Domestic hot water tank for air to water heat pump system

4PW64052-1 – 08.2010

Installation manual

3

I

NSTALLATION

 

OF

 

THE

 EKHTS 

DOMESTIC

 

HOT

 

WATER

 

TANK

If required by relevant local and national regulations, connect a
recirculation pump in between the hot water end point and the
recirculation connection of the domestic hot water tank.

Installation guidelines

Keep in mind the following guidelines when installing the domestic
hot water tank:

The installation location is frost-free.

Standard installation location of the domestic hot water tank is
on top of the indoor unit.

The domestic hot water tank can be floor mounted as well. In
that case, the dedicated EKFMAHTB connection kit for
installation of the domestic hot water tank next to the indoor unit
is required and to be ordered separately.

Locate the domestic hot water tank in a suitable position to
facilitate ease of maintenance. Refer to 

figure 3

  and to the

installation manual of the indoor unit.

Provide a connection for the pressure relief valve and drain on
the cold water inlet.

To  avoid back siphonage it is advised to install a non-return
valve on the cold water inlet of the domestic hot water tank in
accordance with local and national regulations.

Take  care that in the event of a leak, water can not cause any
damage to the installation space and surroundings.

It is advised to install a pressure reducing valve on the cold
water inlet in accordance with local and national regulations.

An expansion vessel should be installed on the cold water inlet
in accordance with local and national regulations.

Installing and commissioning the domestic hot water 
tank

Installing the hot water tank on top of the indoor unit

1

Unpack the domestic hot water tank according to the
instructions mentioned on the unpacking instruction sheet.

2

Check if all domestic hot water tank accessories are enclosed
(see 

"Accessories" on page 1

).

3

Remove the decoration panels and top plate of the indoor unit.

Take  away  the decoration panels by removing the 2 bottom
screws and then unhitching the panels.

Mount the top plate of the indoor unit on the domestic hot water
tank module.

Installation shall be done by a licensed technician, the
choice of materials and installation shall comply with
local and national regulations.

The equipment is not intended for use in a potentially
explosive atmosphere.

Domestic hot water quality must be according to EU
directive 98/83 EC.

A drain device should be installed on the cold water
connection on the domestic hot water tank.

For safety reasons, it is not allowed to add any kind of
glycol to the water circuit.

To  avoid stagnation of water, it is important that the
storage capacity of the domestic hot water tank meets
the daily consumption of domestic hot water.

In cases where during longer periods of time there is
no consumption of hot water, the equipment must be
flushed with fresh water before usage.

The disinfection function provided on the equipment is
specified in the operation manual of the indoor unit.

It is advised to avoid long runs of piping between the
domestic hot water tank and the hot water end point
(shower, bath, ...) and to avoid dead ends.

The installation must be in compliance with local and
national regulations and may require additional
hygienic installation measures.

In accordance with local and national regulations it
may be necessary to install thermostatic mixing
valves.

Immediately after installation, the domestic hot water
tank must be flushed with fresh water. This procedure
must be repeated at least once a day the first
5 consecutive days after installation.

3

4

1

2

1

Recirculation connection

2

Hot water connection

3

Shower

4

Recirculation pump

If available service space to left and/or right side is
limited, carefully consider all indoor module
installation steps first.

2x

2x

2x

3

3

2x

1

1

1

2x

4PW64052-1_digital_EN.book  Page 3  Monday, August 30, 2010  8:48 AM

Summary of Contents for EKHTS200AC

Page 1: ...INSTALLATION MANUAL EKHTS200AC EKHTS260AC EKHTSU200AC EKHTSU260AC EKUHWHTA Domestic hot water tank for air to water heat pump system...

Page 2: ...1 3 2x 5x 1 3 4 2 1x 340 mm 1x B A C 1x 1x 7 5 6 10 11 11 12 2 1 5 4 6 8 3 9 1 2 7 772 902 1032 H 120 6 0 778 694 443 600 300 9 3 10 4 5 A 250 600 30 50 30 A EKHBRD EKHVMR YD EKHVH X 250 250 300 2 1...

Page 3: ...ification ACCESSORIES Accessories supplied with the domestic hot water tank See figure 1 Optional equipment EKFMAHTB Connection kit for installation of the domestic hot water tank on the floor next to...

Page 4: ...G 3 4 Female B T piece field supply C Pressure relief valve connection field supply D Pressure relief valve field supply E Recirculation connection G 1 2 Male F Thermistor socket G Flow inlet connect...

Page 5: ...ck if all domestic hot water tank accessories are enclosed see Accessories on page 1 3 Remove the decoration panels and top plate of the indoor unit Take away the decoration panels by removing the 2 b...

Page 6: ...ing connections 2 Installation position The 3 way valve must be installed in the indoor unit 3 Unpack the 3 way valve body and 3 way valve motor Verify that following accessories are provided with the...

Page 7: ...l 5 5 Install the 3 way valve body in the piping Refer to the figure below before making the connection For EKHBRD indoor units only For EKHVMRD indoor units only Avoid contact between hot piping and...

Page 8: ...00 260AC Domestic hot water tank for air to water heat pump system 4PW64052 1 08 2010 For EKHVMYD indoor units only For EKHVH X indoor units only 8 9 4 A 5 6 1 1 3 2 7 8 A 7 6 2 1 10 10 1 1 13 12 9 4...

Page 9: ...he edges of the knocked out holes to protect the flexible hoses If the recirculation connection is used connect a tube with threaded connection to this hole and guide it through a hole in the rear pla...

Page 10: ...r supply cable must always be at least 25 mm to prevent electromagnetic interference on the thermistor cable 1 Plug the thermistor cable connector in the socket X11A EKHBRD EKHVMR YD A3P or X9A EKHVH...

Page 11: ...ter taps after all air is expelled 4 Check for leaks 5 Manually operate the pressure relief valve to ensure free water flow through the discharge pipe turn knob counterclockwise Refer to Main componen...

Page 12: ...repair activity always switch off the circuit breaker on the supply panel remove the fuses or open the protection devices of the unit Make sure that before starting any maintenance or repair activity...

Page 13: ...l Stainless steel Stainless steel Overall dimensions h x l x w mm 1335 x 600 x 695 1610 x 600 x 695 Connections Quick coupling G 3 4 F Quick coupling G 3 4 F Inspection opening G1 2 M Recirculation co...

Page 14: ...1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 6 6 7 7 8 8 9 8 6 9 1 2 5 EKHVH X 4 EKHBRD 1 2 9 3 9 3 7 6 7 6 8 8 10 10 10 4 4 8 5 5 4 5...

Page 15: ...1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 6 6 7 7 8 8 9 8 6 9 1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 8 6 6 8 8 7 7 9 6 9 7 EKHVMYD 6 EKHVMRD 6 7...

Page 16: ...4PW64052 1 08 2010 Copyright 2010 Daikin...

Reviews: