background image

ERAP110~170MBYNN

Air-cooled condensing units

4PW22681-1

Operation manual

6

How to enter a menu

Digital built-in controller (main menu)
Scroll through the main menu using the 

and

 h

 keys to move

the 

 mark in front of the menu of your choice. Push the 

q

 key

to enter the selected menu.

Digital remote controller
Press the corresponding menu key indicated in "User interface",
paragraph 

"Digital remote controller" on page 5

Connection of a remote digital controller to the unit

For a remote digital controller a cable length of up to 600 metres
between the remote digital controller and the unit is allowed. This
gives the opportunity to control the unit from a considerable distance.
Refer to "Cable for remote digital controller" in the installation manual
for cable specifications.

Working with the unit

This chapter deals with the everyday usage of the unit. Here, you will
find how to perform routine tasks, such as:

"Setting the language" on page 6

"Switching the unit on" on page 6

"Consulting actual operational information" on page 6

"Resetting the unit" on page 7

Setting the language

If wanted, the operating language can be changed to any of the
following languages: English, German, French, Spanish or Italian.

1

Enter the usersettings menu. Refer to chapter 

"How to enter a

menu" on page 6

2

Select the appropriate field using the 

q

 key.

3

Press 

q

  to change the operating language until the desired

language is active.

Switching the unit on

1

Press the 

J

 key on the controller.

Depending on wheter or not a remote ON/OFF switch has been
configured (

refer to the installation manual

), the following

conditions may occur.
When no remote ON/OFF switch is configured, the LED inside
the 

J

 key lights up and an initialization cycle is started. Once all

the timers have reached zero, the unit starts up.
When a remote ON/OFF switch is configured, the following table
applies:

2

If the condensing unit does not start after a few minutes, refer to

"Troubleshooting" on page 13

.

Switching the unit off

If no remote on/off switch is configured:

Press the 

o

 key on the controller.

The LED inside the 

o

 key goes out.

If a remote on/off switch is configured:

Press the 

o

 key on the controller or switch the unit off using the

remote on/off switch.
The LED inside the 

o

 key goes out in the first case and starts

blinking in the second case.

Consulting actual operational information

1

Enter the readout menu. Refer to the chapter 

"How to enter a

menu" on page 6

.

The controller automatically shows the first screen of the
readout menu which provides the following information:

  

  or 

 

:  manual/automatic control

mode operation. If the automatic control mode is selected, the
controller will indicate the active temperature setpoint. Depending
on the status of the remote contact, setpoint one or setpoint two
is active.

   

: actual temperature of sensor thermostat R4T.

2

Press the 

h

 key to enter the next screen of the readout menu.

The 

 

  screen of the readout menu provides

information concerning the status of the different circuits.

: actual status of circuit.

When the circuit is ON, the following status information may
appear.

: 40% - this percentage refers to the activated capacity valve of

that specific circuit.

NOTE

Temperature readout tolerance: ±1°C.

Legibility of the alphanumeric display may decrease in
direct sunlight.

NOTE

When a remote digital controller is connected to a
stand-alone unit, the adress of the remote digital
controller has to be set to 2 by means of the DIP-
switches on the back of the remote digital controller.
Refer to the installation manual "Setting the adresses
on the remote digital controller" for setting the adress.

   

   

     

   

   

   

   

   

Local key

Remote switch

Unit

o

o

o

o

 LED

ON

ON

ON

ON

ON

OFF

OFF

Flashing

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

In case of emergency, switch off the unit by pushing the
emergency stopbutton.

NOTE

Also consult 

"Defining the capacity limitation settings"

on page 10

  and

 

"Customization in the service menu"

chapter "Setting of the changeable inputs and outputs"
in the installation manual.

NOTE

When a circuit is in a high pressure setback, the
indication of capacity will be flashing. A high pressure
setback is a prevention of load-up or a forced load-
down caused by a too high pressure.

Summary of Contents for ERAP110MBYNN

Page 1: ...OPERATION MANUAL ERAP110MBYNN ERAP150MBYNN ERAP170MBYNN Air cooled condensing units...

Page 2: ...RAP150MBYNN ERAP170MBYNN Air cooled condensing units Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before st...

Page 3: ...r intake 1000 1000 1000 1000 1000 3000 2210 2346 13 10 11 7 6 16 2 3 9 5 14 15 8 12 4 1 1 Condenser 9 Power supply intake 2 Compressor M1C 10 Emergency stop S5E 3 Discharge stop valve 11 Switchbox 4 L...

Page 4: ...too low voltage The relays are factory set and may not be adjusted When activated they must be reset manually followed by a reset of the controller Compressor thermal protectors The compressor motors...

Page 5: ...al Q11F Q14F Thermal protectors fan motors Q1M Thermal protector compressor motor R1 Auxiliary resistance for feedback R1F Feedback resistance R1P Reverse phase protector R4T Sensor for thermostat R5T...

Page 6: ...the unit is ready for operation General recommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out cl...

Page 7: ...mote on off switch is configured Press the o key on the controller The LED inside the o key goes out If a remote on off switch is configured Press the o key on the controller or switch the unit off us...

Page 8: ...s refer to User password menu on page 9 Press q to confirm the password and to enter the setpoints menu 2 Select the setpoint to be adjusted using the q key A setpoint is selected when the cursor is b...

Page 9: ...control mode To consult information about the unit status To consult information about the pressures To consult actual operational information about the ambient temperature the total running hours of...

Page 10: ...keys 2 Position the cursor behind the parameter to be modified using the q key 3 Select the appropriate setting using the g and h keys 4 Press q to confirm the selection When the selection has been c...

Page 11: ...group Defining dual evaporator fan pump control The screen of the user settings menu allows the user to define the steering of 2 evaporator fans pumps for this to be possible a changeable digital outp...

Page 12: ...timer has reached zero the pumplead timer and the pumplag timer 2 Press the h key to check the compressor timers The controller shows the actual value of the the guard timers one per circuit and the...

Page 13: ...the fan motor or the pump motor should be ON indicates the status of this voltage free contact It is activated if there is any alarm on the unit The changeable relay outputs are indicates the status...

Page 14: ...es is activated One of the following safety devices is activated Air or waterflow contact S9L Emergency stop Refer to Symptom 5 One of the following safety devices is activated The ON LED is broken Co...

Page 15: ...er supply are connected in the wrong phase position Invert two phases of the power supply by licensed electrician One phase is not connected properly Check the connection of all phases RESET After inv...

Page 16: ...l Saturdays and Sundays will work according to the settings in group 3 2 all holiday days will work according to the settings in the holiday group All group settings of groups 2 and work similar as fo...

Page 17: ...ion manual 16 ANNEX IV q q q g h h g h g h h g h g g h g g h g h g h h g g f 1 1 1 1 1 1 1 h g h g h h q 4 4 2 4 4 2 4 2 6 4 4 4 h g h g h g h 3 g g h g h g q q q q q q q q q q p 2 4 g g h g h 3 2 2 5...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22681 1...

Reviews: