8 Configuration
Q
[C-04] Bivalent hysteresis: defines the temperature difference
between bivalent ON temperature and bivalent OFF
temperature.
Permission signal X1–X2 (
EKRP1HB
)
Bottom plate heater
Applies only to installation with an outdoor unit ERHQ and the option
bottom plate heater kit is installed.
Q
[F-02] Bottom plate heater ON temperature: defines the outdoor
temperature below which the bottom plate heater will be
activated by indoor unit in order to prevent ice build-up in the
bottom plate of the outdoor unit at lower outdoor temperatures.
Q
[F-03] Bottom plate heater hysteresis: defines the temperature
difference between bottom plate heater ON temperature and the
bottom plate heater OFF temperature.
Bottom plate heater
T
A
Outdoor temperature
CAUTION
Make sure to observe all rules mentioned in application
guideline 5 when bivalent operation function is enabled.
Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
INFORMATION
Q
The combination of setting [4-03]=0/2 with bivalent
operation at low outdoor temperature can result in
domestic hot water shortage.
Q
The bivalent operation function has no impact on the
domestic water heating mode. The domestic hot water
is still and only heated by the indoor unit.
Q
The permission signal for the auxiliary boiler is located
on the EKRP1HB (digital I/O PCB). When it is
activated, the contact X1, X2 is closed and open when
it is disactivated. See illustration below for the
schematic location of this contact.
#
Code
Description
N/A
[C-03]
ON temperature.
If the outdoor temperature drops below
this temperature, the bivalent heat
source permission signal will be active.
N/A
[C-04]
Hysteresis.
Temperature difference between bivalent
heat source ON and OFF to prevent too
much switching.
YC Y1 Y2 Y3 Y4
X1
X2
X3
X4
OFF ON
X2M
SS1
X1M
T
A
Outdoor temperature
CAUTION
The bottom plate heater is controlled via EKRP1HB.
#
Code
Description
N/A
[F-02]
Bottom plate heater ON temperature:
3~10°C
Default: 3°C
N/A
[F-03]
Hysteresis: 2~5°C
Default: 5°C
INFORMATION
Dependent from setting [F-04] contact Y2 located on digital
I/O PCB (EKRP1HB) controls the option bottom plate
heater. See illustration below for the schematic location of
this contact. For complete upwiring, see wiring diagram.
YC Y1
Y2
Y3 Y4
X1
X2
X3
X4
OFF ON
X2M
SS1
X1M