background image

E260AC

Domestic hot water tank for air to water heat pump system

4PW64052-1 – 08.2010

Installation manual

9

For EKHVMR/YD indoor units only.

For EKHVH/X indoor units only.

10

Only for EKHBRD and EKHVMR/YD units: reattach the drain
plate on the indoor unit.

11

Commissioning

Follow the next steps to fill up the domestic hot water tank:

1

Open each hot water tap in turn to expel air from the system
pipe work.

2

Open the cold water supply valve. Make sure the decoration
panels of both the domestic hot water tank and the indoor
unit are aligned.

3

Close all water taps after all air is expelled.

4

Check for leaks.

5

Manually operate the pressure relief valve to ensure free
water flow through the discharge pipe (turn knob
counterclockwise). Refer to 

"Main components" on page 2

 for

location of the pressure relief valve.

12

Reattach the front decoration panel
of the domestic hot water tank.

13

Reattach the front decoration panel
of the indoor unit.

Installing the hot water tank by the side of the indoor unit

Refer to the manual delivered with the kit EKFMAHTB.

X2M

A9P

X3M

3

45

A3P

X11A

BLU

BRN

BLK

N

Y L

3-way

valve

>50 mm

X2M

X3M

10

9

8

A1P

X9A

BLU

BRN

BLK

N

Y L

3-way

valve

>25 mm

X9B

The domestic hot water tank coil must be filled with
water at the indoor unit water inlet. This to avoid that
dirt enters the system.

2x

2x

4PW64052-1_digital_EN.book  Page 9  Monday, August 30, 2010  8:48 AM

Summary of Contents for EKHTS200AC

Page 1: ...INSTALLATION MANUAL EKHTS200AC EKHTS260AC EKHTSU200AC EKHTSU260AC EKUHWHTA Domestic hot water tank for air to water heat pump system...

Page 2: ...1 3 2x 5x 1 3 4 2 1x 340 mm 1x B A C 1x 1x 7 5 6 10 11 11 12 2 1 5 4 6 8 3 9 1 2 7 772 902 1032 H 120 6 0 778 694 443 600 300 9 3 10 4 5 A 250 600 30 50 30 A EKHBRD EKHVMR YD EKHVH X 250 250 300 2 1...

Page 3: ...ification ACCESSORIES Accessories supplied with the domestic hot water tank See figure 1 Optional equipment EKFMAHTB Connection kit for installation of the domestic hot water tank on the floor next to...

Page 4: ...G 3 4 Female B T piece field supply C Pressure relief valve connection field supply D Pressure relief valve field supply E Recirculation connection G 1 2 Male F Thermistor socket G Flow inlet connect...

Page 5: ...ck if all domestic hot water tank accessories are enclosed see Accessories on page 1 3 Remove the decoration panels and top plate of the indoor unit Take away the decoration panels by removing the 2 b...

Page 6: ...ing connections 2 Installation position The 3 way valve must be installed in the indoor unit 3 Unpack the 3 way valve body and 3 way valve motor Verify that following accessories are provided with the...

Page 7: ...l 5 5 Install the 3 way valve body in the piping Refer to the figure below before making the connection For EKHBRD indoor units only For EKHVMRD indoor units only Avoid contact between hot piping and...

Page 8: ...00 260AC Domestic hot water tank for air to water heat pump system 4PW64052 1 08 2010 For EKHVMYD indoor units only For EKHVH X indoor units only 8 9 4 A 5 6 1 1 3 2 7 8 A 7 6 2 1 10 10 1 1 13 12 9 4...

Page 9: ...he edges of the knocked out holes to protect the flexible hoses If the recirculation connection is used connect a tube with threaded connection to this hole and guide it through a hole in the rear pla...

Page 10: ...r supply cable must always be at least 25 mm to prevent electromagnetic interference on the thermistor cable 1 Plug the thermistor cable connector in the socket X11A EKHBRD EKHVMR YD A3P or X9A EKHVH...

Page 11: ...ter taps after all air is expelled 4 Check for leaks 5 Manually operate the pressure relief valve to ensure free water flow through the discharge pipe turn knob counterclockwise Refer to Main componen...

Page 12: ...repair activity always switch off the circuit breaker on the supply panel remove the fuses or open the protection devices of the unit Make sure that before starting any maintenance or repair activity...

Page 13: ...l Stainless steel Stainless steel Overall dimensions h x l x w mm 1335 x 600 x 695 1610 x 600 x 695 Connections Quick coupling G 3 4 F Quick coupling G 3 4 F Inspection opening G1 2 M Recirculation co...

Page 14: ...1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 6 6 7 7 8 8 9 8 6 9 1 2 5 EKHVH X 4 EKHBRD 1 2 9 3 9 3 7 6 7 6 8 8 10 10 10 4 4 8 5 5 4 5...

Page 15: ...1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 6 6 7 7 8 8 9 8 6 9 1 2 1 2 3 3 9 9 5 5 4 4 10 10 10 8 6 6 8 8 7 7 9 6 9 7 EKHVMYD 6 EKHVMRD 6 7...

Page 16: ...4PW64052 1 08 2010 Copyright 2010 Daikin...

Reviews: