background image

Operation manual

7

ERAP110~170MBYNN

Air-cooled condensing units

4PW22681-1

When a circuit is OFF, the following status information may
appear.

   

:  one of the circuit safety devices is activated

(refer to 

"Troubleshooting" on page 13

).

: the circuit is limited by a remote contact.

 

: the actual value of one of the software timers is

not zero (refer to 

"Timers menu" on page 8

).

 

 the circuit is ready to start up when extra cooling

load is needed.

The preceding OFF messages are written down in order of priority. If
one of the timers is busy and one of the safeties is active, the status
information says 

   

.

The 

 

  is written down on the bottom of the screen.

The percentage is the actual cooling capacity of the unit.

3

Press the 

h

 key to enter the next screen of the readout menu.

The 

   

 screen of the readout menu provides

information concerning the pressures of circuit.

:  high pressure of the refrigerant in circuit. The first

number stands for the pressure in bar, the second number
stands for the bubble point saturation temperature in degrees
Celsius.

:  low pressure of the refrigerant in circuit. The first

number stands for the pressure in bar, the second number
stands for the dew point saturation temperature in degrees
Celsius.

4

Press the 

h

 key to enter the next screen of the readout menu.

This menu is available if voltage and current transmitters are
installed. This readout menu provides information concerning
the voltage and the compressor current.

5

Press the 

h

 key to enter the next screen of the readout menu.

To  consult actual operational information about the ambient
temperature and the total running hours of the compressor.

6

Press the 

g

 key to return to the other readout menus.

Adjusting the temperature setpoint

The unit provides definition and selection of two independent
temperature setpoints.

 

: setpoint 1,

 

: setpoint 2.

The selection between setpoint 1 and 2 is done by a remote dual
setpoint switch (to be installed by the customer). The actual active
setpoint can be consulted in the readout menu.

If the manual control mode is selected (refer to 

"Usersettings menu"

on page 8

), none of the above-mentioned setpoints will be active.

To adjust a setpoint, proceed as follows:

1

Enter the setpoints menu. Refer to the chapter 

"How to enter a

menu" on page 6

.

If the user password is disabled for setpoint modifications (refer
to 

"Usersettings menu" on page 

8

), the controller will

immediately enter the setpoints menu.
If the user password is enabled for setpoint modifications, enter
the correct code using the 

and

  h 

keys (refer to 

"User

password menu" on page 9

). Press 

q

 to confirm the password

and to enter the setpoints menu.

2

Select the setpoint to be adjusted using the 

q

 key.

A setpoint is selected when the cursor is blinking behind the
setpoint's name.
The "

" sign indicates the actual active temperature setpoint.

3

Press the 

g

 and 

keys to adjust the temperature setting.

The default, limit and step values for the cooling temperature
setpoints are:

4

Press 

q

 to save the adjusted temperature setpoint.

When the setting has been confirmed, the cursor switches to the
next setpoint.

5

To adjust other setpoints, repeat from 

step 2

.

Resetting the unit

When a unit safety occurs, one compressor is shut down. The
safeties menu will indicate which safety is activated. The 

  screen of the readout menu will indicate 

   

 

.  The red LED inside the 

p

  key  lights up and the buzzer

inside the controller is activated.

If the unit has been shut down due to a power failure, it will carry out
an autoreset and restart automatically when the electrical power is
restored.

To reset the unit, proceed as follows:

1

Press the 

p

 key to acknowledge the alarm.

The buzzer is de-activated.
The controller automatically switches to the corresponding
screen of the safeties menu: unit safety or circuit safety or
network safety.

2

Find the cause of shutdown and correct.

Refer to 

"Listing activated safeties and checking the unit status"

on page 11

 and 

"Troubleshooting" on page 13

.

When a safety can be reset, the LED under the 

p

  key  starts

blinking.

3

Press the 

p

 key to reset the safeties that are no longer active.

If required, enter the 

 

  or the 

  

.  (Refer to the installation manual "Setting the

password for safety reset".)
Once all safety devices are de-activated and reset, the LED
under the 

p

 key goes out. If one of the safeties is still active, the

LED under the 

p

  key  goes on again. In this case, return to

step 2

.

NOTE

The customer is also allowed to define a setpoint in
function of an analog input.

NOTE

Refer to "Customization in the service menu" chapter
"Setting of the changeable inputs and outputs" in the
installation manual

 

default value

limit values

(a)

(a) The lower limit of the cooling temperature setpoint can be

adapted by changing the minimum operating temperature in
the service menu (refer to the installation manual). The
following values apply:

 

: 2°C, 0°C, –5°C, –10°C

!

 --> 

"

step value

#$

NOTE

Also consult 

"Defining the floating setpoint settings" on

page 10

.

If the user shuts down the power supply in order to repair a
safety, the safety will automatically be reset after power-up.

NOTE

The history information, i.e. the number of times a unit
safety or a circuit safety occurred and the unit status at
the moment of shutdown, can be checked by means of
the history menu.

Summary of Contents for ERAP110MBYNN

Page 1: ...OPERATION MANUAL ERAP110MBYNN ERAP150MBYNN ERAP170MBYNN Air cooled condensing units...

Page 2: ...RAP150MBYNN ERAP170MBYNN Air cooled condensing units Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before st...

Page 3: ...r intake 1000 1000 1000 1000 1000 3000 2210 2346 13 10 11 7 6 16 2 3 9 5 14 15 8 12 4 1 1 Condenser 9 Power supply intake 2 Compressor M1C 10 Emergency stop S5E 3 Discharge stop valve 11 Switchbox 4 L...

Page 4: ...too low voltage The relays are factory set and may not be adjusted When activated they must be reset manually followed by a reset of the controller Compressor thermal protectors The compressor motors...

Page 5: ...al Q11F Q14F Thermal protectors fan motors Q1M Thermal protector compressor motor R1 Auxiliary resistance for feedback R1F Feedback resistance R1P Reverse phase protector R4T Sensor for thermostat R5T...

Page 6: ...the unit is ready for operation General recommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out cl...

Page 7: ...mote on off switch is configured Press the o key on the controller The LED inside the o key goes out If a remote on off switch is configured Press the o key on the controller or switch the unit off us...

Page 8: ...s refer to User password menu on page 9 Press q to confirm the password and to enter the setpoints menu 2 Select the setpoint to be adjusted using the q key A setpoint is selected when the cursor is b...

Page 9: ...control mode To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total running hours of...

Page 10: ...keys 2 Position the cursor behind the parameter to be modified using the q key 3 Select the appropriate setting using the g and h keys 4 Press q to confirm the selection When the selection has been c...

Page 11: ...group Defining dual evaporator fan pump control The screen of the user settings menu allows the user to define the steering of 2 evaporator fans pumps for this to be possible a changeable digital outp...

Page 12: ...timer has reached zero the pumplead timer and the pumplag timer 2 Press the h key to check the compressor timers The controller shows the actual value of the the guard timers one per circuit and the...

Page 13: ...the fan motor or the pump motor should be ON indicates the status of this voltage free contact It is activated if there is any alarm on the unit The changeable relay outputs are indicates the status...

Page 14: ...es is activated One of the following safety devices is activated Air or waterflow contact S9L Emergency stop Refer to Symptom 5 One of the following safety devices is activated The ON LED is broken Co...

Page 15: ...er supply are connected in the wrong phase position Invert two phases of the power supply by licensed electrician One phase is not connected properly Check the connection of all phases RESET After inv...

Page 16: ...l Saturdays and Sundays will work according to the settings in group 3 2 all holiday days will work according to the settings in the holiday group All group settings of groups 2 and work similar as fo...

Page 17: ...ion manual 16 ANNEX IV q q q g h h g h g h h g h g g h g g h g h g h h g g f 1 1 1 1 1 1 1 h g h g h h q 4 4 2 4 4 2 4 2 6 4 4 4 h g h g h g h 3 g g h g h g q q q q q q q q q q p 2 4 g g h g h 3 2 2 5...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22681 1...

Reviews: