8
|
Piping installation
Installer reference guide
87
ERGA04~08EA + 08S18+23EA
Daikin Altherma 3 R F
4P629093-1A – 2021.11
FHL1...3
Floor heating loop (field supply)
HPC1...3
Heat pump convector (field supply)
T1...3
Individual room thermostat (optional)
M1...3
Individual motorised valve to control loop FHL1...3 and HPC1...3 (field supply)
INFORMATION
The pump of the additional zone ensures that the minimum flow rate for correct
operation of the unit is guaranteed.
Maximum water volume
Use the following graph to determine the maximum water volume for the
calculated pre-pressure.
0.3
0.5
1
1.5
2
2.4
50
20
100
150
200
250
290
a
b
a
Pre-pressure (bar)
b
Maximum water volume (l)
Example: Maximum water volume and expansion vessel pre-pressure
Installation
height
difference
(a)
Water volume
≤200 l
>200 l
≤7 m
No pre-pressure adjustment is
required.
Do the following:
▪
Decrease the pre-pressure
according to the required
installation
height
difference. The pre-pressure
should decrease by 0.1 bar
for each metre below 7 m.
▪
Check if the water volume
does
NOT
exceed
the
maximum allowed water
volume.
>7 m
Do the following:
▪
Increase the pre-pressure
according to the required
installation
height
difference. The pre-pressure
should increase by 0.1 bar
for each metre above 7 m.
▪
Check if the water volume
does
NOT
exceed
the
maximum allowed water
volume.
The expansion vessel of the
indoor unit is too small for the
installation. In this case, it is
recommended to install an
extra vessel outside the unit.