7 Installation
7.3.3 To fill the water circuit
1
Connect the water supply hose to the fill valve.
2
Open the fill valve.
3
Make sure that the automatic air purge valve is open (at least 2
turns).
4
Fill the circuit with water until the manometer indicates a
pressure of ±2.0 bar.
5
Purge as much air as possible from the water circuit.
6
Close the fill valve.
7
Disconnect the water supply hose from the fill valve.
7.3.4 To fill the domestic hot water tank
1
Open every hot water tap in turn to purge air from the system
pipe work.
2
Open the cold water supply valve.
3
Close all water taps after all air is purged.
4
Check for water leaks.
5
Manually operate the field installed pressure relief valve to
ensure that free water flow through the discharge pipe.
7.3.5 To insulate the water piping
The piping in the complete water circuit must be insulated to prevent
condensation during cooling operation and reduction of the heating
and cooling capacity.
If the temperature is higher than 30°C and the humidity is higher than
RH 80%, the thickness of the sealing materials should be at least
20 mm to prevent condensation on the surface of the sealing.
7.4
Connecting the electrical wiring
7.4.1 About electrical compliance
Only for ERLQERLQ008CAV3
Equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and
≤
75 A per phase.).
Only for indoor units
See To connect the backup heater power supply.
INFORMATION
For location of the air purge valve, see Components: Indoor
unit.
NOTICE
Q
Air in the water circuit can cause malfunctioning of the
backup heater. During filling, it may not be possible to
remove all the air from the circuit. Remaining air will be
removed through the automatic air purge valves during
the initial operating hours of the system. Additional
filling with water afterwards may be required.
Q
To purge the system, use the special function as
described in To perform an air purge. This function
should be used to purge the heat exchanger coil of the
domestic hot water tank.
NOTICE
The water pressure indicated on the manometer will vary
depending on the water temperature (higher pressure at
higher water temperature).
However, at all times water pressure shall remain above
1 bar to avoid air entering the circuit.
DANGER: RISK OF ELECTROCUTION
INFORMATION
More information about the legend and the location of the
wiring diagram of the unit can be found in Wiring diagram.