Installation manual

8

E260AC

Domestic hot water tank for air to water heat pump system

4PW64052-1 – 08.2010

9

Connect the thermistor wire to the indoor unit switch box. Make
sure power supply is switched off. Refer to the wiring diagram
delivered with the indoor unit.

For EKHBRD and EKHVMR/YD units only

For EKHVH/X units only

The distance between the thermistor cable and power supply
cable must always be at least 25 mm to prevent electromagnetic
interference on the thermistor cable.

1

Plug the thermistor cable connector in the socket X11A
( EKHVMR/YD (A3P)) or X9A (EKHVH/X (A1P))
on the PCB.

2

Fix the cables to the cable tie mountings with cable ties to
ensure strain relief.

3

When routing out cables, make sure that these do not
obstruct mounting of the indoor unit cover.

Note: only relevant field wiring is shown.

For EKHBRD indoor units only.

X11A

A3P

BLU

BLK

BRN

N Y L

3-way

valve

X2M

3 4 5

>25 mm

1~

BLU

BLK

BRN

N Y L

3-way

valve

X2M

3 4 5

>25 mm

X11A

A3P

3~

4PW64052-1_digital_EN.book  Page 8  Monday, August 30, 2010  8:48 AM

Summary of Contents for EKHTS200AC

Page 1: ...INSTALLATION MANUAL EKHTS200AC EKHTS260AC EKHTSU200AC EKHTSU260AC EKUHWHTA Domestic hot water tank for air to water heat pump system...

Page 2: ...1 3 2x 5x 1 3 4 2 1x 340 mm 1x B A C 1x 1x 7 5 6 10 11 11 12 2 1 5 4 6 8 3 9 1 2 7 772 902 1032 H 120 6 0 778 694 443 600 300 9 3 10 4 5 A 250 600 30 50 30 A EKHBRD EKHVMR YD EKHVH X 250 250 300 2 1...

Page 3: ...ification ACCESSORIES Accessories supplied with the domestic hot water tank See figure 1 Optional equipment EKFMAHTB Connection kit for installation of the domestic hot water tank on the floor next to...

Page 4: ...G 3 4 Female B T piece field supply C Pressure relief valve connection field supply D Pressure relief valve field supply E Recirculation connection G 1 2 Male F Thermistor socket G Flow inlet connect...

Page 5: ...ck if all domestic hot water tank accessories are enclosed see Accessories on page 1 3 Remove the decoration panels and top plate of the indoor unit Take away the decoration panels by removing the 2 b...

Page 6: ...ing connections 2 Installation position The 3 way valve must be installed in the indoor unit 3 Unpack the 3 way valve body and 3 way valve motor Verify that following accessories are provided with the...

Page 7: ...l 5 5 Install the 3 way valve body in the piping Refer to the figure below before making the connection For EKHBRD indoor units only For EKHVMRD indoor units only Avoid contact between hot piping and...

Page 8: ...00 260AC Domestic hot water tank for air to water heat pump system 4PW64052 1 08 2010 For EKHVMYD indoor units only For EKHVH X indoor units only 8 9 4 A 5 6 1 1 3 2 7 8 A 7 6 2 1 10 10 1 1 13 12 9 4...

Page 9: ...he edges of the knocked out holes to protect the flexible hoses If the recirculation connection is used connect a tube with threaded connection to this hole and guide it through a hole in the rear pla...

Page 10: ...r supply cable must always be at least 25 mm to prevent electromagnetic interference on the thermistor cable 1 Plug the thermistor cable connector in the socket X11A EKHBRD EKHVMR YD A3P or X9A EKHVH...

Page 11: ...ter taps after all air is expelled 4 Check for leaks 5 Manually operate the pressure relief valve to ensure free water flow through the discharge pipe turn knob counterclockwise Refer to Main componen...

Page 12: ...repair activity always switch off the circuit breaker on the supply panel remove the fuses or open the protection devices of the unit Make sure that before starting any maintenance or repair activity...

Page 13: ...l Stainless steel Stainless steel Overall dimensions h x l x w mm 1335 x 600 x 695 1610 x 600 x 695 Connections Quick coupling G 3 4 F Quick coupling G 3 4 F Inspection opening G1 2 M Recirculation co...

Page 14: ...1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 6 6 7 7 8 8 9 8 6 9 1 2 5 EKHVH X 4 EKHBRD 1 2 9 3 9 3 7 6 7 6 8 8 10 10 10 4 4 8 5 5 4 5...

Page 15: ...1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 6 6 7 7 8 8 9 8 6 9 1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 8 6 6 8 8 7 7 9 6 9 7 EKHVMYD 6 EKHVMRD 6 7...

Page 16: ...4PW64052 1 08 2010 Copyright 2010 Daikin...

Reviews: