background image

Operation manual

5

ERAP110~170MBYNN

Air-cooled condensing units

4PW22681-1

4

Earth wiring

Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.

5

Internal wiring

Visually check the switch box on loose connections or damaged
electrical components.

6

Fixation

Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.

7

Damaged equipment

Check the inside of the unit on damaged components or
squeezed pipes.

8

Refrigerant leak

Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local dealer.

9

Oil leak

Check the compressor on oil leakage. If there is an oil leak, call
your local dealer.

10

Stop valves

Open the liquid line, discharge and suction (if provided) stop
valves completely.

11

Air inlet/outlet

Check that the air inlet and outlet of the unit is not obstructed by
paper sheets, cardboard, or any other material.

12

Power supply voltage

Check the power supply voltage on the local supply panel. The
voltage must correspond to the voltage on the identification label
of the unit.

Power supply connection and crankcase heating

To switch on the crankcase heater proceed as follows:

1

Switch on the circuit breaker on the local supply panel. Make
sure that the unit is "OFF".

2

The crankcase heater is switched on automatically.

3

Check the supply voltage on the supply terminals L1, L2, L3, by
means of a voltmeter. The voltage must correspond to the
voltage indicated on the identification label of the unit. If the
voltmeter reads values which are not within the ranges specified
in the technical data, check the field wiring and replace the
supply cables if necessary.

4

Check the LED on the reverse phase protectors. If it lights up,
the phase order is correct. If not, switch off the circuit breaker
and call a licensed electrician to connect the wires of the power
supply cable in the correct phase order.

5

Check if the crankcase heaters are warming up.

After 8 hours, the unit is ready for operation.

General recommendations

Before switching on the unit, read following recommendations:

1

When the complete installation and all necessary settings have
been carried out, close all front panels of the unit.

2

The service panels of the switch boxes may only be opened by a
licensed electrician for maintenance purposes.

3

To  avoid damage to the LCD display of the digital controller,
never switch off the power supply during winter.

O

PERATION

The ERAP units are equipped with a digital controller offering a user-
friendly way to set up, use and maintain the unit.

This part of the manual has a task-oriented, modular structure. Apart
from the first section, which gives a brief description of the controller
itself, each section or subsection deals with a specific task you can
perform with the unit.

Digital controller

User interface

The digital controller consists of an alphanumeric display, labelled
keys which you can press and a number of LEDs.

Digital built-in controller

Figure - Digital built-in controller

Digital remote controller (to be ordered separately)

Figure - Digital remote controller

In order to avoid compressor damage, it is necessary to
switch on the crankcase heater for at least 8 hours before
starting the compressor after a long period of standstill.

f

key, to enter the main menu

o

key, to start up or to shut down the unit.

p

key, to enter the safeties menu or to reset an alarm.

g
h

keys, to scroll up or down through the screens of a menu
(only in case 

W

X

 or 

C

 appears) or to raise, respectively

lower a setting.

q

key, to confirm a selection or a setting.

o

key, to start up or to shut down the unit.

p

key, to enter the safeties menu or to reset an alarm.

k

key, to scroll through the screens of a menu (only in case

W

X

  or 

C

  appears) or to raise, respectively lower a

setting.

q

key, to confirm a selection or a setting.

u

key, to enter the readout menu.

s

key, to enter the setpoint menu.

z

key, to enter the user settings menu.

e

key, to enter the timers menu.

r

key, to enter the history menu.

t

key, to enter the info menu.

y

key, to enter the input/output status menu.

a

key, to enter the user password menu.

d

key, has no effect on ERAP units.

i

key, has no effect on ERAP units.

Summary of Contents for ERAP110MBYNN

Page 1: ...OPERATION MANUAL ERAP110MBYNN ERAP150MBYNN ERAP170MBYNN Air cooled condensing units...

Page 2: ...RAP150MBYNN ERAP170MBYNN Air cooled condensing units Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before st...

Page 3: ...r intake 1000 1000 1000 1000 1000 3000 2210 2346 13 10 11 7 6 16 2 3 9 5 14 15 8 12 4 1 1 Condenser 9 Power supply intake 2 Compressor M1C 10 Emergency stop S5E 3 Discharge stop valve 11 Switchbox 4 L...

Page 4: ...too low voltage The relays are factory set and may not be adjusted When activated they must be reset manually followed by a reset of the controller Compressor thermal protectors The compressor motors...

Page 5: ...al Q11F Q14F Thermal protectors fan motors Q1M Thermal protector compressor motor R1 Auxiliary resistance for feedback R1F Feedback resistance R1P Reverse phase protector R4T Sensor for thermostat R5T...

Page 6: ...the unit is ready for operation General recommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out cl...

Page 7: ...mote on off switch is configured Press the o key on the controller The LED inside the o key goes out If a remote on off switch is configured Press the o key on the controller or switch the unit off us...

Page 8: ...s refer to User password menu on page 9 Press q to confirm the password and to enter the setpoints menu 2 Select the setpoint to be adjusted using the q key A setpoint is selected when the cursor is b...

Page 9: ...control mode To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total running hours of...

Page 10: ...keys 2 Position the cursor behind the parameter to be modified using the q key 3 Select the appropriate setting using the g and h keys 4 Press q to confirm the selection When the selection has been c...

Page 11: ...group Defining dual evaporator fan pump control The screen of the user settings menu allows the user to define the steering of 2 evaporator fans pumps for this to be possible a changeable digital outp...

Page 12: ...timer has reached zero the pumplead timer and the pumplag timer 2 Press the h key to check the compressor timers The controller shows the actual value of the the guard timers one per circuit and the...

Page 13: ...the fan motor or the pump motor should be ON indicates the status of this voltage free contact It is activated if there is any alarm on the unit The changeable relay outputs are indicates the status...

Page 14: ...es is activated One of the following safety devices is activated Air or waterflow contact S9L Emergency stop Refer to Symptom 5 One of the following safety devices is activated The ON LED is broken Co...

Page 15: ...er supply are connected in the wrong phase position Invert two phases of the power supply by licensed electrician One phase is not connected properly Check the connection of all phases RESET After inv...

Page 16: ...l Saturdays and Sundays will work according to the settings in group 3 2 all holiday days will work according to the settings in the holiday group All group settings of groups 2 and work similar as fo...

Page 17: ...ion manual 16 ANNEX IV q q q g h h g h g h h g h g g h g g h g h g h h g g f 1 1 1 1 1 1 1 h g h g h h q 4 4 2 4 4 2 4 2 6 4 4 4 h g h g h g h 3 g g h g h g q q q q q q q q q q p 2 4 g g h g h 3 2 2 5...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22681 1...

Reviews: