EKHBRD011~Y1

Indoor unit for air to water heat pump system

4PW60970-1B

Installation manual

2

Room thermostat (option)

An optional room thermostat EKRTR or EKRTW can be connected to
the indoor unit.

Refer to the room thermostat installation manual for further details.

Heater kit (option)

An optional EKBUH heater kit can be combined with the indoor unit.
Purpose is to provide an additional heating capacity during cold
outdoor temperatures. The heater kit has a heating capacity of 6 kW,
and available for both 1-phase and 3-phase power supply
specifications. When using this heater kit, installation of the optional
demand PCB is required as well.

Refer to the heater kit installation manual for further details.

Digital I/O PCB (option) 

An optional EKRP1HBA digital I/O PCB can be connected to the
indoor unit and be used to remotely monitor your system. This
address card offers 3 voltage free outputs.

Refer to the operation manual of the indoor unit and to the digital I/O
PCB installation manual for more information.

Refer to the wiring diagram or connection diagram for connecting this
PCB to the unit.

Demand PCB (option)

An optional EKRP1AHTA demand PCB can be connected to the
indoor unit. This PCB is needed when the optional heater kit EKBUH
or Daikin room thermostat EKRTR or EKRTW is installed or when
multiple set point control is used, and provides the communication
with the indoor unit.

Refer to the demand PCB installation manual for further details.

Refer to the wiring diagram or connection diagram for connecting this
PCB to the unit.

Scope of this manual

This installation manual describes the procedures for handling,
installing and connecting all EKHBRD indoor unit models.

Model identification

Indoor unit

Typical application examples

The application examples given below are for illustration purposes
only.

Application examples with only 1 heat emitter and 1
heat source (EKHBRD unit)

If only 1 heat emitter (= all system has 1 water set point), it is
recommended NOT to use a balancing bottle.

Using a balancing bottle will affect the optimal pump control of the
unit and will increase the cost of the system unnecessarily.

Application 1

Space heating and domestic hot water heating with a single
remote controller installed in the living room.

The remote controller gives immediate feedback to the indoor
unit and by doing so it matches in a smart way the unit
performance to the demanded space heating requirements. In
this way there is no frequent start/stop of the unit or there are no
too big temperature fluctuations in the to be heated rooms. This
remote controller has also a smart logic functionality which
controls the combined space heating and domestic hot water
demand (e.g. if room temperature drops more than 3°C during
domestic hot water operation, the unit will automatically switch
back to space heating). There is no remote controller near the
unit. During service maintenance an additional remote controller
can be connected by a service person.

If this option is installed it is not possible to use the remote
controller thermostat function.

1

Heat pump capacity

2

Required heating capacity (site dependent)

3

Additional heating capacity provided by the heater kit

T

A

Ambient (outdoor) temperature

P

H

Heating capacity

NOTE

Installation of the ERSQ or ERRQ heat pump outdoor
is described in the outdoor unit installation manual.

Operation of the indoor unit is described in the indoor
unit operation manual.

T

A

2

1

P

H

3

EK

HBR

D

016

AB

V1

V1=1N~, 220-240 V, 50 Hz
Y1=3N~, 380-415 V, 50 Hz

Series

Indication of heating capacity (kW)

(a)

(a) For exact values, refer to 

"Unit specifications" on page 37

.

Refrigerant type R134a

Hydro box - high temperature heating only

European kit

1

Outdoor unit

9

Domestic hot water 
tank (optional)

2

Indoor unit

3

Refrigerant heat 
exchanger

10

Collector (field supply)

11

Radiator (field supply)

4

Water heat exchanger

12

Electronic expansion 
valve

5

Compressor

6

Pump

13

By-pass valve (field 
supply)

7

Shut-off valve

8

Motorized 3-way valve 
(optional)

C1

Remote controller

A

Installation place

B

Living room

7 10 13

4

3

12

12

2

1

8

6

5

M

11

9

C1

A

B

4PW60970-1B_digital_EN.book  Page 2  Thursday, September 2, 2010  1:15 PM

Summary of Contents for EKHBRD011ABV1

Page 1: ...ION MANUAL EKHBRD011ABV1 EKHBRD014ABV1 EKHBRD016ABV1 EKHBRD011ABY1 EKHBRD014ABY1 EKHBRD016ABY1 Indoor unit for air to water heat pump system 4PW60970 1B_digital_EN book Page 1 Thursday September 2 201...

Page 2: ...62 15 12 13 14 14 14 14 PS LV HV HV LV PS LV HV PS 552 37 227 7 120 143 69 3 3 11 8 11 6 10 2 1 24 45 16 31 10 4 9 16 5 8 10 10 11 11 6 7 1x 1x 8x 1x 1x 1x 1 2 3 1x 4 6 2x 8 2x 7 2x 9 1x 10 11 2x 12 5...

Page 3: ...06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 1...

Page 4: ...N General information Thank you for purchasing this unit The unit is the indoor part of the air to water ERSQ or ERRQ heat pump The unit is designed for floor standing indoor installation and used for...

Page 5: ...NOT to use a balancing bottle Using a balancing bottle will affect the optimal pump control of the unit and will increase the cost of the system unnecessarily Application 1 Space heating and domestic...

Page 6: ...mer operation 1 Outdoor unit 10 Collector field supply 2 Indoor unit 11 Radiator field supply 3 Refrigerant heat exchanger 12 Electronic expansion valve 4 Water heat exchanger 13 By pass valve field s...

Page 7: ...fer to the chapter Multiple set point control on page 28 for more information about the configuration of your system 1 Outdoor unit 14 By pass valve field supply 2 Indoor unit 3 Electronic expansion v...

Page 8: ...3 4 5 6 8 2 1 11 M 9 12 12 7 C1 15 16 13 13 20 20 19 10 A B 14 17 18 Boiler thermostat Boiler thermostat C Auxiliary contact normal closed th Heating only room thermostat K1A Auxiliary relay for activ...

Page 9: ...15 21 23 25 27 29 31 33 35 37 39 41 43 45 47 flow l min ESP kPa 90 100 110 16 kW 14 kW 14 kW 11 kW 11 kW 16 kW NOTE When replacing an old gas or fuel oil boiler by a air to water heat pump system EKHB...

Page 10: ...Maintenance activities on page 34 12 Expansion vessel 12 l 13 Manometer The manometer allows readout of the water pressure in the water circuit 14 Pump The pump circulates the water in the water circ...

Page 11: ...nterface relay K1A 21 Wiring bridges 22 Fuse F1 only Y1 23 Fuse F2 only Y1 Functional diagram 8 12 20 19 14 13 1 3 5 9 16 17 18 10 11 6 7 21 2 8 12 20 19 14 13 1 2 3 4 6 16 17 18 10 9 11 23 21 22 7 NO...

Page 12: ...rder to prevent damage during transport Unpack the indoor unit completely according to the instructions mentioned on the unpacking instructions sheet Check if all indoor unit accessories see Accessori...

Page 13: ...rd installation location of the optional domestic hot water tank is on top of the indoor unit If available service space to left and or right side is limited carefully consider all tank module install...

Page 14: ...s back to the unit using the appropriate screws 4 Stick the top plate insulation accessory at the inside of the top decoration panel according to the figure below 5 Fix the top decoration panel on top...

Page 15: ...air in the water circuit remains possible Take care that the components installed in the field piping can withstand the water pressure and temperature Always use materials which are compatible with th...

Page 16: ...this must be done is explained in the chapter Opening the unit on page 35 Connecting the water circuit Water connections must be made The location of the water inlet connection and the water outlet c...

Page 17: ...e to install the required fuses as mentioned on the electrical wiring diagram The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions giv...

Page 18: ...R3L Reactor R1H Humidity sensor optional EKRTR R1T Ambient sensor optional EKRTW R R2T Domestic hot water tank thermistor EKHTS optional R2T External sensor floor or ambient EKRTETS optional R3T Liqu...

Page 19: ...LV Benefit kWh rate power supply switch S1S a 2 2 100 mA c 9 LV Multiple set point signal 1 a 2 2 100 mA c 10 LV Multiple set point signal 2 a 2 2 100 mA c 11 LV Heater kit signal a Refer to the inst...

Page 20: ...f time The indoor unit is designed to receive an input signal by which the unit switches into forced off mode At that moment the unit compressors will not operate Possible types of benefit kWh rate po...

Page 21: ...h box and the inside of the unit on loose connections or damaged electrical components 5 Installation Check that the unit is properly installed to avoid abnormal noises and vibrations when starting up...

Page 22: ...s at variance with the default value A detailed description of each field setting is given under Detailed description on page 20 Refer to the Annex on page 38 for a detailed overview and guide to star...

Page 23: ...n is enabled the setback operation will have priority over the scheduled action in the schedule timer Permission level 2 level 3 Operation ON OFF Operable Operable Domestic water heating operation ON...

Page 24: ...receding programmed command and will remain active until the next programmed command occurs Example imagine the actual time is 17 30 and actions are programmed at 13 00 16 00 and 19 00 The last progra...

Page 25: ...high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 4 Disinfection function This mode will disinfect...

Page 26: ...8 Option setup 8 00 Remote controller temperature control When using the remote control delivered with the unit 2 types of temperature control are possible Default 8 00 1 which means that the remote c...

Page 27: ...a certain temperature When enabled the indoor unit will deliver hot water to the domestic hot water tank if the reheat minimum value is reached The domestic water heating will continue until the rehe...

Page 28: ...the air removal from the circuit The pump can operate at different speed E 04 0 normal operation of the unit default E 04 1 low pump speed operation E 04 2 high pump speed operation If you select E 0...

Page 29: ...aving water thermo on request F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature maximum possible storage temperature b 03 H Domestic hot water reheat minimum te...

Page 30: ...Remote controller room temperature F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature maximum possible storage temperature b 03 H Domestic hot water reheat mini...

Page 31: ...t point requested during space heating operation The valve allowing water to enter the domestic hot water tank coil is open The heat pump will deliver water with a higher temperature which is needed f...

Page 32: ...rnal room thermostat Indoor unit Domestic hot water tank Temperature reducing device Space 1 Space 1 Space 2 Space 2 Balancing bottle Set point Field setting Thermo status Domestic hot water 70 C a a...

Page 33: ...ermostat control with remote controller room thermostat function and external room thermostat 1 When using the automatic weather dependent function for setting of space 0 you have to make sure that th...

Page 34: ...temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day selection Fri...

Page 35: ...re 70 45 75 1 C 04 Automatic maximum domestic hot water storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Set point leaving water maximum temperature 80 37 80 1 C 01 Set point lea...

Page 36: ...user interface will return to normal mode after 10 seconds or by pressing the z button once To test the space heating operation push the y button to start the test run operation 4 The test run operati...

Page 37: ...certain troubles which may occur in the unit This troubleshooting and related corrective actions may only be carried out by your local Daikin technician General guidelines Before starting the troubles...

Page 38: ...ake sure there is no air in the system purge air Check on the manometer that there is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Make sure that the...

Page 39: ...Contact your local dealer E1 Compressor PCB error Contact your local dealer E3 High pressure error S1PH Check wiring connections on outdoor unit and indoor unit Make sure the circuit is filled with wa...

Page 40: ...h 15 9 5 8 inch 15 9 5 8 inch Expansion vessel volume l 12 12 12 12 12 12 maximum working pressure MWP bar 4 4 4 4 4 4 Pump type DC motor DC motor DC motor DC motor DC motor DC motor no of speed inver...

Page 41: ...01 1 page 23 What type of appliance do you have No Blank display Push the b button n You selected permission level 3 on remote controller 0 00 3 page 20 You selected automatic leaving water control p...

Page 42: ...g on settings request w icon will start blinking with 0 5 second intervals Domestic hot water production will start immediately w icon will start blinking with 1 second intervals Choose start time 1 0...

Page 43: ...room thermostat control Yes Yes Yes 2 No Operation will switch to space heating Operation will switch to space heating Timer d 02 15 minutes passed since 2 No Space heating operation will continue til...

Page 44: ...NOTES 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...

Page 45: ...NOTES 4PW60970 1B_digital_EN book Page 2 Thursday September 2 2010 1 15 PM...

Page 46: ...NOTES 4PW60970 1B_digital_EN book Page 3 Thursday September 2 2010 1 15 PM...

Page 47: ...V1 Y1 NOTES 5 5 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...

Page 48: ...4PW60970 1B Copyright 2010 Daikin 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...

Reviews: