background image

EKHBRD011~Y1

Indoor unit for air to water heat pump system

4PW60970-1B

Installation manual

14

Precautions when connecting field piping and regarding 
insulation

The complete water circuit, inclusive all piping, must be insulated to
prevent reduction of the heating capacity.

If the indoor ambient temperature is higher than 30°C and the
humidity is higher than RH 80% then the thickness of the insulation
materials should be at least 20 mm in order to avoid condensation on
the surface of the insulation.

C

HARGING

 

WATER

Method for adding water

1

Connect the water supply to a fill valve (field supply).

2

Make sure the automatic air purge valve is open (at least 2
turns).

3

Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as
possible using the air purge valves (refer to 

"[E-04] Pump only

operation" on page 25

). Air present in the water circuit might

cause malfunctioning of the heater kit (if installed).

4

For units with optional heater kit: remove air in the heater vessel
using the heater kit air purge valve.

E

LECTRICAL

 

WIRING

 

WORK

Precautions on electrical wiring work

NOTE

During filling, it might not be possible to remove all
air in the system. Remaining air will be removed
through the automatic air purge valves during first
operating hours of the system. Additional filling
with water afterwards might be required.

The water pressure indicated on the manometer
will vary depending on the water temperature
(higher pressure at higher water temperature).
However, at all times water pressure should
remain above 0.3 bar to avoid air entering the
circuit.

The unit might dispose some excessive water
through the pressure relief valve.

Water quality must be according to EU directive
98/83 EC.

WARNING

A main switch or other means for disconnection,
having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with
relevant local and national regulations.

Switch off the power supply before making any
connections.

Use only copper wires.

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.

Be sure to install the required fuses as mentioned on
the electrical wiring diagram.

The field wiring must be carried out in accordance
with the wiring diagram supplied with the unit and the
instructions given below.

Never squeeze bundled cables and make sure that it
does not come in contact with the piping and sharp
edges.

Make sure no external pressure is applied to the
terminal connections.

Be sure to use a dedicated power supply. Never use a
power supply shared by another appliance.

Be sure to establish an earth. Do not earth the unit to
a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.

Be sure to install an earth leakage protector in
accordance with relevant local and national
regulations. Failure to do so may cause electrical
shock.

When installing the earth leakage protector make
sure that it is compatible with the inverter (resistant to
high frequency electrical noise) to avoid unnecessary
opening of the earth leakage protector.

As this unit is equipped with an inverter, installing a
phase advancing capacitor not only will deteriorate
power factor improvement effect, but also may cause
capacitor abnormal heating accident due to high-
frequency waves. Therefore, never install a phase
advancing capacitor.

Be sure that after installation work all the rubber
bushings are put back in place to protect the wires
from touching sharp edges.

For V1 models only

Equipment complying with EN/IEC 61000-3-12

(a)

This equipment complies with EN/IEC 61000-3-11

(b)

provided that the system impedance Z

sys

 is less than

or equal to Z

max

  at the interface point between the

user's supply and the public system. It is the
responsibility of the installer or user of the equipment
to ensure, by consultation with the distribution
network operator if necessary, that the equipment is
connected only to a supply with a system impedance
Z

sys

 less than or equal to Z

max

.

(a) European/International Technical Standard setting the limits for harmonic currents 

produced by equipment connected to public low-voltage systems with input 
current >16 A and 

75 A per phase.

(b) European/International Technical Standard setting the limits for voltage changes, 

voltage fluctuations and flicker in public low-voltage supply systems for equipment 
with rated current 

75 A.

011

014

016

Z

max

 =

0.34 

0.32 

0.32 

4PW60970-1B_digital_EN.book  Page 14  Thursday, September 2, 2010  1:15 PM

Summary of Contents for EKHBRD011ABV1

Page 1: ...ION MANUAL EKHBRD011ABV1 EKHBRD014ABV1 EKHBRD016ABV1 EKHBRD011ABY1 EKHBRD014ABY1 EKHBRD016ABY1 Indoor unit for air to water heat pump system 4PW60970 1B_digital_EN book Page 1 Thursday September 2 201...

Page 2: ...62 15 12 13 14 14 14 14 PS LV HV HV LV PS LV HV PS 552 37 227 7 120 143 69 3 3 11 8 11 6 10 2 1 24 45 16 31 10 4 9 16 5 8 10 10 11 11 6 7 1x 1x 8x 1x 1x 1x 1 2 3 1x 4 6 2x 8 2x 7 2x 9 1x 10 11 2x 12 5...

Page 3: ...06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 1...

Page 4: ...N General information Thank you for purchasing this unit The unit is the indoor part of the air to water ERSQ or ERRQ heat pump The unit is designed for floor standing indoor installation and used for...

Page 5: ...NOT to use a balancing bottle Using a balancing bottle will affect the optimal pump control of the unit and will increase the cost of the system unnecessarily Application 1 Space heating and domestic...

Page 6: ...mer operation 1 Outdoor unit 10 Collector field supply 2 Indoor unit 11 Radiator field supply 3 Refrigerant heat exchanger 12 Electronic expansion valve 4 Water heat exchanger 13 By pass valve field s...

Page 7: ...fer to the chapter Multiple set point control on page 28 for more information about the configuration of your system 1 Outdoor unit 14 By pass valve field supply 2 Indoor unit 3 Electronic expansion v...

Page 8: ...3 4 5 6 8 2 1 11 M 9 12 12 7 C1 15 16 13 13 20 20 19 10 A B 14 17 18 Boiler thermostat Boiler thermostat C Auxiliary contact normal closed th Heating only room thermostat K1A Auxiliary relay for activ...

Page 9: ...15 21 23 25 27 29 31 33 35 37 39 41 43 45 47 flow l min ESP kPa 90 100 110 16 kW 14 kW 14 kW 11 kW 11 kW 16 kW NOTE When replacing an old gas or fuel oil boiler by a air to water heat pump system EKHB...

Page 10: ...Maintenance activities on page 34 12 Expansion vessel 12 l 13 Manometer The manometer allows readout of the water pressure in the water circuit 14 Pump The pump circulates the water in the water circ...

Page 11: ...nterface relay K1A 21 Wiring bridges 22 Fuse F1 only Y1 23 Fuse F2 only Y1 Functional diagram 8 12 20 19 14 13 1 3 5 9 16 17 18 10 11 6 7 21 2 8 12 20 19 14 13 1 2 3 4 6 16 17 18 10 9 11 23 21 22 7 NO...

Page 12: ...rder to prevent damage during transport Unpack the indoor unit completely according to the instructions mentioned on the unpacking instructions sheet Check if all indoor unit accessories see Accessori...

Page 13: ...rd installation location of the optional domestic hot water tank is on top of the indoor unit If available service space to left and or right side is limited carefully consider all tank module install...

Page 14: ...s back to the unit using the appropriate screws 4 Stick the top plate insulation accessory at the inside of the top decoration panel according to the figure below 5 Fix the top decoration panel on top...

Page 15: ...air in the water circuit remains possible Take care that the components installed in the field piping can withstand the water pressure and temperature Always use materials which are compatible with th...

Page 16: ...this must be done is explained in the chapter Opening the unit on page 35 Connecting the water circuit Water connections must be made The location of the water inlet connection and the water outlet c...

Page 17: ...e to install the required fuses as mentioned on the electrical wiring diagram The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions giv...

Page 18: ...R3L Reactor R1H Humidity sensor optional EKRTR R1T Ambient sensor optional EKRTW R R2T Domestic hot water tank thermistor EKHTS optional R2T External sensor floor or ambient EKRTETS optional R3T Liqu...

Page 19: ...LV Benefit kWh rate power supply switch S1S a 2 2 100 mA c 9 LV Multiple set point signal 1 a 2 2 100 mA c 10 LV Multiple set point signal 2 a 2 2 100 mA c 11 LV Heater kit signal a Refer to the inst...

Page 20: ...f time The indoor unit is designed to receive an input signal by which the unit switches into forced off mode At that moment the unit compressors will not operate Possible types of benefit kWh rate po...

Page 21: ...h box and the inside of the unit on loose connections or damaged electrical components 5 Installation Check that the unit is properly installed to avoid abnormal noises and vibrations when starting up...

Page 22: ...s at variance with the default value A detailed description of each field setting is given under Detailed description on page 20 Refer to the Annex on page 38 for a detailed overview and guide to star...

Page 23: ...n is enabled the setback operation will have priority over the scheduled action in the schedule timer Permission level 2 level 3 Operation ON OFF Operable Operable Domestic water heating operation ON...

Page 24: ...receding programmed command and will remain active until the next programmed command occurs Example imagine the actual time is 17 30 and actions are programmed at 13 00 16 00 and 19 00 The last progra...

Page 25: ...high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 4 Disinfection function This mode will disinfect...

Page 26: ...8 Option setup 8 00 Remote controller temperature control When using the remote control delivered with the unit 2 types of temperature control are possible Default 8 00 1 which means that the remote c...

Page 27: ...a certain temperature When enabled the indoor unit will deliver hot water to the domestic hot water tank if the reheat minimum value is reached The domestic water heating will continue until the rehe...

Page 28: ...the air removal from the circuit The pump can operate at different speed E 04 0 normal operation of the unit default E 04 1 low pump speed operation E 04 2 high pump speed operation If you select E 0...

Page 29: ...aving water thermo on request F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature maximum possible storage temperature b 03 H Domestic hot water reheat minimum te...

Page 30: ...Remote controller room temperature F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature maximum possible storage temperature b 03 H Domestic hot water reheat mini...

Page 31: ...t point requested during space heating operation The valve allowing water to enter the domestic hot water tank coil is open The heat pump will deliver water with a higher temperature which is needed f...

Page 32: ...rnal room thermostat Indoor unit Domestic hot water tank Temperature reducing device Space 1 Space 1 Space 2 Space 2 Balancing bottle Set point Field setting Thermo status Domestic hot water 70 C a a...

Page 33: ...ermostat control with remote controller room thermostat function and external room thermostat 1 When using the automatic weather dependent function for setting of space 0 you have to make sure that th...

Page 34: ...temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day selection Fri...

Page 35: ...re 70 45 75 1 C 04 Automatic maximum domestic hot water storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Set point leaving water maximum temperature 80 37 80 1 C 01 Set point lea...

Page 36: ...user interface will return to normal mode after 10 seconds or by pressing the z button once To test the space heating operation push the y button to start the test run operation 4 The test run operati...

Page 37: ...certain troubles which may occur in the unit This troubleshooting and related corrective actions may only be carried out by your local Daikin technician General guidelines Before starting the troubles...

Page 38: ...ake sure there is no air in the system purge air Check on the manometer that there is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Make sure that the...

Page 39: ...Contact your local dealer E1 Compressor PCB error Contact your local dealer E3 High pressure error S1PH Check wiring connections on outdoor unit and indoor unit Make sure the circuit is filled with wa...

Page 40: ...h 15 9 5 8 inch 15 9 5 8 inch Expansion vessel volume l 12 12 12 12 12 12 maximum working pressure MWP bar 4 4 4 4 4 4 Pump type DC motor DC motor DC motor DC motor DC motor DC motor no of speed inver...

Page 41: ...01 1 page 23 What type of appliance do you have No Blank display Push the b button n You selected permission level 3 on remote controller 0 00 3 page 20 You selected automatic leaving water control p...

Page 42: ...g on settings request w icon will start blinking with 0 5 second intervals Domestic hot water production will start immediately w icon will start blinking with 1 second intervals Choose start time 1 0...

Page 43: ...room thermostat control Yes Yes Yes 2 No Operation will switch to space heating Operation will switch to space heating Timer d 02 15 minutes passed since 2 No Space heating operation will continue til...

Page 44: ...NOTES 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...

Page 45: ...NOTES 4PW60970 1B_digital_EN book Page 2 Thursday September 2 2010 1 15 PM...

Page 46: ...NOTES 4PW60970 1B_digital_EN book Page 3 Thursday September 2 2010 1 15 PM...

Page 47: ...V1 Y1 NOTES 5 5 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...

Page 48: ...4PW60970 1B Copyright 2010 Daikin 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...

Reviews: