quiet mode differ depending on
the schedule (if programmed) and
the restrictions (if enabled/
defined). See below.
To configure restrictions
1
Enable the restrictions.
Go to [7.4.4.1]:
User settings
>
Quiet
>
Restrictions
>
Enable
and select
Yes
.
2
Define the restrictions (time + level) to be used before midday
(AM):
▪
[7.4.4.2]
AM Restricted time
Example:
From 9 a.m. to 11 a.m.
▪
[7.4.4.3]
AM Restricted level
Example:
More quiet
3
Define the restrictions (time + level) to be used after midday
(PM):
▪
[7.4.4.4]
PM Restricted time
Example:
From 3 p.m. to 7 p.m.
▪
[7.4.4.5]
PM Restricted level
Example:
Most quiet