background image

ERAP110~170MBYNN

Air-cooled condensing units

4PW22681-1

Operation manual

10

Defining and activating the control mode

The unit is equipped with a thermostat which controls the capacity of
the unit.

Two different control modes exist:

Manual control mode: the operator controls the capacity
himself - 

 

0

 (air flow in manual mode): off, low, medium or high.

 (capacity step in manual mode): 0%, 30%~100%.

Thermostat mode: uses the thermostat control to control the
capacity of the unit - 

 

Defining the thermostat settings

When automatic control mode is selected, the unit uses a thermostat
function to control the cooling capacity. However, the thermostat
parameters are not fixed and can be modified via the 

 $

 

 screen of the user settings menu.

The default, limit and step values for the thermostat parameters are
shown in 

"Annex I" on page 15

.

Defining the capacity limitation settings

A capacity limitation can be activated:

 

:

   

  see 

"Defining the schedule timer" on

page 10

.

   

  when a changeable input is configured as

capacity limitation.

: to activate capacity limitation 1.

  

: the capacity limitation is not active.

2!  

:  capacity limitation value of circuit 1 in

case of capacity limitation 1/2/3/4.

Defining the flow control settings

The 

 screen of the user settings menu allows the user

to define the pump-leadtime and pump-lagtime.

  

:  used to define the time that the fan or pump-

motor must run before the unit starts.

 

:  used to define the time that the fan or

pumpmotor keeps running after the unit is stopped.

Defining the schedule timer

To  activate the screens of the schedule timer or holiday period, these
first need to be enabled by changing their setting to 

 in the appropriate

screen. To de-activate the schedule timer or holiday period, their setting
needs to be reset to 

(See 

"Usersettings menu" on page 8

.)

The 

   

 screen of the user settings menu allows the

user to define the schedule timer settings.

Each day of the week can be appointed to a group. The actions defined
in a group will be executed in each day belonging to that group.

 

 

 and 

: used to define to which

group each day of the week belongs (

/

/

/

2

/

!

).

For each of the four groups up to nine actions can be set, each
with their respective timing. Actions include: putting the unit on/
off and setting capacity limitation.

Beside these four groups there is also a holiday period group
which is set the same way as the other groups. Up to 12 holiday
periods can be entered in the 

 

 screen. During these

periods the schedule timer will follow the settings of the holiday
period group.

Defining dual evaporator fan/pump control

The 

  $

 screen of the user settings menu allows the

user to define the steering of 2 evaporator fans/pumps (for this to be
possible a changeable digital output has to be configured for a
second evaporator fan/pump in the service menu). Refer to the
installation manual.

 

:  used to define which kind of control will be used for the

two evaporator pumps. When automatic rotation is chosen the
offset on running hours also has to be entered.

: pump 1 and pump 2 will alternate to the offset on RH.

 

: pump 1 will always start up first.

 

: pump 2 will always start up first.

   

:  used to define the offset in running hours

between the two pumps. Used to switch over between pumps
when they work in automatic rotation mode.

Defining the floating setpoint settings

The 

 

 screen of the user settings menu allows

the active setpoint to be modified in function of the ambient. The
source and settings of the floating setpoint can be configured by the
user.

 

: used to define the mode of the floating setpoint.

   

: floating setpoint is not activated.

 

:  floating setpoint is altered based on the ambient

temperature.

.$  

: used to define maximum value that can be added

to the active setpoint.

:  used to define the ambient (source) at which the floating

setpoint value is equal to zero.

:  used to define the rise in floating setpoint value for 10°C

drop in ambient.

Defining the display settings

The 

 

  screens of the usersettings menu allows

the user to define the choice of language, time and date.

 

:  used to define the language of the displayed

information of the controller (on the first screen). (Push the 

q

button repeatedly to change the operating language).

 

: used to define the present time (on the second screen).

 

: used to define the present date (on the second screen).

NOTE

To  activate manual control mode, select 

  as

present mode. To deactivate the manual control mode,
select 

 

 

as present mode.

NOTE

If changed on one of the units in a DICN
configuration, this setting is transferred to all other
units in the network.

A functional diagram showing the thermostat
parameters can be found in 

"Annex I" on page 15

.

NOTE

Refer to "Customization in the service menu",
chapter "Setting of the changeable digital
inputs and outputs" in the installation manual 

NOTE

A functional diagram showing the schedule timer
working can be found in 

"Annex I" on page 15

.

NOTE

The unit always works with "last command". This means
that the last command given, whether manually by the
user or by the schedule timer, is always executed.

Examples of command that can be given are switching
the unit on/off or changing a setpoint.

NOTE

A functional diagram showing the floating setpoint
working can be found in 

"Annex III" on page 15

.

Summary of Contents for ERAP110MBYNN

Page 1: ...OPERATION MANUAL ERAP110MBYNN ERAP150MBYNN ERAP170MBYNN Air cooled condensing units...

Page 2: ...RAP150MBYNN ERAP170MBYNN Air cooled condensing units Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before st...

Page 3: ...r intake 1000 1000 1000 1000 1000 3000 2210 2346 13 10 11 7 6 16 2 3 9 5 14 15 8 12 4 1 1 Condenser 9 Power supply intake 2 Compressor M1C 10 Emergency stop S5E 3 Discharge stop valve 11 Switchbox 4 L...

Page 4: ...too low voltage The relays are factory set and may not be adjusted When activated they must be reset manually followed by a reset of the controller Compressor thermal protectors The compressor motors...

Page 5: ...al Q11F Q14F Thermal protectors fan motors Q1M Thermal protector compressor motor R1 Auxiliary resistance for feedback R1F Feedback resistance R1P Reverse phase protector R4T Sensor for thermostat R5T...

Page 6: ...the unit is ready for operation General recommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out cl...

Page 7: ...mote on off switch is configured Press the o key on the controller The LED inside the o key goes out If a remote on off switch is configured Press the o key on the controller or switch the unit off us...

Page 8: ...s refer to User password menu on page 9 Press q to confirm the password and to enter the setpoints menu 2 Select the setpoint to be adjusted using the q key A setpoint is selected when the cursor is b...

Page 9: ...control mode To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total running hours of...

Page 10: ...keys 2 Position the cursor behind the parameter to be modified using the q key 3 Select the appropriate setting using the g and h keys 4 Press q to confirm the selection When the selection has been c...

Page 11: ...group Defining dual evaporator fan pump control The screen of the user settings menu allows the user to define the steering of 2 evaporator fans pumps for this to be possible a changeable digital outp...

Page 12: ...timer has reached zero the pumplead timer and the pumplag timer 2 Press the h key to check the compressor timers The controller shows the actual value of the the guard timers one per circuit and the...

Page 13: ...the fan motor or the pump motor should be ON indicates the status of this voltage free contact It is activated if there is any alarm on the unit The changeable relay outputs are indicates the status...

Page 14: ...es is activated One of the following safety devices is activated Air or waterflow contact S9L Emergency stop Refer to Symptom 5 One of the following safety devices is activated The ON LED is broken Co...

Page 15: ...er supply are connected in the wrong phase position Invert two phases of the power supply by licensed electrician One phase is not connected properly Check the connection of all phases RESET After inv...

Page 16: ...l Saturdays and Sundays will work according to the settings in group 3 2 all holiday days will work according to the settings in the holiday group All group settings of groups 2 and work similar as fo...

Page 17: ...ion manual 16 ANNEX IV q q q g h h g h g h h g h g g h g g h g h g h h g g f 1 1 1 1 1 1 1 h g h g h h q 4 4 2 4 4 2 4 2 6 4 4 4 h g h g h g h 3 g g h g h g q q q q q q q q q q p 2 4 g g h g h 3 2 2 5...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22681 1...

Reviews: