Installer reference guide
33
EHVH/X16
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
8 Configuration
[A.2.1.8]
[7-02]
The system can supply leaving water to
up to 2 water temperature zones. During
configuration, the number of water zones
must be set.
Number of LWT zones:
Q
0 (1 LWT zone)(default): Only 1
leaving water temperature zone.
This zone is called the main leaving
water temperature zone.
Q
1 (2 LWT zones): 2 leaving water
temperature zones. The zone with
the lowest leaving water
temperature (in heating) is called
the main leaving water temperature
zone. The zone with the highest
leaving water temperature (in
heating) is called the additional
leaving water temperature zone. In
practice, the main leaving water
temperature zone consists of the
higher load heat emitters and a
mixing station is installed to achieve
the desired leaving water
temperature.
#
Code
Description
[A.2.1.9]
[F-0D]
When the space heating/cooling control
is OFF by the user interface, the pump is
always OFF. When the space
heating/cooling control is On, you can
select the desired pump operation mode
(only applicable during space
heating/cooling)
Pump operation mode:
Q
0 (Continuous): Continuous pump
operation, regardless of thermo ON
or OFF condition. Remark:
continuous pump operation requires
more energy than sample or request
pump operation.
Q
1 (Sample)(default): The pump is
ON. When there is heating or
cooling demand as the the leaving
temperature has not reached the
desired temperature yet. When
thermo OFF condition occurs, the
pump runs every 5 minutes to check
the water temperature and demand
heating or cooling if necessary.
Remark: Sample is NOT available in
extended room thermostat control or
room thermostat control.
Q
2 (Request): Pump operation based
on request. Example: Using a room
thermostat creates thermo ON/OFF
condition. When there is no such
demand, the pump is OFF. Remark:
Request is NOT available in leaving
water temperature control.
#
Code
Description