4/10
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.1
[4-06]
R/W
0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
9.1
[7-02]
R/W
0: Single zone
1: Dual zone
└─
Backup heater
9.1
[5-0D]
R/W (*2)
R/O (*1)
(*3)
0: 230V, 1~ (*1) (*2)
1: 230V, 3~ (*2)
2: 400V, 3~ (*3)
9.1
[4-0A]
R/W
0: 1 (*1)
1: 1/1+2 (*2) (*3)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.1
[6-03]
R/W
0~10kW, step: 0,2kW
2
kW (*2)
3kW (*1)(*3)
9.1
[6-04]
R/O (*1)
R/W (*2)
(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW (*3)
└─
Main zone
9.1
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
9.1
R/W
0: Fixed
2: Weather dependent
9.1
R/W
0: No
1: Yes
9.1
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
9.1
[1-01]
R/W
10~25°C, step: 1°C
15°C
9.1
[1-02]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.1
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
9.1
[1-06]
20
9.1
[1-07]
35
9.1
[1-08]
22
9.1
[1-09]
18
└─
Additional zone
9.1
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1
R/W
0: Fixed
2: Weather dependent
9.1
R/W
0: No
1: Yes
9.1
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.1
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
9.1
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.1
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
9.1
[0-04]
8
9.1
[0-05]
12
9.1
[0-06]
35
9.1
[0-07]
20
└─
Tank
9.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.1
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.1
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
└─
Domestic hot water
9.2.1
[E-05]
[E-06]
[E-07]
R/O
3: Integrated
9.2.2
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
9.2.4
[D-07]
R/W
0: No
1: Yes
└─
Back up heater
9.3.1
[E-03]
R/O
2: 3V (*1)
3: 6V (*2)
4: 9W (*3)
9.3.2
[5-0D]
R/W (*2)
R/O (*1)
(*3)
0: 230V, 1~ (*1) (*2)
1: 230V, 3~ (*2)
2: 400V, 3~ (*3)
9.3.3
[4-0A]
R/W
0: 1 (*1)
1: 1/1+2 (*2) (*3)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.3.4
[6-03]
R/W
0~10kW, step: 0,2kW
2
kW (*2)
3kW (*1)(*3)
9.3.5
[6-04]
R/O (*1)
R/W (*2)
(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW (*3)
Emergency
Number of zones
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Emitter type
Schedule
Emitter type
Setpoint mode
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Control
Setpoint mode
Schedule
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Heat up mode
Comfort setpoint
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Eco setpoint
Reheat setpoint
Domestic hot water
DHW pump
Solar
BUH type
Voltage
Configuration
Capacity step 1
Additional capacity step 2
--
--
--
--
--
--
--
--
4P629095-1A - 2021.02
(#) Setting is not applicable for this unit.
(*1) *3V_
(*2) *6V_
(*3) *9W